SOLA 4000 - Operation
5 Operating Instructions
5.2Switching Off the UPS System / to Main- tenance Bypass
Initial UPS Operating Mode:
The UPS is in any operating mode described in the previous sections "Operating Modes" (except maintenance bypass opera- tion). All power switches except IBY are closed, and the load is fed either through the inverter or the static bypass.
|
| Operating Steps: | |
| A: | • Make sure that the LEDs 14 and 26 "Bypass Power Supply | |
|
|
| O.K." and "Bypass available" are illuminated and not flashing. |
|
| • | Press the pushbutton on the CPHC16 |
|
|
| the bypass supply. |
|
|
| The UPS or all UPS modules |
|
|
| "Bypass Operation" mode. The yellow LED 18 lights up. |
IBY |
| • | After LED 18 is illuminated, close the IBY switch. |
|
| The load is now supplied by the static bypass and the maintenance | |
|
| bypass in parallel. If more than one IBY switch is present, close all | |
|
| switches. | |
IUG: | B: | • | Open the IUG switch. |
IB: |
| • | Open the battery switch IB. |
IRE: |
| • | Open the IRE switch. |
IRP: |
| • | Open the IRP switch. |
After opening the IRP switch the display is only powered by the DC capacitors and will fade out within a few minutes.
C:• Repeat the steps in B for all units present.
Note: If the optional SOLA external maintenance bypass switch (MB3/2 - version 2) is installed, it is not necessary to perform step B if the switch is switched directly to position 3 "UPS ISOLATED" in step A
| . |
JUE 401266 | 69 |