5.15 PARALLEL OPERATION

Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to provide up to four times the Output Current capability. One of the units operates as a Master and the remain- ing units are Slaves. The Slave units are analog programmed by the Master unit. In remote digital op- eration, only the Master unit can be programmed by the computer, while the Slave units may be con- nected to the computer for voltage, current and status readback only. Follow the following procedure to configure multiple supplies for parallel operation. Refer to Sec. 5.15.1 and to Sec. 5.15.2 for de- tailed explanation.

5.15.1 Basic parallel operation

In this method, setting the units as Master and Slaves is made by the rear panel J1 connections and the setup switch SW1. Each unit displays its own output current and voltage. To program the load cur- rent, the Master unit should be programmed to the total load current divided by the number of units in the system. Refer to the following procedure to configure multiple supplies for basic parallel operation.

1.Setting up the Master unit

Set the Master unit Output Voltage to the desired voltage. Program the Output Current to the desired load current divided by the number of parallel units. During operation, the Master unit operates in CV mode, regulating the load voltage at the programmed Output Voltage. Connect the sensing circuit to local or remote sensing as shown in Fig.5-4 or fig.5-5.

2.Setting up the Slave units

-1. The Output Voltage of the Slave units should be programmed 2-5% higher than the Output Voltage of the Master unit to prevent interference with the Master unit’s control. The Output Current setting of each unit should be programmed to the desired load current divided by the number of parallel units.

-2. Set the rear panel setup switch SW1 position 2 to the up position.

-3. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).

-4. Connect J1 terminal 10(IPGM) of the slave unit to J1 terminal 25(P) of the master unit.

During operation, the Slave units operate as a controlled current source following the Master Out- put Current. It is recommended that the power system be designed so that each unit supplies up to 95% of its current rating because of the imbalance which may be caused by cabling and con- nection voltage drop.

3.Daisy Chain Connection: (See Fig. 5-6)

These set up and connections are optional but is strongly recommended. It will shut down all power supplies when a fault condition occurs in any one of them.

oSwitch SW1 position 5 should be in its down position for all power supplies.

oConnect J1-16 of the Master Supply to J1-15 of the ‘First’ Slave Supply (If any).

o Connect J1-16 of the ‘First’ Slave Supply to J1-15 of the ‘Second’ Slave Supply (if any). o Connect J1-16 of the ‘Second’ Slave Supply to J1-15 of the ‘Third’ Slave Supply (If any). o Connect J1-16 of the ‘Last’ Slave Supply to J1-15 of the ‘Third’ Slave Supply (If any).

o Connect J1-2 (or J1-3) common to all supplies (See Fig. 5.6).

4.Setting Over Voltage protection

The Master unit OVP setting should be programmed to the desired OVP level. The OVP setting of the slave units should be programmed to a higher value than the Master OVP. When the Master unit shuts down, it programs the Slave unit to zero Output Voltage. If a Slave unit shuts down (when its OVP is set lower than the Master Output Voltage), only that Slave unit would shut down, and the remaining Slave units would supply all of the load current.

5.Setting Foldback protection

Foldback protection, is desired, may only be used with the Master unit. When the Master unit shuts down, it programs the Slave units to zero Output Voltage.

41

83-507-013 Rev. D

Image 49
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Warranty Service Limitation of WarrantyDisclaimer Trademark InformationSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleUmweltbedingungen General Information Features and optionsIntroduction General DescriptionControl via the serial communication port Multiple output power systemAnalog voltage programming and monitoring Parallel operationAccessories Chapter SpecificationsVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings General InstallationPreparation for USE Initial InspectionsLOCATON, Mounting and Cooling AC Input Power ConnectionAC Source Requirements Rack Mount Slides optionalAC Input Connector, 750W models AC Input Connector, 1500W modelsAC Input Wire Connection, 1500W models AC Input CordGeneral TURN-ON Checkout ProcedurePrior to Operation Constant Current Check Constant Voltage CheckOVP Check UVL CheckConnecting the Load AWG Wire terminationInductive loads Noise and Impedance EffectsMaking the load connections 6V to 60V Models 80V to 600V Models Wire terminal lug 2 placesLoad wires connection to the output connector Connecting single loads, remote sensing Connecting single loads, local sensing defaultConnecting multiple loads, radial distribution method Grounding outputs Multiple load connection with distribution terminalsOutput Terminal Grounding Sense wiringLocal and Remote Sensing Local sensingRemote sensing 10.4 J2 sense connector technical informationFront Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsAuxiliary Function Rear panel connections and controls Rear Panel Connections and ControlsRear Panel SW1 Setup Switch 1 SW1 position function Resetting the SW1 switchMaking J1 connections Rear Panel J1 Programming and Monitorng ConnectorEnain SignalIfcom LocalConstant Current Mode Constant Voltage ModeLocal Operation Resetting the OVP circuit Setting the OVP levelOver Voltage Protection OVP Automatic CrossoverUnder Voltage Limit UVL Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorFoldback Protection Output ON/OFF ControlCV/CC Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorPsok Signal Last Setting Memory Over Temperature Protecton OTPAuto-restart mode Safe-start modeSeries connection for increased output voltage Series OperationSeries connection for positive/negative output voltages Series connection for positive and negative output voltageParallel Operation Setting the units as Master or Slave Advanced parallel configurationMaster and Slave units default operation Connection to the loadCurrent display accuracy To release units from Slave modeAST OFF *OUT OFF Front Panel Locking DAISY-CHAIN ConnectionUnlocked front panel Locked front panelLOCAL/REMOTE Analog Indication Remote Analog ProgrammingRemote voltage programming connection DownRemote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote Control6 RS232/RS485 port in Local mode Rear Panel RS232/RS485 ConnectorFront panel in Remote mode MD Mode enable Serial communication mode MD Mode Option Factory Installed MD Mode DescriptionMD Mode SRQ MD Mode SRQ RetransmissionSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesID Control Commands Initialization Control CommandsOutput Control Commands Filter DVC?FILTER? OUT?Global Output Commands Enable MD Mode MD Mode Option Required Single Byte CommandsDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredPrint Power On Time Addressed commands with response Read registersTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range 10.6 Status Control Commands STATUS, Error and SRQ RegistersStatus Registers Conditional RegistersBIT Service Request Enable and Event RegistersFault Event Register Fault Enable RegisterStatus Event Register Status Enable RegisterSerial Communication Test SET-UP Power supply set-upCommunication Test Isolated Analog Programming Option Specifications1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating