Powerware SOLA 4000 Operating Modes Parallel and Parallel/Redundant Operation, Battery Operation

Page 65

SOLA 4000 - Operation

4 Operating Modes Parallel and Parallel/Redundant Operation

4.3 Battery Operation

The "Battery Operation" mode is activated by a mains failure or rectifier failure

The rectifiers supply no power

The batteries supply the required d.c. power to the inverters

The inverters supply a.c. power to the load as described in 4.1

Power will only be supplied to the load for a certain period of time depending on the battery capacity

If there were stand-by units switched off at the time of the mains failure, all units will automatically switch ON in order to extend the battery autonomy time.

4.4 Operation with an Inverter Failure

This operating mode is activated by a failure in one or more invert- ers.

As long as the load is not too great for the remaining units, the parallel system will stay in UPS (inverter) operation mode, otherwise see 4.5.

The static inverter-switch(es) (SSI) of the defective unit(s) will open automatically, separating them from the load-busbar

The rectifier(s) of the defective unit(s) will supply d.c. power to the battery (batteries) only if the respective rectifier is not defective.

JUE 401266

65

Image 65
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Sola 4000 Operating Manual Safety InstructionsSafety Instructions Safety Instructions Sola 4000 General System Description Chapters UPS AssemblySola 4000 General System Description UPS AssemblyFeatures UPS System Structure Rectifier/Battery ChargerInverter Battery AccumulatorStatic Switches Under inverter failure conditions Hot-Standby Systems Maintenance BypassParallel Systems Parallel-Redundant SystemsOperating Panel Emergency Power OffFunctional Description Remote MonitoringInstallation Sola 4000 Installation and Initial Start-Up ChaptersFiguresAdditional START- UP Procedure for MULTI-UNIT SYSTEMS42 Initial START- UPSola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpMechanical Installation InstallationFloor Space Required Weight6 UPS 10-60kVA room size JUE Room Size for 10-60 kVA UPS7 UPS 80-120kVA room size JUE Room Size for 80-120 kVA UPS with auxiliary AC001 cabinet8 UPS 80-120kVA room size JUE Room Size for 80-120 kVA UPS with auxiliary AC002 cabinetGeneral Electrical Installation1 UPS connection diagram, version Mm² Input Cables / Fuses2 UPS connection diagram, version Input Fuses Output / Battery CablesInput Cables Sola 4000 with isolation transformer of the bypass supply Installation of additional optional cabi- netsSola 4000 with THD filters 3 UPS connection diagram, with THD filtersSola 4000 with 12-pulse charger / rectifier 4 Installation of 12-pulse units without galvanic isolation1 External Maintenance Bypass Switch Version 1 2 position Installation of an External Maintenance Bypass2 External Maintenance Bypass Switch Version 2 3 position Functions InstallationCpnet Interface Card MOK 1 Connection of Remote EPO with N.C. contact Remote Emergency Power offDiesel Generator Operation Remote Reset Common Alarm ContactsInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation 11.3 Location of connectors on the IBYBP-CP pcb Installation of the Interconnection CablesBattery Installation Internal Electrical Connections 12.1 Internal Battery connections12.3 B3/38 battery trays in the second and the third level Installation of External BatteriesInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection of Auxiliary Contacts Connection Between UPS and Additional Battery CabinetsInitial START-UP Start-Up ProcedureInitial Start-Up ? Does this voltage have positive polarity? OK? Battery Charging Current Limitation Static Switch Commutation CheckYes CheckAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Hot -standby Sys- temsAdditional Start-Up Proced. for Multi-Unit Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters Sola 4000 Operation Operating ModesOperating Modes GeneralLED Indication Operating Modes Stand-alone Unit Battery OperationOperating Modes STAND-ALONE Unit Normal OperationStandby Operation Maintenance Bypass OperationBypass Operation Operation with an Inverter Failure Operating Modes Hot-Standby OperationOperating Modes HOT-STANDBY Operation Operating Modes Hot-Standby Operation Partial Load Operation Operating Modes Parallel and Parallel/Redundant OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Initial UPS Operating Mode Switching On the UPS System / from Maintenance BypassOperating Instructions Operating StepsFinal UPS Operating Mode CPHC16-S Switching Off the UPS System / to Main- tenance BypassIPR IPRS1 ICPPB2 IRE IUG IRP Emergency Shut Down Reset after Activating E.P.OTables Sola 4000 Operating Panel ChaptersFunctions Battery MonitoringSola 4000 Operating Panel Indication of Important DataAlarm signalling UPS Operating Mode IndicationEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LED 28 E.P.O LEDs Battery IndicatorLED 30 Boost Charge Connection to PC Communication with a PCCommunication with a PC Service Mode Snmp ModeAlarms Static switch failure SSB Static switch failure SSIOscillator failure IUG monitoring failureMetering UPS statusDIP Switch Settings Panel SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Remote Panel InstallationUPS =1...8 identifies the UPS FunctionsUPSx Followed by DIP-switch settingsUPS Control Logic Sola 4000 PCB Description ChaptersUPS Control Logic UPS Control LogicSola 4000 PCB Description IF/PS R Front View RectifierCPHC16 R Front View Reset MAX. VdcInverter ICP Front View ResetTP5 ICT-2 Front ViewIPS-500 Front View IPR front view Bypass IF/PS S Front View Bypass CPHC16 S Front ViewBattery Data Sola 4000 Technical DataSystem Data Rectifier DataSystem Data Sola 4000 Technical DataRectifier Data Battery Data Battery DataInverter Data Inverter Data