Powerware SOLA 4000 manual Emergency Shut Down, Reset after Activating E.P.O

Page 72

SOLA 4000 - Operation

5 Operating Instructions

5.5 Emergency Power Off

Operating Steps:

To activate the Emergency Power Off, press simultaneously the two pushbuttons in the E.P.O. section of the operating panel (For hot-standby and parallel systems, the operation needs to be performed at one unit only).

Attention! This operation will remove all supply to the load.

Emergency Shut Down:

When E.P.O. is activated, all static switches SSI and SSB and the battery switch(es) IB (when connected with a trip circuit) are opened, the rectifier(s) and inverter(s) are switched off. The Data Monitor Panel / NCP will lose supply when the internal DC filter capacitors discharge.

Attention! Although the load is no longer supplied by the UPS, the input and output switches are still closed. Voltage is still present in the UPS unless the input circuit breaker(s) have a shunt trip circuit connected with the EPO circuit (see JUE 401066 "Installation and Initial Start-up", section 1.5).

 

Reset after Activating E.P.O.

RESET:

To restart the UPS press the RESET push-button PL2 located

 

 

on the CPU / NCP pcb inside the front door of the UPS. This

 

 

releases the EPO circuit and the rectifier will restart.

 

 

Note that if the input switch(es) were automatically tripped, it is

 

 

sufficient to reclose the switch(es) without the need to press the

 

 

reset pushbutton above.

 

Press the pushbutton at the front of the CPHC16-R pcb at the

 

 

right side of the UPS control electronic.

IB:

After the front panel is illuminated, close IB.

 

Repeat for all units in the system.

 

Press the "RESET" button for one second on the operating

 

 

panel.

 

Press the "START" button for one second on the operating

 

 

panel and repeat for all units in the system (if multiple units are

 

 

present).

Final UPS Operating Mode:

The UPS is returned to normal operation, and all power switches except IBY are closed.

JUE 401266

72

Image 72
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Safety Instructions Safety InstructionsSola 4000 Operating Manual Safety Instructions UPS Assembly Sola 4000 General System Description ChaptersUPS Assembly FeaturesSola 4000 General System Description Rectifier/Battery Charger UPS System StructureBattery Accumulator Static SwitchesInverter Under inverter failure conditions Maintenance Bypass Hot-Standby SystemsParallel-Redundant Systems Parallel SystemsEmergency Power Off Operating PanelFunctional Description Remote MonitoringSola 4000 Installation and Initial Start-Up ChaptersFigures InstallationAdditional START- UP Procedure for MULTI-UNIT SYSTEMS42 Initial START- UPSola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpInstallation Mechanical InstallationWeight Floor Space RequiredRoom Size for 10-60 kVA UPS 6 UPS 10-60kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC001 cabinet 7 UPS 80-120kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC002 cabinet 8 UPS 80-120kVA room size JUEElectrical Installation General1 UPS connection diagram, version Input Cables / Fuses Mm²2 UPS connection diagram, version Output / Battery Cables Input CablesInput Fuses Installation of additional optional cabi- nets Sola 4000 with isolation transformer of the bypass supply3 UPS connection diagram, with THD filters Sola 4000 with THD filters4 Installation of 12-pulse units without galvanic isolation Sola 4000 with 12-pulse charger / rectifierInstallation of an External Maintenance Bypass 1 External Maintenance Bypass Switch Version 1 2 position2 External Maintenance Bypass Switch Version 2 3 position Installation Cpnet Interface CardFunctions MOK Remote Emergency Power off 1 Connection of Remote EPO with N.C. contactDiesel Generator Operation Common Alarm Contacts Remote ResetInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation Installation of the Interconnection Cables 11.3 Location of connectors on the IBYBP-CP pcbBattery Installation 12.1 Internal Battery connections Internal Electrical ConnectionsInstallation of External Batteries 12.3 B3/38 battery trays in the second and the third levelInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection Between UPS and Additional Battery Cabinets Connection of Auxiliary ContactsStart-Up Procedure Initial Start-UpInitial START-UP ? Does this voltage have positive polarity? OK? Static Switch Commutation Check Battery Charging Current LimitationYes CheckStart-Up Procedure for Hot -standby Sys- tems Additional Start-Up Proced. for Multi-Unit SystemsAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters Operating Modes Sola 4000 OperationOperating Modes GeneralLED Indication Battery Operation Operating Modes Stand-alone UnitOperating Modes STAND-ALONE Unit Normal OperationMaintenance Bypass Operation Bypass OperationStandby Operation Operating Modes Hot-Standby Operation Operating Modes HOT-STANDBY OperationOperation with an Inverter Failure Operating Modes Hot-Standby Operation Operating Modes Parallel and Parallel/Redundant Operation Partial Load OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Switching On the UPS System / from Maintenance Bypass Initial UPS Operating ModeOperating Instructions Operating StepsFinal UPS Operating Mode Switching Off the UPS System / to Main- tenance Bypass CPHC16-SIPR IPRS1 ICPPB2 IRE IUG IRP Reset after Activating E.P.O Emergency Shut DownSola 4000 Operating Panel Chapters TablesBattery Monitoring FunctionsSola 4000 Operating Panel Indication of Important DataUPS Operating Mode Indication Alarm signallingEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LEDs Battery Indicator LED 28 E.P.OLED 30 Boost Charge Communication with a PC Communication with a PCConnection to PC Snmp Mode Service ModeAlarms Static switch failure SSI Static switch failure SSBOscillator failure IUG monitoring failureUPS status MeteringPanel Settings DIP Switch SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Installation Remote PanelFunctions UPS =1...8 identifies the UPSDIP-switch settings UPSx Followed bySola 4000 PCB Description Chapters UPS Control LogicUPS Control Logic Sola 4000 PCB DescriptionUPS Control Logic Rectifier IF/PS R Front ViewReset MAX. Vdc CPHC16 R Front ViewInverter Reset ICP Front ViewICT-2 Front View TP5IPS-500 Front View IPR front view Bypass IF/PS S Front View CPHC16 S Front View BypassSola 4000 Technical Data Battery DataSystem Data Rectifier DataSola 4000 Technical Data System DataRectifier Data Battery Data Battery DataInverter Data Inverter Data