SOLA 4000 - PCB Description
1 UPS Control Logic
CPHC16 - R Front View
DIAGNOSTICS
RESET MAX. Vdc
FIG. 1.2 illustrates the display, switches and connectors of the CPHC16 - R PCB which are accessible from the front.
-7 segment display for diagnostics (see table below)
-Reset max. Vdc pushbutton: press when the character "4" is displayed or the central segment is blinking.
-Reset Boost Charge Alarm
-Reset after EPO (V2.1)
RS 232
- RS232 connector (male)
RS 485
- RS485 connector (female)
Priority | Indication | Diagnostics |
|
|
|
1 | 8 | E²PROM failure |
|
|
|
2 | 2 | Fuse blown |
|
|
|
3 | C | Mains not OK |
|
|
|
4 | P | Wrong phase rotation |
|
|
|
5 | 3 | Overtemperature |
|
|
|
6 | 4 | Overvoltage |
|
|
|
7 | Ø | Pulse release missing |
|
|
|
8 | 9 | Rectifier failure |
|
|
|
9 | 6 | Fan failure |
|
|
|
10 | L | Overload |
|
|
|
| Boost charge | |
|
|
|
|
| (when blinking) |
|
| Has left the boost |
|
| charge due to a given |
| time limit but the | |
| battery was not | |
|
| |
|
| completely charged. |
|
| Reset with "RESET |
|
| max. Vdc" above. |
|
|
|
JUE 401268 | 95 |