TDK 1500W, 750W technical manual Bit, Service Request Enable and Event Registers

Page 72

7.11.2Conditional Registers (continued) Table 7-8: Fault Condition Register

BIT

Fault name

Fault symbol

Bit Set condition

Bit Reset condition

0 (LSB)

Spare bit

SPARE

Fixed to zero

Fixed to zero

 

 

 

 

 

1

AC Fail

AC

AC fail has occurred.

The AC input returns to normal.

2

Over

OTP

OTP shutdown has

The power supply cools down.

 

temperature

 

occurred.

 

3

Foldback

FOLD

Foldback shutdown

The supply output is turned On by front

 

 

 

has occurred

panel button or OUT 1 command.

4

Over voltage

OVP

OVP shutdown has

The supply output is turned ON by front

 

 

 

occurred.

panel button or OUT 1 command.

5

Shut Off

SO

Rear panel J1 “Shut

Rear panel J1 “Shut Off” condition has

 

 

 

Off” condition has oc-

been removed.

 

 

 

curred.

 

6

Output Off

OFF

Front panel OUT but-

The supply output is turned On by front

 

 

 

ton pressed to Off.

panel button or OUT 1 command.

7(MSB)

Enable

ENA

Rear panel J1 Enable

Rear panel J1 Enable terminals closed.

 

 

 

terminal (J1-1&J1-14)

 

 

 

 

opened.

 

Table 7-9: Status Condition Register

 

 

BIT

Fault name

Fault symbol

Bit Set condition

Bit Reset condition

0 (LSB)

Constant

CV

Output is On and the

Output is ON and the supply is not in

 

Voltage

 

supply in CV.

CV.

1

Constant

CC

Output is ON and the

Output is ON and the supply is not in

 

Current

 

supply in CC.

CC.

2

No Fault

NFLT

The power supply is

One or more faults are active and fault

 

 

 

operating normally or

reporting is enabled (using “FENAxx”).

 

 

 

fault reporting is not

 

 

 

 

enabled.

 

 

 

 

See “OUT n” com-

 

 

 

 

mand in Section 7.7.5.

 

3

Fault active

FLT

One or more faults are

Fault Event Register cleared (FEVE?).

 

 

 

enabled and occur.

 

4

Auto-Restart

AST

Supply is in Auto-

Supply is in Safe-Start mode (from

 

Enabled

 

Restart mode (from

Front Panel or serial command).

 

 

 

Front Panel or serial

 

 

 

 

command).

 

5

Fold

FDE

Fold protection is

Fold protection disabled (from Front

 

Enabled

 

enabled (from Front

Panel or serial command).

 

 

 

Panel or serial

 

 

 

 

command).

 

6

Spare bit

SPARE

Fixed to zero.

Fixed to zero.

7(MSB)

Local Mode

LCL

Supply in Local mode.

Supply in Remote mode or Local-

 

 

 

 

Lockout mode.

7.11.3 Service Request: Enable and Event Registers

The conditional Registers are continuously monitored. When a change is detected in a register bit which is enabled, the power supply will generate an SRQ message.

The SRQ message is: “Inn” terminated by CR, where the nn is the power supply address. The SRQ will be generated either in Local or Remote mode.

64

83-507-013 Rev. D

Image 72
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Limitation of Warranty Warranty ServiceDisclaimer Trademark InformationSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Sicherheits-und Warnsymbole Anderungen and BauteileersatzUmweltbedingungen Features and options General InformationIntroduction General DescriptionMultiple output power system Control via the serial communication portAnalog voltage programming and monitoring Parallel operationAccessories Specifications ChapterVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Installation GeneralPreparation for USE Initial InspectionsAC Input Power Connection LOCATON, Mounting and CoolingAC Source Requirements Rack Mount Slides optionalAC Input Connector, 1500W models AC Input Connector, 750W modelsAC Input Wire Connection, 1500W models AC Input CordTURN-ON Checkout Procedure GeneralPrior to Operation Constant Voltage Check Constant Current CheckOVP Check UVL CheckConnecting the Load Wire termination AWGNoise and Impedance Effects Inductive loadsMaking the load connections 6V to 60V Models Wire terminal lug 2 places 80V to 600V ModelsLoad wires connection to the output connector Connecting single loads, local sensing default Connecting single loads, remote sensingConnecting multiple loads, radial distribution method Multiple load connection with distribution terminals Grounding outputsSense wiring Output Terminal GroundingLocal and Remote Sensing Local sensing10.4 J2 sense connector technical information Remote sensingFront and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsAuxiliary Function Rear Panel Connections and Controls Rear panel connections and controlsRear Panel SW1 Setup Switch Resetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitorng Connector Making J1 connectionsSignal EnainIfcom LocalConstant Voltage Mode Constant Current ModeLocal Operation Setting the OVP level Resetting the OVP circuitOver Voltage Protection OVP Automatic CrossoverOutput SHUT-OFF SO Control VIA Rear Panel J1 Connector Under Voltage Limit UVLFoldback Protection Output ON/OFF ControlENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal Over Temperature Protecton OTP Last Setting MemoryAuto-restart mode Safe-start modeSeries Operation Series connection for increased output voltageSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Advanced parallel configuration Setting the units as Master or SlaveMaster and Slave units default operation Connection to the loadTo release units from Slave mode Current display accuracyAST OFF *OUT OFF DAISY-CHAIN Connection Front Panel LockingUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog IndicationDown Remote voltage programming connectionResisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control ConfigurationRear Panel RS232/RS485 Connector 6 RS232/RS485 port in Local modeFront panel in Remote mode MD Mode Option Factory Installed MD Mode Description MD Mode enable Serial communication modeMD Mode SRQ MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionInitialization Control Commands ID Control CommandsOutput Control Commands DVC? FilterFILTER? OUT?Global Output Commands Single Byte Commands Enable MD Mode MD Mode Option RequiredDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredAddressed commands with response Read registers Print Power On TimeTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range STATUS, Error and SRQ Registers 10.6 Status Control CommandsConditional Registers Status RegistersService Request Enable and Event Registers BITFault Enable Register Fault Event RegisterStatus Enable Register Status Event RegisterPower supply set-up Serial Communication Test SET-UPCommunication Test Specifications Isolated Analog Programming Option1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP