TDK 1500W, 750W technical manual Connecting the Load

Page 26

3.8.7Foldback Check

WARNING

Shorting the output may expose the user to hazardous voltages. Observe proper safety procedures.

Refer to Section 5.5 for explanation of the FOLD function prior to performing the procedure below.

1.Ensure that the Output Voltage is set to approx. 10% of the unit rating.

2.Adjust the CURRENT encoder to set the Output Current setting to approx. 10% of the unit rating.

3.Momentarily press the FOLD button. Ensure that the FOLD LED illuminates. The Output Voltage remains unchanged.

4.Short the output terminals momentarily (approx. 0.5 sec.). Ensure that the Output Voltage falls to zero, the VOLT display shows “Fb” and the ALARM LED blinks.

5.Press the FOLD button again to cancel the protection. The Output Voltage remains zero.

6.Press the OUT button. Ensure that the Output Voltage returns to its last setting.

7.Turn the output off by pressing the OUT button. Ensure that the VOLT display shows “OFF”.

3.8.8Address Setting

1.Press and hold the REM/LOC button for approx. 3 sec. The VOLT display will show the communi- cation port address.

2.Using the VOLT adjust encoder, check that the address can be set within the range of 0 to 30.

3.8.9Baud Rate Setting (RS-232 and RS-485 only)

1.Press and hold the REM/LOC button for approx. 3 sec. The CURRENT display will show the communication port Baud Rate.

2.Using The CURRENT adjust encoder, check that the Baud Rate can be set to 1200, 2400, 4800, 9600 and 19200.

3.9 CONNECTING THE LOAD

WARNING

Turn Off the AC input power before making or changing any rear panel connection. Ensure that all connections are se- curely tightened before applying power. There is a potential shock hazard when using a power supply with a rated out- put greater than 40V.

3.9.1Load Wiring

The following considerations should be made to select wiring for connecting the load to the power sup- ply:

Current carrying capacity of the wire (refer to Section 3.9.2)

Insulation rating of the wire should be at least equivalent to the maximum output voltage of the power supply.

Maximum wire length and voltage drop (refer to Section 3.9.2)

Noise and impedance effects of the load wiring (refer to Section 3.9.4).

3.9.2 Current Carrying Capacity

Two factors must be considered when selecting the wire size:

1.Wires should be at least heavy enough not to overheat while carrying the power supply load current at the rated load, or the current that would flow in the event the load wires were shorted, whichever is greater.

18

83-507-013 Rev. D

Image 26
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Disclaimer Limitation of WarrantyWarranty Service Trademark InformationSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Umweltbedingungen Sicherheits-und WarnsymboleAnderungen and Bauteileersatz Introduction Features and optionsGeneral Information General DescriptionAnalog voltage programming and monitoring Multiple output power systemControl via the serial communication port Parallel operationAccessories Specifications ChapterVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Preparation for USE InstallationGeneral Initial InspectionsAC Source Requirements AC Input Power ConnectionLOCATON, Mounting and Cooling Rack Mount Slides optionalAC Input Wire Connection, 1500W models AC Input Connector, 1500W modelsAC Input Connector, 750W models AC Input CordPrior to Operation TURN-ON Checkout ProcedureGeneral OVP Check Constant Voltage CheckConstant Current Check UVL CheckConnecting the Load Wire termination AWGMaking the load connections 6V to 60V Models Noise and Impedance EffectsInductive loads Wire terminal lug 2 places 80V to 600V ModelsLoad wires connection to the output connector Connecting multiple loads, radial distribution method Connecting single loads, local sensing defaultConnecting single loads, remote sensing Multiple load connection with distribution terminals Grounding outputsLocal and Remote Sensing Sense wiringOutput Terminal Grounding Local sensing10.4 J2 sense connector technical information Remote sensingFront and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsAuxiliary Function Rear Panel Connections and Controls Rear panel connections and controlsRear Panel SW1 Setup Switch Resetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitorng Connector Making J1 connectionsIfcom SignalEnain LocalLocal Operation Constant Voltage ModeConstant Current Mode Over Voltage Protection OVP Setting the OVP levelResetting the OVP circuit Automatic CrossoverFoldback Protection Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorUnder Voltage Limit UVL Output ON/OFF ControlPsok Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorCV/CC Signal Auto-restart mode Over Temperature Protecton OTPLast Setting Memory Safe-start modeSeries Operation Series connection for increased output voltageSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Master and Slave units default operation Advanced parallel configurationSetting the units as Master or Slave Connection to the loadAST OFF *OUT OFF To release units from Slave modeCurrent display accuracy Unlocked front panel DAISY-CHAIN ConnectionFront Panel Locking Locked front panelRemote Analog Programming LOCAL/REMOTE Analog IndicationDown Remote voltage programming connectionResisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control ConfigurationFront panel in Remote mode Rear Panel RS232/RS485 Connector6 RS232/RS485 port in Local mode MD Mode SRQ MD Mode Option Factory Installed MD Mode DescriptionMD Mode enable Serial communication mode MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionOutput Control Commands Initialization Control CommandsID Control Commands FILTER? DVC?Filter OUT?Global Output Commands Disable SRQ retransmission MD Mode Option Required Single Byte CommandsEnable MD Mode MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredTest if MD Mode is Installed Addressed commands with response Read registersPrint Power On Time Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range STATUS, Error and SRQ Registers 10.6 Status Control CommandsConditional Registers Status RegistersService Request Enable and Event Registers BITFault Enable Register Fault Event RegisterStatus Enable Register Status Event RegisterCommunication Test Power supply set-upSerial Communication Test SET-UP 1 0-5V/0-10V Option PN IS510 SpecificationsIsolated Analog Programming Option PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP