4.Route the AC wires to the input connector terminals as required. To connect the wires, loosen the terminal screw, insert the stripped wire into the terminal and tighten the screw securely (4.4-5.3 Lb-inch).

5.Route the wires inside the cover to prevent pinching. Fasten the cover to the unit using the M3x8 Flat Head screws provided. Refer to Fig.3-3 for details.

L N

Cover

M3x8

Flat Head screws

(2 places)

Assembled Strain Relief

Fig.3-3: AC input cover and strain relief, 1500W models

3.8 TURN-ON CHECKOUT PROCEDURE

3.8.1General

The following procedure ensures that the power supply is operational and may be used as a basic in- coming inspection check. Refer to Fig. 4-1 and fig. 4-2 for the location of the controls indicated in the procedure.

3.8.2Prior to Operation

1.Ensure that the power supply is configured to the default setting:

On/Off switch at Off position.

Dip switch: All positions at Down (“Off”) position.

J2 Sense connector: Configured to Local Sense as shown in Fig. 3-4:

1

Remote (+) sense

Plug P/N: MC1,5/5-ST-3,81

2

Local (+) sense

(Phoenix)

3Not connected

4Local (-) sense

5Remote (-) sense

Fig.3-4: J2 Sense connector default connection

For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default) po- sition (Refer to Fig.4-2, Item 9 for location) if checkout is to be done in IEEE mode.

16

83-507-013 Rev. D

Image 24
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Limitation of Warranty Warranty ServiceDisclaimer Trademark InformationSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Sicherheits-und Warnsymbole Anderungen and BauteileersatzUmweltbedingungen Features and options General InformationIntroduction General DescriptionMultiple output power system Control via the serial communication portAnalog voltage programming and monitoring Parallel operationAccessories Specifications ChapterVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Installation GeneralPreparation for USE Initial InspectionsAC Input Power Connection LOCATON, Mounting and CoolingAC Source Requirements Rack Mount Slides optionalAC Input Connector, 1500W models AC Input Connector, 750W modelsAC Input Wire Connection, 1500W models AC Input CordTURN-ON Checkout Procedure GeneralPrior to Operation Constant Voltage Check Constant Current CheckOVP Check UVL CheckConnecting the Load Wire termination AWGNoise and Impedance Effects Inductive loadsMaking the load connections 6V to 60V Models Wire terminal lug 2 places 80V to 600V ModelsLoad wires connection to the output connector Connecting single loads, local sensing default Connecting single loads, remote sensingConnecting multiple loads, radial distribution method Multiple load connection with distribution terminals Grounding outputsSense wiring Output Terminal GroundingLocal and Remote Sensing Local sensing10.4 J2 sense connector technical information Remote sensingFront and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsAuxiliary Function Rear Panel Connections and Controls Rear panel connections and controlsRear Panel SW1 Setup Switch Resetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitorng Connector Making J1 connectionsSignal EnainIfcom LocalConstant Voltage Mode Constant Current ModeLocal Operation Setting the OVP level Resetting the OVP circuitOver Voltage Protection OVP Automatic CrossoverOutput SHUT-OFF SO Control VIA Rear Panel J1 Connector Under Voltage Limit UVLFoldback Protection Output ON/OFF ControlENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal Over Temperature Protecton OTP Last Setting MemoryAuto-restart mode Safe-start modeSeries Operation Series connection for increased output voltageSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Advanced parallel configuration Setting the units as Master or SlaveMaster and Slave units default operation Connection to the loadTo release units from Slave mode Current display accuracyAST OFF *OUT OFF DAISY-CHAIN Connection Front Panel LockingUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog IndicationDown Remote voltage programming connectionResisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control ConfigurationRear Panel RS232/RS485 Connector 6 RS232/RS485 port in Local modeFront panel in Remote mode MD Mode Option Factory Installed MD Mode Description MD Mode enable Serial communication modeMD Mode SRQ MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionInitialization Control Commands ID Control CommandsOutput Control Commands DVC? FilterFILTER? OUT?Global Output Commands Single Byte Commands Enable MD Mode MD Mode Option RequiredDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredAddressed commands with response Read registers Print Power On TimeTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range STATUS, Error and SRQ Registers 10.6 Status Control CommandsConditional Registers Status RegistersService Request Enable and Event Registers BITFault Enable Register Fault Event RegisterStatus Enable Register Status Event RegisterPower supply set-up Serial Communication Test SET-UPCommunication Test Specifications Isolated Analog Programming Option1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP