TDK 750W, 1500W technical manual Serial Communication Test SET-UP, Power supply set-up

Page 75

7.12 SERIAL COMMUNICATION TEST SET-UP

Use the following instructions as basic set-up to test the serial communication operation.

1.Equipment: PC with Windows Hyper Terminal, software installed, GenesysTM Power supply, RS232 cable.

2.PC set-up: 2.1 Open Hyper Terminal…………………….New Connection.

2.2Enter a name

2.3Connect to…………………………………Direct to Com 1 or Com 2

2.4Configure port properties:

 

Bits per second……9600

 

Data bits……………8

 

Parity……………….None

 

Stop bits……………1

 

Flow control……….None

2.5 Open Properties in the program

File………………….Properties

2.6 Setting: ASCII Set Up

Select Echo characters locally, select send line ends with line feed.

On some PC systems, pressing the number keypad “Enter” will distort displayed messages. Use the alphabetic “Enter” instead.

3.Power supply set-up:

3.1Connect the power supply to the PC using the RS232 cable.

3.2Set via the front panel: Baud Rate: 9600, Address: 06 (default).

3.3Set via the rear panel: RS232/RS485 to RS232 (refer to Section 4-4).

4.Communication Test:

4.1Model identification: PC:write: ADR 06

Power supply response: “OK”

4.2Command test: PC write: OUT1

Power supply response: “OK”

PC write: PVn

Power supply response: “OK”

PC write: PCn (for values of n see Tables 7-4, 7-5 and 7-6)

Power supply response: “OK”

The power supply should turn on and the display will indicate the actual Output Voltage and the actual Output Current.

67

83-507-013 Rev. D

Image 75
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Trademark Information Limitation of WarrantyWarranty Service DisclaimerSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Sicherheits-und Warnsymbole Anderungen and BauteileersatzUmweltbedingungen General Description Features and optionsGeneral Information IntroductionParallel operation Multiple output power systemControl via the serial communication port Analog voltage programming and monitoringAccessories Chapter SpecificationsVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Initial Inspections InstallationGeneral Preparation for USERack Mount Slides optional AC Input Power ConnectionLOCATON, Mounting and Cooling AC Source RequirementsAC Input Cord AC Input Connector, 1500W modelsAC Input Connector, 750W models AC Input Wire Connection, 1500W modelsTURN-ON Checkout Procedure GeneralPrior to Operation UVL Check Constant Voltage CheckConstant Current Check OVP CheckConnecting the Load AWG Wire terminationNoise and Impedance Effects Inductive loadsMaking the load connections 6V to 60V Models 80V to 600V Models Wire terminal lug 2 placesLoad wires connection to the output connector Connecting single loads, local sensing default Connecting single loads, remote sensingConnecting multiple loads, radial distribution method Grounding outputs Multiple load connection with distribution terminalsLocal sensing Sense wiringOutput Terminal Grounding Local and Remote SensingRemote sensing 10.4 J2 sense connector technical informationFront Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsAuxiliary Function Rear panel connections and controls Rear Panel Connections and ControlsRear Panel SW1 Setup Switch 1 SW1 position function Resetting the SW1 switchMaking J1 connections Rear Panel J1 Programming and Monitorng ConnectorLocal SignalEnain IfcomConstant Voltage Mode Constant Current ModeLocal Operation Automatic Crossover Setting the OVP levelResetting the OVP circuit Over Voltage Protection OVPOutput ON/OFF Control Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorUnder Voltage Limit UVL Foldback ProtectionENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal Safe-start mode Over Temperature Protecton OTPLast Setting Memory Auto-restart modeSeries connection for increased output voltage Series OperationSeries connection for positive/negative output voltages Series connection for positive and negative output voltageParallel Operation Connection to the load Advanced parallel configurationSetting the units as Master or Slave Master and Slave units default operationTo release units from Slave mode Current display accuracyAST OFF *OUT OFF Locked front panel DAISY-CHAIN ConnectionFront Panel Locking Unlocked front panelLOCAL/REMOTE Analog Indication Remote Analog ProgrammingRemote voltage programming connection DownRemote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote ControlRear Panel RS232/RS485 Connector 6 RS232/RS485 port in Local modeFront panel in Remote mode MD Mode SRQ Retransmission MD Mode Option Factory Installed MD Mode DescriptionMD Mode enable Serial communication mode MD Mode SRQSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesInitialization Control Commands ID Control CommandsOutput Control Commands OUT? DVC?Filter FILTER?Global Output Commands Enable SRQ retransmission MD Mode Option Required Single Byte CommandsEnable MD Mode MD Mode Option Required Disable SRQ retransmission MD Mode Option RequiredAddressed commands without response Acknowledge SRQ Addressed commands with response Read registersPrint Power On Time Test if MD Mode is Installed1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range 10.6 Status Control Commands STATUS, Error and SRQ RegistersStatus Registers Conditional RegistersBIT Service Request Enable and Event RegistersFault Event Register Fault Enable RegisterStatus Event Register Status Enable RegisterPower supply set-up Serial Communication Test SET-UPCommunication Test PPM/C SpecificationsIsolated Analog Programming Option 1 0-5V/0-10V Option PN IS510Isolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating