Powerware SOLA 4000 manual Functions, UPS =1...8 identifies the UPS

Page 90

SOLA 4000 - Operating Panel

5 Remote Panel

5.3 Functions

General The Remote Panel provides the same LED indications as the SOLA 4000 operating panel. Alarms are indicated by flashing LEDs and an integrated buzzer. The alarms can be muted directly at the Remote Panel by pressing the "Alarm Reset" push-button.

The buzzer can be deactivated by setting switch 2 of DIP1 to the Off position. The inverter can be switched on from the remote panel but cannot be switched off.

Automatic alarm phone calls The Remote Panel can be connected to an external modem through the RS232 DB9 connector, in order to perform an auto- matic phone call to one or two programmed phone numbers (corre- sponding to Computers in host Mode), in case of one of the below listed alarm conditions:

RETRANSFER BLOCKED

BATTERY TEST FAILURE

INVERTER FAILURE

LOAD ON BYPASS

RECTIFIER FAILURE

The automatic call feature is enabled by setting switch 3 of DIP1 to the ON position.

One computer can receive alarm messages from 8 different Re- mote Panels. The Remote Panels (and hence the connected UPS) can be identified by a number from 1 to 8 which is binarily pro- grammed by setting the switches 6,7 and 8 of DIP1.

In case of an alarm at a certain UPS the corresponding Remote Panel calls the computer and transmits a two line alarm message (ASCII characters) with the following structure:

UPS x

x =1...8 identifies the UPS

Alarm condition One or more of the above listed alarms

Programming of phone numbers In case of an alarm one or two phone numbers may be called automatically, i.e. the UPS status may be monitored by one com- puter only or by two different computers. With switch 4 of DIP1 the number of computers to be called can be set.

To program the phone numbers to be called connect a PC with a serial interface to the RS232 DB9 connector on the rear side of the Remote Panel and run a terminal program.

Type

P1XXXXX...X[CR]

P2YYYYY...Y[CR]

to program the first phone number (XXXXX...X)

to program the second phone number (YYYYY...Y)

Each phone number may contain up to 20 digits.

To read programmed phone numbers from the panel type

N1[CR]

N1=XXXXX...X

N2[CR]

N2=YYYYY...Y

The Remote Panel responds with the first number:

The Remote Panel responds with the second number:

The programmed numbers are stored in an EEPROM and are thus protected against power failures and CPU resets.

JUE 401267

90

Image 90
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Safety Instructions Safety InstructionsSola 4000 Operating Manual Safety Instructions UPS Assembly Sola 4000 General System Description ChaptersUPS Assembly FeaturesSola 4000 General System Description Rectifier/Battery Charger UPS System StructureBattery Accumulator Static SwitchesInverter Under inverter failure conditions Maintenance Bypass Hot-Standby SystemsParallel-Redundant Systems Parallel SystemsFunctional Description Emergency Power OffOperating Panel Remote MonitoringAdditional START- UP Procedure for MULTI-UNIT SYSTEMS42 Sola 4000 Installation and Initial Start-Up ChaptersFiguresInstallation Initial START- UPSola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpInstallation Mechanical InstallationWeight Floor Space RequiredRoom Size for 10-60 kVA UPS 6 UPS 10-60kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC001 cabinet 7 UPS 80-120kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC002 cabinet 8 UPS 80-120kVA room size JUEElectrical Installation General1 UPS connection diagram, version Input Cables / Fuses Mm²2 UPS connection diagram, version Output / Battery Cables Input CablesInput Fuses Installation of additional optional cabi- nets Sola 4000 with isolation transformer of the bypass supply3 UPS connection diagram, with THD filters Sola 4000 with THD filters4 Installation of 12-pulse units without galvanic isolation Sola 4000 with 12-pulse charger / rectifierInstallation of an External Maintenance Bypass 1 External Maintenance Bypass Switch Version 1 2 position2 External Maintenance Bypass Switch Version 2 3 position Installation Cpnet Interface CardFunctions MOK Remote Emergency Power off 1 Connection of Remote EPO with N.C. contactDiesel Generator Operation Common Alarm Contacts Remote ResetInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation Installation of the Interconnection Cables 11.3 Location of connectors on the IBYBP-CP pcbBattery Installation 12.1 Internal Battery connections Internal Electrical ConnectionsInstallation of External Batteries 12.3 B3/38 battery trays in the second and the third levelInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection Between UPS and Additional Battery Cabinets Connection of Auxiliary ContactsStart-Up Procedure Initial Start-UpInitial START-UP ? Does this voltage have positive polarity? OK? Yes Static Switch Commutation CheckBattery Charging Current Limitation CheckStart-Up Procedure for Hot -standby Sys- tems Additional Start-Up Proced. for Multi-Unit SystemsAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters Operating Modes Operating ModesSola 4000 Operation GeneralLED Indication Operating Modes STAND-ALONE Unit Battery OperationOperating Modes Stand-alone Unit Normal OperationMaintenance Bypass Operation Bypass OperationStandby Operation Operating Modes Hot-Standby Operation Operating Modes HOT-STANDBY OperationOperation with an Inverter Failure Operating Modes Hot-Standby Operation Operating Modes Parallel and Parallel/Redundant Operation Partial Load OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Operating Instructions Switching On the UPS System / from Maintenance BypassInitial UPS Operating Mode Operating StepsFinal UPS Operating Mode Switching Off the UPS System / to Main- tenance Bypass CPHC16-SIPR IPRS1 ICPPB2 IRE IUG IRP Reset after Activating E.P.O Emergency Shut DownSola 4000 Operating Panel Chapters TablesSola 4000 Operating Panel Battery MonitoringFunctions Indication of Important DataUPS Operating Mode Indication Alarm signallingEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LEDs Battery Indicator LED 28 E.P.OLED 30 Boost Charge Communication with a PC Communication with a PCConnection to PC Snmp Mode Service ModeAlarms Oscillator failure Static switch failure SSIStatic switch failure SSB IUG monitoring failureUPS status MeteringPanel Settings DIP Switch SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Installation Remote PanelFunctions UPS =1...8 identifies the UPSDIP-switch settings UPSx Followed bySola 4000 PCB Description Chapters UPS Control LogicUPS Control Logic Sola 4000 PCB DescriptionUPS Control Logic Rectifier IF/PS R Front ViewReset MAX. Vdc CPHC16 R Front ViewInverter Reset ICP Front ViewICT-2 Front View TP5IPS-500 Front View IPR front view Bypass IF/PS S Front View CPHC16 S Front View BypassSystem Data Sola 4000 Technical DataBattery Data Rectifier DataSola 4000 Technical Data System DataRectifier Data Battery Data Battery DataInverter Data Inverter Data