TDK 1500W, 750W technical manual Fuse Rating, Oup

Page 80

SYMPTOM

CHECK

ACTION

REF

Output Voltage will not adjust.

Is the unit in constant current

Check Output Current

5.2.1

Front panel CC LED is On.

mode?

setting and load current.

5.2.2

Output Voltage will not adjust

Check if output voltage is

Set OVP or UVL so they will

5.3

Front panel CV Led is On.

adjusted above OVP setting

not limit the output.

5.4

 

or below UVL setting.

 

 

Output Current will not adjust.

Is the unit in constant voltage

Check Output Current and

5.2

Front panel CV LED is on.

mode?

voltage setting

 

Large ripple present in output.

Is the power supply in

Check load and sense

3.9.4

 

remote sense?

wires connection for noise

3.9.8

 

Is the voltage drop on the

and impedance effects.

 

 

load wire high?

Minimize the drop on the

 

 

 

load wires.

 

No output. Display indicates

Overvoltage Protection

Turn off the AC power

5.3

“OUP”

circuit is tripped.

switch. Check load

 

 

 

connections. If Analog

 

 

 

Programming is used,

 

 

 

check if the OVP is set

 

 

 

lower than the output.

 

No output. Front panel

Display indicates “ENA”

Check rear panel J1

5.8

ALARM LED is blinking.

 

ENABLE connection.

 

 

 

Setup switch SW1 setting.

4.4

 

Display indicates “SO”

Check rear panel J1 Output

5.7

 

 

Shut-Off connection.

 

 

Display indicates “OTP”

Check if air intake or

 

 

 

exhaust are blocked.

 

 

 

Check if the unit is

 

 

 

installed adjacent to heat

 

 

 

generating equipment.

 

 

Display indicates “Fb”

Check Foldback setting and

5.5

 

 

load current.

 

Poor Load regulation.

Are sensing wires connected

Connect the sense wires

3.9.8

Front panel CV LED is on.

properly?

according to User’s Manual

 

 

 

instructions.

 

The front panel controls are

Is the power supply in

Turn Off the AC power

7.2.5

non-functional.

Local-Lockout mode?

and wait until the display

 

 

 

turns off. Turn on the AC

 

 

 

power and press front

 

 

 

panel REM/LOC button.

 

9.7 FUSE RATING

There are no user replaceable fuses in the power supply. Internal fuses are sized for fault protection and if a fuse was opened, it would indicate that service is required. Fuse replacement should be made by qualified technical personnel. Refer to Table 9-2 for a listing of the fuses.

Table 9-2: Internal fuses

Fuse designation

1500W model

750W model

F301

30A

250VAC, TIME DELAY

20A 250VAC, FAST

F302, F304

2A 400VDC, NORMAL

2A 400VDC, NORMAL

F31, F32

20A

250VAC, FAST

NOT USED

72

83-507-013 Rev. D

Image 80
Contents Genesystm 750W/1500W Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ………...……… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Programming OPTION………………………………… Limitation of Warranty Warranty ServiceDisclaimer Trademark InformationSafety Instructions Environmental Conditions SICHERHEITS-INSTALLATIONS Anweisungen Umweltbedingungen Sicherheits-und WarnsymboleAnderungen and Bauteileersatz Features and options General InformationIntroduction General DescriptionMultiple output power system Control via the serial communication portAnalog voltage programming and monitoring Parallel operationAccessories Specifications ChapterVout Supplemental Characteristics Genesystm 750W & 1500W Power Supplies Outline Drawings Installation GeneralPreparation for USE Initial InspectionsAC Input Power Connection LOCATON, Mounting and CoolingAC Source Requirements Rack Mount Slides optionalAC Input Connector, 1500W models AC Input Connector, 750W modelsAC Input Wire Connection, 1500W models AC Input CordPrior to Operation TURN-ON Checkout ProcedureGeneral Constant Voltage Check Constant Current CheckOVP Check UVL CheckConnecting the Load Wire termination AWGMaking the load connections 6V to 60V Models Noise and Impedance EffectsInductive loads Wire terminal lug 2 places 80V to 600V ModelsLoad wires connection to the output connector Connecting multiple loads, radial distribution method Connecting single loads, local sensing defaultConnecting single loads, remote sensing Multiple load connection with distribution terminals Grounding outputsSense wiring Output Terminal GroundingLocal and Remote Sensing Local sensing10.4 J2 sense connector technical information Remote sensingFront and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsAuxiliary Function Rear Panel Connections and Controls Rear panel connections and controlsRear Panel SW1 Setup Switch Resetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitorng Connector Making J1 connectionsSignal EnainIfcom LocalLocal Operation Constant Voltage ModeConstant Current Mode Setting the OVP level Resetting the OVP circuitOver Voltage Protection OVP Automatic CrossoverOutput SHUT-OFF SO Control VIA Rear Panel J1 Connector Under Voltage Limit UVLFoldback Protection Output ON/OFF ControlPsok Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorCV/CC Signal Over Temperature Protecton OTP Last Setting MemoryAuto-restart mode Safe-start modeSeries Operation Series connection for increased output voltageSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Advanced parallel configuration Setting the units as Master or SlaveMaster and Slave units default operation Connection to the loadAST OFF *OUT OFF To release units from Slave modeCurrent display accuracy DAISY-CHAIN Connection Front Panel LockingUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog IndicationDown Remote voltage programming connectionResisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control ConfigurationFront panel in Remote mode Rear Panel RS232/RS485 Connector6 RS232/RS485 port in Local mode MD Mode Option Factory Installed MD Mode Description MD Mode enable Serial communication modeMD Mode SRQ MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionOutput Control Commands Initialization Control CommandsID Control Commands DVC? FilterFILTER? OUT?Global Output Commands Single Byte Commands Enable MD Mode MD Mode Option RequiredDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredAddressed commands with response Read registers Print Power On TimeTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by GEN750W models GEN1500W models Current programming range STATUS, Error and SRQ Registers 10.6 Status Control CommandsConditional Registers Status RegistersService Request Enable and Event Registers BITFault Enable Register Fault Event RegisterStatus Enable Register Status Event RegisterCommunication Test Power supply set-upSerial Communication Test SET-UP Specifications Isolated Analog Programming Option1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP