TDK 1500W DAISY-CHAIN Connection, Front Panel Locking, Unlocked front panel, Locked front panel

Page 52

 

 

 

 

 

 

 

 

 

 

+S

 

 

 

 

 

 

 

 

 

 

-S

 

 

 

 

 

 

 

 

 

 

Twisted

 

 

 

 

 

 

 

 

 

 

pair

To J1-10

 

 

 

 

-S

+S

 

 

 

 

As short as possible

 

 

 

 

 

 

 

 

+V

SLAVE#2

MASTER

 

 

 

 

 

+S

POWER SUPPLY

POWER SUPPLY

 

 

-V

Twisted

 

 

 

pair

 

 

 

 

J1-25

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

IPGM

 

 

 

 

 

J1-8 J1-12 J1

-10

 

 

 

 

 

SLAVE#1

 

 

+V

 

 

POWER SUPPLY

 

 

-V

-S

 

 

 

 

 

 

 

 

 

 

 

 

-S -LS

+LS +S

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

Fig.5-5: Parallel operation with Remote sensing

5.16 DAISY-CHAIN CONNECTION

It is possible to configure a multiple power supply system to shut down all the units when a fault condi- tion occurs in one of the units. When the fault is removed, the system recovers according to its setting to Safe-start or Auto-restart mode.

Setup switch SW1, position 5 should be set to its DOWN position to enable the Daisy-chain operation. Other SW1 positions can be set according to the application requirements.

If a fault occurs in one of the units, its PS_OK signal will be set to a low level and the display will indi- cate the fault. The other units will shut off and their display will indicate “SO”. When the fault condition is removed, the units will recover to their last setting according to their Safe-start or Auto-restart set- ting.

Fig.5-6 shows connection of three units, however the same connection method applies to systems with a larger number of units.

POWER SUPPLY

#1

J1-2,3 J1-16 J1-15

POWER SUPPLY

#2

J1-2,3 J1-16 J1-15

POWER SUPPLY

#3

J1-2,3 J1-16 J1-15

IF_COM

PS_OK

SO

IF_COM PS_OK SO

IF_COM

PS_OK

SO

 

 

Fig.5-6: Daisy-chain connection

 

 

5.17 FRONT PANEL LOCKING

The front panel controls can be locked to protect from accidental power supply parameter change. Press and hold the PREV button to toggle between “Locked front panel’ and “Unlocked front panel”. The display will cycle between “LFP” and “UFP”. Releasing the PREV button while one of the modes is displayed, selects that mode.

5.17.1 Unlocked front panel

In this mode, the front panel controls are Enabled to program and monitor the power supply parame- ters.

5.17.2 Locked front panel

In this mode the following front panel controls are Disabled: -VOLTAGE and CURRENT encoders.

-FOLD button. -OUT button

The power supply will not respond to attempts to use these controls. The VOLT display will show “LFP” to indicate that the front panel is locked.

OVP/ UVL button is active to preview the OVP and UVL setting.

Use the PREV button to preview the Output Voltage and Current setting or to unlock the front panel.

44

83-507-013 Rev. D

Image 52
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Limitation of Warranty Warranty ServiceDisclaimer Trademark InformationSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleUmweltbedingungen Features and options General InformationIntroduction General DescriptionMultiple output power system Control via the serial communication portAnalog voltage programming and monitoring Parallel operationAccessories Specifications ChapterVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Installation GeneralPreparation for USE Initial InspectionsAC Input Power Connection LOCATON, Mounting and CoolingAC Source Requirements Rack Mount Slides optionalAC Input Connector, 1500W models AC Input Connector, 750W modelsAC Input Wire Connection, 1500W models AC Input CordGeneral TURN-ON Checkout ProcedurePrior to Operation Constant Voltage Check Constant Current CheckOVP Check UVL CheckConnecting the Load Wire termination AWGInductive loads Noise and Impedance EffectsMaking the load connections 6V to 60V Models Wire terminal lug 2 places 80V to 600V ModelsLoad wires connection to the output connector Connecting single loads, remote sensing Connecting single loads, local sensing defaultConnecting multiple loads, radial distribution method Multiple load connection with distribution terminals Grounding outputsSense wiring Output Terminal GroundingLocal and Remote Sensing Local sensing10.4 J2 sense connector technical information Remote sensingFront and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsAuxiliary Function Rear Panel Connections and Controls Rear panel connections and controlsRear Panel SW1 Setup Switch Resetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitorng Connector Making J1 connectionsSignal EnainIfcom LocalConstant Current Mode Constant Voltage ModeLocal Operation Setting the OVP level Resetting the OVP circuitOver Voltage Protection OVP Automatic CrossoverOutput SHUT-OFF SO Control VIA Rear Panel J1 Connector Under Voltage Limit UVLFoldback Protection Output ON/OFF ControlCV/CC Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorPsok Signal Over Temperature Protecton OTP Last Setting MemoryAuto-restart mode Safe-start modeSeries Operation Series connection for increased output voltageSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Advanced parallel configuration Setting the units as Master or SlaveMaster and Slave units default operation Connection to the loadCurrent display accuracy To release units from Slave modeAST OFF *OUT OFF DAISY-CHAIN Connection Front Panel LockingUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog IndicationDown Remote voltage programming connectionResisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control Configuration6 RS232/RS485 port in Local mode Rear Panel RS232/RS485 ConnectorFront panel in Remote mode MD Mode Option Factory Installed MD Mode Description MD Mode enable Serial communication modeMD Mode SRQ MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionID Control Commands Initialization Control CommandsOutput Control Commands DVC? FilterFILTER? OUT?Global Output Commands Single Byte Commands Enable MD Mode MD Mode Option RequiredDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredAddressed commands with response Read registers Print Power On TimeTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range STATUS, Error and SRQ Registers 10.6 Status Control CommandsConditional Registers Status RegistersService Request Enable and Event Registers BITFault Enable Register Fault Event RegisterStatus Enable Register Status Event RegisterSerial Communication Test SET-UP Power supply set-upCommunication Test Specifications Isolated Analog Programming Option1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP