SOLA 4000 - Operating Panel
1 Functions
1 FUNCTIONS
1.1 Indication of Important Data
Actual Load The actual load of the UPS is indicated as a percentage of its nominal load capacity.
Battery Charging Status While the battery is being charged (green LED 5 on), the actual charging status of the battery is indicated as a percentage of the nominal battery capacity.
Battery Autonomy While the battery is being discharged (yellow LED 4 on), the actual battery autonomy is indicated as a percentage of the nominal battery autonomy.
1.2 Battery Monitoring
Low Battery The Low Battery alarm indicates that only 20% of the battery autonomy is left. The colour of the LEDs for battery autonomy indication changes from green to red. In addition the alarm buzzer beeps.
Battery Test The SOLA 4000 UPS automatically performs a battery test every 30 days.
Whenever the test shows that the battery is damaged or its capac- ity is reduced, the red LED "BATTERY TEST", located on the operating panel is illuminated and the buzzer beeps.
This test is of vital importance, since it monitors the battery, warn- ing of possible failures caused by reduced battery autonomy due to defective batteries.
However this function can be deactivated with DSW2 - 3 on the CPU/NCP pcb inside the UPS front door. In this case the LED "BATTERY TEST" is off.
JUE 401267