Powerware SOLA 4000 manual DIP-switch settings, UPSx Followed by

Page 91

SOLA 4000 - Operating Panel

5 Remote Panel

Communication timing When an alarm condition occurs, the Remote Panel calls the first programmed number.

If the line is busy and only one number is to be called, the Remote Panel waits for 5 minutes and, if the alarm condition is still present, it tries to call the number again. This procedure will be repeated until the connection has been established or the alarm condition ends.

If the line is busy and two numbers are to be called, the second number will be called. If this line is also busy the first number will be tried again and so on.

After a successful connection the Remote Panel will normally hold the line for five minutes. Any additional alarm messages that are activated during that time will be displayed automatically at the computer display and one minute will be added to the remaining connection time. The maximum connection time is, however, limited to ten minutes.

If during the connection all alarms are deactivated, the Remote

Panel sends the following messages:

UPSx

followed by:

UPS OK

and the remaining connection time is set to one minute.

5.4 DIP-switch settings

DIP Switch DIP1

 

switch 1

 

Not used

 

ON

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

switch 2

 

Local buzzer

 

 

 

 

 

 

ON

 

active

 

 

 

 

 

 

OFF

 

not active

 

switch 3

 

Automatic call

 

ON

 

active

 

 

 

 

 

 

OFF

 

not active

 

switch 4

 

Phone numbers

 

 

 

 

 

 

ON

 

two phone numbers

 

 

 

 

 

 

OFF

 

one phone number

 

 

 

 

 

 

switch 5

 

Not used

 

 

 

 

 

 

ON

 

-

 

 

 

 

 

 

OFF

 

-

sw. 6

sw. 7

 

sw. 8

UPS number for

 

identification

 

 

 

 

 

 

 

 

 

ON

ON

 

ON

1

 

 

 

 

 

OFF

ON

 

ON

2

 

 

 

 

 

ON

OFF

 

ON

3

 

 

 

 

 

OFF

OFF

 

ON

4

 

 

 

 

 

ON

ON

 

OFF

5

 

 

 

 

 

OFF

ON

 

OFF

6

 

 

 

 

 

ON

OFF

 

OFF

7

 

 

 

 

 

OFF

OFF

 

OFF

8

FIG. 5.1 - Setting of DIP1

JUE 401267

91

Image 91
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Safety Instructions Safety InstructionsSola 4000 Operating Manual Safety Instructions Sola 4000 General System Description Chapters UPS AssemblyFeatures UPS AssemblySola 4000 General System Description UPS System Structure Rectifier/Battery ChargerStatic Switches Battery AccumulatorInverter Under inverter failure conditions Hot-Standby Systems Maintenance BypassParallel Systems Parallel-Redundant SystemsRemote Monitoring Emergency Power OffOperating Panel Functional DescriptionInitial START- UP Sola 4000 Installation and Initial Start-Up ChaptersFiguresInstallation Additional START- UP Procedure for MULTI-UNIT SYSTEMS42Sola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpMechanical Installation InstallationFloor Space Required Weight6 UPS 10-60kVA room size JUE Room Size for 10-60 kVA UPS7 UPS 80-120kVA room size JUE Room Size for 80-120 kVA UPS with auxiliary AC001 cabinet8 UPS 80-120kVA room size JUE Room Size for 80-120 kVA UPS with auxiliary AC002 cabinetGeneral Electrical Installation1 UPS connection diagram, version Mm² Input Cables / Fuses2 UPS connection diagram, version Input Cables Output / Battery CablesInput Fuses Sola 4000 with isolation transformer of the bypass supply Installation of additional optional cabi- netsSola 4000 with THD filters 3 UPS connection diagram, with THD filtersSola 4000 with 12-pulse charger / rectifier 4 Installation of 12-pulse units without galvanic isolation1 External Maintenance Bypass Switch Version 1 2 position Installation of an External Maintenance Bypass2 External Maintenance Bypass Switch Version 2 3 position Cpnet Interface Card InstallationFunctions MOK 1 Connection of Remote EPO with N.C. contact Remote Emergency Power offDiesel Generator Operation Remote Reset Common Alarm ContactsInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation 11.3 Location of connectors on the IBYBP-CP pcb Installation of the Interconnection CablesBattery Installation Internal Electrical Connections 12.1 Internal Battery connections12.3 B3/38 battery trays in the second and the third level Installation of External BatteriesInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection of Auxiliary Contacts Connection Between UPS and Additional Battery CabinetsInitial Start-Up Start-Up ProcedureInitial START-UP ? Does this voltage have positive polarity? OK? Check Static Switch Commutation CheckBattery Charging Current Limitation YesAdditional Start-Up Proced. for Multi-Unit Systems Start-Up Procedure for Hot -standby Sys- temsAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters General Operating ModesSola 4000 Operation Operating ModesLED Indication Normal Operation Battery OperationOperating Modes Stand-alone Unit Operating Modes STAND-ALONE UnitBypass Operation Maintenance Bypass OperationStandby Operation Operating Modes HOT-STANDBY Operation Operating Modes Hot-Standby OperationOperation with an Inverter Failure Operating Modes Hot-Standby Operation Partial Load Operation Operating Modes Parallel and Parallel/Redundant OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Operating Steps Switching On the UPS System / from Maintenance BypassInitial UPS Operating Mode Operating InstructionsFinal UPS Operating Mode CPHC16-S Switching Off the UPS System / to Main- tenance BypassIPR IPRS1 ICPPB2 IRE IUG IRP Emergency Shut Down Reset after Activating E.P.OTables Sola 4000 Operating Panel ChaptersIndication of Important Data Battery MonitoringFunctions Sola 4000 Operating PanelAlarm signalling UPS Operating Mode IndicationEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LED 28 E.P.O LEDs Battery IndicatorLED 30 Boost Charge Communication with a PC Communication with a PCConnection to PC Service Mode Snmp ModeAlarms IUG monitoring failure Static switch failure SSIStatic switch failure SSB Oscillator failureMetering UPS statusDIP Switch Settings Panel SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Remote Panel InstallationUPS =1...8 identifies the UPS FunctionsUPSx Followed by DIP-switch settingsUPS Control Logic Sola 4000 PCB Description ChaptersSola 4000 PCB Description UPS Control LogicUPS Control Logic IF/PS R Front View RectifierCPHC16 R Front View Reset MAX. VdcInverter ICP Front View ResetTP5 ICT-2 Front ViewIPS-500 Front View IPR front view Bypass IF/PS S Front View Bypass CPHC16 S Front ViewRectifier Data Sola 4000 Technical DataBattery Data System DataSystem Data Sola 4000 Technical DataRectifier Data Battery Data Battery DataInverter Data Inverter Data