Powerware SOLA 4000 manual Alarms

Page 83

SOLA 4000 - Operating Panel

3 Communication with a PC

3.4 Alarms

With a connected PC, the following alarms are realised (SNMP and service modes):

Rectifier Failure The Rectifier mains is in order but a failure is present within the rectifier.

Inverter Failure The inverter is ON but the inverter voltage or inverter conditions are not in order.

Battery Switch OFF The battery switch is OFF

Retransfer blocked The inverter has attempted unsuccesfully to take over the load at least 5 times within 3 minutes.

To reset, press the "RESET" pushbutton a second time after muting the alarm.

Overtemperature The inverter/rectifier components are operating at an excessive temperature. This can be due to extreme environmental conditions or a failure within the inverter or rectifier sections.

If the bypass is available the UPS transfers immediately to the bypass supply (in the case of a hot-standby system, the second unit takes over the load, in the case of a parallel system the re- maining inverters take over the load). If the bypass or another inverter is not available then the UPS will continue to supply the load for a further 10 minutes before shutting down.

Mains Failure The mains is not present or not within the specified voltage and frequency tolerances.

Inverter not Feeding The inverter is not feeding the load and the bypass static switch, SSI is OFF.

Battery Discharging The mains or rectifier has failed and the batteries are discharging.This alarm is activated at a battery voltage of approx. 360Vdc.

Low Battery The remaining battery capacity during discharge has been calcu-

lated to be less than 20% of the nominal capacity.

Battery Test Failed The routine battery test has detected a decrease in capacity of the battery. The battery must be checked.

Paralleling Fault The inverter has failed to regulate correctly in parallel operation

with another inverter (parallel systems only).

Bypass not Available The bypass mains supply is OK but the bypass is not available to take the load if the inverter fails (the inverter is not synchronised or is blocked externally).

JUE 401267

83

Image 83
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Sola 4000 Operating Manual Safety InstructionsSafety Instructions Safety Instructions Sola 4000 General System Description Chapters UPS AssemblySola 4000 General System Description UPS AssemblyFeatures UPS System Structure Rectifier/Battery ChargerInverter Battery AccumulatorStatic Switches Under inverter failure conditions Hot-Standby Systems Maintenance BypassParallel Systems Parallel-Redundant SystemsRemote Monitoring Emergency Power OffOperating Panel Functional DescriptionInitial START- UP Sola 4000 Installation and Initial Start-Up ChaptersFiguresInstallation Additional START- UP Procedure for MULTI-UNIT SYSTEMS42Sola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpMechanical Installation InstallationFloor Space Required Weight6 UPS 10-60kVA room size JUE Room Size for 10-60 kVA UPS7 UPS 80-120kVA room size JUE Room Size for 80-120 kVA UPS with auxiliary AC001 cabinet8 UPS 80-120kVA room size JUE Room Size for 80-120 kVA UPS with auxiliary AC002 cabinetGeneral Electrical Installation1 UPS connection diagram, version Mm² Input Cables / Fuses2 UPS connection diagram, version Input Fuses Output / Battery CablesInput Cables Sola 4000 with isolation transformer of the bypass supply Installation of additional optional cabi- netsSola 4000 with THD filters 3 UPS connection diagram, with THD filtersSola 4000 with 12-pulse charger / rectifier 4 Installation of 12-pulse units without galvanic isolation1 External Maintenance Bypass Switch Version 1 2 position Installation of an External Maintenance Bypass2 External Maintenance Bypass Switch Version 2 3 position Functions InstallationCpnet Interface Card MOK 1 Connection of Remote EPO with N.C. contact Remote Emergency Power offDiesel Generator Operation Remote Reset Common Alarm ContactsInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation 11.3 Location of connectors on the IBYBP-CP pcb Installation of the Interconnection CablesBattery Installation Internal Electrical Connections 12.1 Internal Battery connections12.3 B3/38 battery trays in the second and the third level Installation of External BatteriesInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection of Auxiliary Contacts Connection Between UPS and Additional Battery CabinetsInitial START-UP Start-Up ProcedureInitial Start-Up ? Does this voltage have positive polarity? OK? Check Static Switch Commutation CheckBattery Charging Current Limitation YesAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Hot -standby Sys- temsAdditional Start-Up Proced. for Multi-Unit Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters General Operating ModesSola 4000 Operation Operating ModesLED Indication Normal Operation Battery OperationOperating Modes Stand-alone Unit Operating Modes STAND-ALONE UnitStandby Operation Maintenance Bypass OperationBypass Operation Operation with an Inverter Failure Operating Modes Hot-Standby OperationOperating Modes HOT-STANDBY Operation Operating Modes Hot-Standby Operation Partial Load Operation Operating Modes Parallel and Parallel/Redundant OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Operating Steps Switching On the UPS System / from Maintenance BypassInitial UPS Operating Mode Operating InstructionsFinal UPS Operating Mode CPHC16-S Switching Off the UPS System / to Main- tenance BypassIPR IPRS1 ICPPB2 IRE IUG IRP Emergency Shut Down Reset after Activating E.P.OTables Sola 4000 Operating Panel ChaptersIndication of Important Data Battery MonitoringFunctions Sola 4000 Operating PanelAlarm signalling UPS Operating Mode IndicationEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LED 28 E.P.O LEDs Battery Indicator LED 30 Boost Charge Connection to PC Communication with a PCCommunication with a PC Service Mode Snmp ModeAlarms IUG monitoring failure Static switch failure SSIStatic switch failure SSB Oscillator failureMetering UPS statusDIP Switch Settings Panel SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Remote Panel InstallationUPS =1...8 identifies the UPS FunctionsUPSx Followed by DIP-switch settingsUPS Control Logic Sola 4000 PCB Description ChaptersUPS Control Logic UPS Control LogicSola 4000 PCB Description IF/PS R Front View RectifierCPHC16 R Front View Reset MAX. VdcInverter ICP Front View ResetTP5 ICT-2 Front ViewIPS-500 Front View IPR front view Bypass IF/PS S Front View Bypass CPHC16 S Front ViewRectifier Data Sola 4000 Technical DataBattery Data System DataSystem Data Sola 4000 Technical DataRectifier Data Battery Data Battery DataInverter Data Inverter Data