SOLA 4000 - Operating Panel
4 Panel Settings
4 PANEL SETTINGS
4.1 DIP Switch Settings
With the DIP switches SW1 and SW2 on the CPU/NCP pcb inside the front door , the operating parameters can be set according to actual conditions.
Note: The following settings apply only with the software V2.0 or later.
DIP Switch SW1
Dip 1 | Dip 2 | Dip 3 | Dip 4 | UPS RATING | |
(KVA) | |||||
|
|
|
| ||
|
|
|
|
| |
OFF | OFF | OFF | OFF | 10 | |
|
|
|
|
| |
ON | OFF | OFF | OFF | 15 | |
|
|
|
|
| |
OFF | ON | OFF | OFF | 20 | |
|
|
|
|
| |
ON | ON | OFF | OFF | 30 | |
|
|
|
|
| |
OFF | OFF | ON | OFF | 40 | |
|
|
|
|
| |
ON | OFF | ON | OFF | 60 | |
|
|
|
|
| |
OFF | ON | ON | OFF | 80 | |
|
|
|
|
| |
ON | ON | ON | OFF | 100 | |
|
|
|
|
| |
OFF | OFF | OFF | ON | 120 | |
|
|
|
|
|
TAB. 4.1 - Setting of SW1 - UPS rating
DIP Switch SW1
DIP 5 | CONFIGURATION |
|
|
OFF | Not |
|
|
ON | |
|
|
DIP 6 | BYPASS - LINE |
|
|
OFF | Installed |
|
|
ON | Not installed |
|
|
TAB. 4.2 - Setting of SW1
DIP Switch SW1
Nominal Voltage
DIP 7 | DIP 8 | Vnom |
|
|
|
OFF | OFF | 120 |
|
|
|
ON | OFF | 220 |
|
|
|
OFF | ON | 230 |
|
|
|
ON | ON | 240 |
|
|
|
TAB. 4.3 - Setting of SW1 Nominal Voltage