Liebert 610 manual Electrical Specifications

Page 102

Specifications

5.5Electrical Specifications

RECTIFIER INPUT

 

Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC

Input Voltage

Standard voltages for 500 - 1000kVA units: 480 and 600VAC

 

Other voltages available on request. 3-phase, 3-wire plus ground.

Voltage Range

+10%, -15% (no battery discharge at -20%)

Frequency Range

57 Hz to 63 Hz

 

Less than 3 times normal full load input current for UPS models without optional

Subcycle Magnetization Inrush

input isolation transformer. Typically less than 8 times normal full load input current

 

for models with optional input isolation transformer and optional input filter.

Input Current Walk-In

From 20% to 100% in 15-20 seconds

Current Limit

Maximum of 125% normal full load input current

 

Less than 30% reflected THD typical at normal full load input current. Less than 7%

 

reflected THD typical at normal full load input current with optional input filter.

Current Distortion

For models with optional 12-pulse rectifier, less than 9% reflected THD typical at

 

normal full load input current. Less than 4% reflected THD typical with optional input

 

filter.

Power Factor

0.85 minimum lagging at full load

0.92 minimum lagging at full load with optional input filter

 

BYPASS INPUT

 

 

Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. 3-phase, 3-wire

Input Voltage

plus ground or 3-phase, 4-wire plus ground. Other optional voltages available.

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

 

 

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Range

±5% for manually initiated bypass transfer

±10% for automatically initiated uninterrupted transfer

 

Frequency Range

59.5 Hz to 60.5 Hz

Voltage Transient

±4% for manually initiated bypass transfer

CRITICAL LOAD OUTPUT

 

 

Standard voltages - 208/120 VAC, 480/277 VAC and 600/347 VAC. 3-phase, 3-wire

Output Voltage

plus ground or 3-phase, 4-wire plus ground. Other optional voltages available.

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

 

 

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Regulation

±0.5% for balanced load

±2% for unbalanced load

 

Voltage Adjustment Range

±5% manually (front panel knob)

Line Drop Compensation Range

Up to +5% automatic load dependent

Frequency

59.5 Hz to 60.5 Hz

Slew Rate

0.01 to 1 Hz per second adjustable

Phase Balancing

120° ±1° for balanced loads

120° ±3° for 50% unbalanced loads

 

Voltage Imbalance

 

20% Unbalanced Load

50% Unbalanced Load

±1% from the arithmetic average of the 3 phases ±2% from the arithmetic average of the 3 phases

Voltage Transient

20% Load Step

±4% RMS

50% Load Step

±4% RMS for 100-750kVA units; ±5% RMS for 1000kVA units

100% Load Step

±5% RMS for 100-750kVA units; ±8% RMS for 1000kVA units

Loss or Return of AC Input Power

±1% RMS

Manual Transfer of 100% Load

±4% RMS

Voltage Transient Recovery Time

To within 1% of steady state output voltage within 50 milliseconds

Voltage Harmonic Content

Maximum 5% RMS total, for any combination of linear and nonlinear 3-phase loads

Maximum 3% RMS single, for linear loads

 

 

104% of full load rating continuously

Overload at Full Output Voltage

125% of full load rating for 10 minutes

150% of full load rating for 30 seconds

 

 

(with ±2% voltage regulation)

 

Up to 300% of normal full load current subcycle; up to 500% of normal full load

Fault Clearing

current for up to 40 milliseconds with bypass available; up to 1000% of normal full

 

load current for up to 16 milliseconds with bypass available.

96

Image 102
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Reliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Battery Load Testing Customer Alarm InterfaceTemperature-Compensated Charging Automatic RestartBattery Plant General Component DescriptionsUPS Module Detailed Component Descriptions Controls HardwareSoftware Operation Input Power FactorRectifier/Charger Input Circuit BreakerBattery Charge Current Limiting Battery Charging CircuitBattery Disconnect Battery Equalize Charge CircuitInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceBypass Circuit Breaker Static Switch Backfeed ProtectionStatic Bypass Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Remote Monitor Alarm messagesAdditional alarm messages Standard Remote Monitor Indications ChannelBattery Discharging Alarm Limit Settings ScreenOverload Alarm Low BatteryBattery Rating Battery Shutdown 60 MinutesBattery Rating 100% Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsCommunication Interfaces Worldwide ReportingAuto-Dial Site Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Requesting InformationSeparate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Keys FunctionLoad on Bypass Circuit breaker abbreviationsAbbreviation Circuit Breaker OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results below1000% Automatic OperationsOverloads Without Transfer 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Automatic Restart Optional Enabling Automatic RestartSequence of Operation Maintenance Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Corrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Recommended Test EquipmentPower factor pf KVA RatingKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Locations Technical Support/ServiceCompany Behind the Products United States