TDK AC Input Connector, 1500W models, AC Input Connector, 750W models, AC Input Cord

Page 23

WARNING

Some components inside the power supply are at AC voltage even when the On/Off switch is in the “Off” position. To avoid electric shock hazard, disconnect the line cord and load and wait two minutes before removing cover.

3.7.1 AC Input Connector, 1500W models

The AC input connector is a 3-Terminal wire clamp located on the rear panel. Use suitable wires and tightening torque as follows:

1.Wire diameter: 12AWG or 10AWG.

2.Tightening torque: 6.5 - 7.0 Lb-inch.

3.7.2 AC Input Connector, 750W models

An IEC connector is provided on the rear panel for connecting the unit to the AC power source with an AC cord. The IEC connector also provides the safety ground connection while the AC cord is plugged into an appropriate AC receptacle.

WARNING

The AC input cord is the disconnect device of the power supply. The plug must be readily identifiable and accessible to the user. The AC input cord must be no longer than 3m.

3.7.3 AC Input Cord

Refer to Section 1.3.4 for details of the AC input cords recommended for the 750W and the 1500W models.

3.7.4AC Input Wire Connection, 1500W models

1.Strip the outside insulation of the AC cable approx. 10cm (3.94 inches). Trim the wires so that the ground wire is 10mm (0.4 inches) longer than the other wires. Strip 14mm (0.55 inches) at the end of each of the wires.

2.Unscrew the base of the strain relief from the helix-shaped body. Insert the base through the outside opening in the AC input cover and screw the locknut securely (11-14 Lb-inch.) the base, from the inside.

3.Slide the helix-shaped body onto the AC cable. Insert the stripped wires through the strain re- lief base until the outer cable jacket is flush with the edge of the base. Tighten (16-18 Lb-inch.) the body to the base while holding the cable in place. Now the cable is securely fastened in- side the strain relief. Refer to Fig. 3-2.

Screw-on

Locknut

Fig.3-2: Stripped Wires installed in Strain Relief

15

83-507-013 Rev. D

Image 23
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Trademark Information Limitation of WarrantyWarranty Service DisclaimerSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Umweltbedingungen Sicherheits-und WarnsymboleAnderungen and Bauteileersatz General Description Features and optionsGeneral Information IntroductionParallel operation Multiple output power systemControl via the serial communication port Analog voltage programming and monitoringAccessories Chapter SpecificationsVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Initial Inspections InstallationGeneral Preparation for USERack Mount Slides optional AC Input Power ConnectionLOCATON, Mounting and Cooling AC Source RequirementsAC Input Cord AC Input Connector, 1500W modelsAC Input Connector, 750W models AC Input Wire Connection, 1500W modelsPrior to Operation TURN-ON Checkout ProcedureGeneral UVL Check Constant Voltage CheckConstant Current Check OVP CheckConnecting the Load AWG Wire terminationMaking the load connections 6V to 60V Models Noise and Impedance EffectsInductive loads 80V to 600V Models Wire terminal lug 2 placesLoad wires connection to the output connector Connecting multiple loads, radial distribution method Connecting single loads, local sensing defaultConnecting single loads, remote sensing Grounding outputs Multiple load connection with distribution terminalsLocal sensing Sense wiringOutput Terminal Grounding Local and Remote SensingRemote sensing 10.4 J2 sense connector technical informationFront Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsAuxiliary Function Rear panel connections and controls Rear Panel Connections and ControlsRear Panel SW1 Setup Switch 1 SW1 position function Resetting the SW1 switchMaking J1 connections Rear Panel J1 Programming and Monitorng ConnectorLocal SignalEnain IfcomLocal Operation Constant Voltage ModeConstant Current Mode Automatic Crossover Setting the OVP levelResetting the OVP circuit Over Voltage Protection OVPOutput ON/OFF Control Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorUnder Voltage Limit UVL Foldback ProtectionPsok Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorCV/CC Signal Safe-start mode Over Temperature Protecton OTPLast Setting Memory Auto-restart modeSeries connection for increased output voltage Series OperationSeries connection for positive/negative output voltages Series connection for positive and negative output voltageParallel Operation Connection to the load Advanced parallel configurationSetting the units as Master or Slave Master and Slave units default operationAST OFF *OUT OFF To release units from Slave modeCurrent display accuracy Locked front panel DAISY-CHAIN ConnectionFront Panel Locking Unlocked front panelLOCAL/REMOTE Analog Indication Remote Analog ProgrammingRemote voltage programming connection DownRemote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote ControlFront panel in Remote mode Rear Panel RS232/RS485 Connector6 RS232/RS485 port in Local mode MD Mode SRQ Retransmission MD Mode Option Factory Installed MD Mode DescriptionMD Mode enable Serial communication mode MD Mode SRQSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesOutput Control Commands Initialization Control CommandsID Control Commands OUT? DVC?Filter FILTER?Global Output Commands Enable SRQ retransmission MD Mode Option Required Single Byte CommandsEnable MD Mode MD Mode Option Required Disable SRQ retransmission MD Mode Option RequiredAddressed commands without response Acknowledge SRQ Addressed commands with response Read registersPrint Power On Time Test if MD Mode is Installed1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range 10.6 Status Control Commands STATUS, Error and SRQ RegistersStatus Registers Conditional RegistersBIT Service Request Enable and Event RegistersFault Event Register Fault Enable RegisterStatus Event Register Status Enable RegisterCommunication Test Power supply set-upSerial Communication Test SET-UP PPM/C SpecificationsIsolated Analog Programming Option 1 0-5V/0-10V Option PN IS510Isolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating