SOLA 4000 - Operating Manual
Safety Instructions
Earth leakage protection: this device has a high leakage current towards protective earthing. The maximum earth leakage current is 300 mA. When setting the threshold of the earth leakage circuit breaker installed upstream from this equipment consider this amount of current and that due to the loads.
All primary power switches installed downstream of the UPS must be labelled as follows: "Isolate UPS (Uninterruptible Power Supply) before working on this circuit.
The unit is provided with the E.P.O. (Emergency Power Off) function. This function is activated by pressing simultaneously the two push buttons on the bottom part of the Front Panel. This function provides UPS disconnection from the load and from the battery. Dangerous voltages will still be present inside the unit, if a
During electrolysis, batteries release hydrogen gas. There is a risk of an explosion if the amount of hydrogen in the battery room becomes too high. Ensure appropriate ventilation of the battery room according to the standard