Powerware SOLA 4000 manual Additional Start-Up Proced. for Multi-Unit Systems

Page 54

SOLA 4000 - Installation and Initial Start-Up

3 Additional Start-Up Proced. for Multi-Unit Systems

3ADDITIONAL START-UP PROCED. FOR MULTI-UNIT SYSTEMS

3.1Start-Up Procedure for Hot -standby Sys- tems

Repeat the procedure of section 2 for the second unit in the system (with the first unit off).

Ensure that the interconnecting BUS cable is connected according to section 1.9.1 and FIG 1.9.3.

J• Switch off the inverter at the second unit with PB2 at the top of the ICP pcb. The unit will transfer to the bypass supply.

Switch on IRP of the first unit.

Ensure that the switch IUG of this unit is off.

Switch on IRE of the first unit.

After approx. 10 seconds the display will flash with a "U" indica- tion and static bypass switch SSB will be closed.

Measure across the output switch IUG from input to output of each phase.

?Is this voltage less than 2V a.c for all three phases?

no The output power interconnections are incorrect and must be reconnected correctly. Switch off both units and the mains supply and recheck the connections.Return to J

yes Continue

Close IUG of the first unit. The two static bypasses (SSB) are now connected in parallel.

Close the battery switch of the first unit.

Start the unit by pressing "START" on the front operating panel.

when the inverter is synchronised, the unit will transfer the inverter to the output (SSI closes and both SSB switches switch off).

Press "START" on the operating panel of the second unit.

The inverter will start and become ready (check that the green LED LD6 on the ICP pcb is illuminated) but the static switch SSI will not close.

Check the commutation of the inverters by pressing PB2 at the top of the ICP pcb on the unit currently with SSI closed.

Restart the inverters (with PB2 on ICP or with "START").

THE SYSTEM IS NOW IN NORMAL OPERATION AND THE HOT-STANDBYSTART-UP

HAS BEEN SUCCESSFULLY COMPLETED.

JUE 401265

54

Image 54
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Safety Instructions Safety InstructionsSola 4000 Operating Manual Safety Instructions UPS Assembly Sola 4000 General System Description ChaptersUPS Assembly FeaturesSola 4000 General System Description Rectifier/Battery Charger UPS System StructureBattery Accumulator Static SwitchesInverter Under inverter failure conditions Maintenance Bypass Hot-Standby SystemsParallel-Redundant Systems Parallel SystemsFunctional Description Emergency Power OffOperating Panel Remote MonitoringAdditional START- UP Procedure for MULTI-UNIT SYSTEMS42 Sola 4000 Installation and Initial Start-Up ChaptersFiguresInstallation Initial START- UPSola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpInstallation Mechanical InstallationWeight Floor Space RequiredRoom Size for 10-60 kVA UPS 6 UPS 10-60kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC001 cabinet 7 UPS 80-120kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC002 cabinet 8 UPS 80-120kVA room size JUEElectrical Installation General1 UPS connection diagram, version Input Cables / Fuses Mm²2 UPS connection diagram, version Output / Battery Cables Input CablesInput Fuses Installation of additional optional cabi- nets Sola 4000 with isolation transformer of the bypass supply3 UPS connection diagram, with THD filters Sola 4000 with THD filters4 Installation of 12-pulse units without galvanic isolation Sola 4000 with 12-pulse charger / rectifierInstallation of an External Maintenance Bypass 1 External Maintenance Bypass Switch Version 1 2 position2 External Maintenance Bypass Switch Version 2 3 position Installation Cpnet Interface CardFunctions MOK Remote Emergency Power off 1 Connection of Remote EPO with N.C. contactDiesel Generator Operation Common Alarm Contacts Remote ResetInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation Installation of the Interconnection Cables 11.3 Location of connectors on the IBYBP-CP pcbBattery Installation 12.1 Internal Battery connections Internal Electrical ConnectionsInstallation of External Batteries 12.3 B3/38 battery trays in the second and the third levelInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection Between UPS and Additional Battery Cabinets Connection of Auxiliary ContactsStart-Up Procedure Initial Start-UpInitial START-UP ? Does this voltage have positive polarity? OK? Yes Static Switch Commutation CheckBattery Charging Current Limitation CheckStart-Up Procedure for Hot -standby Sys- tems Additional Start-Up Proced. for Multi-Unit SystemsAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters Operating Modes Operating ModesSola 4000 Operation GeneralLED Indication Operating Modes STAND-ALONE Unit Battery OperationOperating Modes Stand-alone Unit Normal OperationMaintenance Bypass Operation Bypass OperationStandby Operation Operating Modes Hot-Standby Operation Operating Modes HOT-STANDBY OperationOperation with an Inverter Failure Operating Modes Hot-Standby Operation Operating Modes Parallel and Parallel/Redundant Operation Partial Load OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Operating Instructions Switching On the UPS System / from Maintenance BypassInitial UPS Operating Mode Operating StepsFinal UPS Operating Mode Switching Off the UPS System / to Main- tenance Bypass CPHC16-SIPR IPRS1 ICPPB2 IRE IUG IRP Reset after Activating E.P.O Emergency Shut DownSola 4000 Operating Panel Chapters TablesSola 4000 Operating Panel Battery MonitoringFunctions Indication of Important DataUPS Operating Mode Indication Alarm signallingEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LEDs Battery Indicator LED 28 E.P.OLED 30 Boost Charge Communication with a PC Communication with a PCConnection to PC Snmp Mode Service ModeAlarms Oscillator failure Static switch failure SSIStatic switch failure SSB IUG monitoring failureUPS status MeteringPanel Settings DIP Switch SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Installation Remote PanelFunctions UPS =1...8 identifies the UPSDIP-switch settings UPSx Followed bySola 4000 PCB Description Chapters UPS Control LogicUPS Control Logic Sola 4000 PCB DescriptionUPS Control Logic Rectifier IF/PS R Front ViewReset MAX. Vdc CPHC16 R Front ViewInverter Reset ICP Front ViewICT-2 Front View TP5IPS-500 Front View IPR front view Bypass IF/PS S Front View CPHC16 S Front View BypassSystem Data Sola 4000 Technical DataBattery Data Rectifier DataSola 4000 Technical Data System DataRectifier Data Battery Data Battery DataInverter Data Inverter Data