Liebert 610 manual Shutdown Procedures Screen, Battery Time Screen

Page 50

Operation

3.2.9Shutdown Procedures Screen

Go to the Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select pad and the Shutdown Procedures screen is displayed.

This two-page screen contains the steps you must follow to perform a controlled shutdown of the UPS system. The instructions are listed so you can review them before performing the controlled shutdown.

To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line. Then open the battery circuit breaker and manually open the UPS input circuit breaker. The Control Power may be turned off (by pulling open the two fuseholders labeled Control Disconnect) if required for maintenance purposes.

Refer to 3.4.4 - Shutdown Procedures for more details, including module shutdowns for service and emergency shutdowns.

Figure 33 Shutdown procedures screen

DOWN : NEXT PAGE

SELECT : MASTER MENU

© 1989-2003

 

SHUTDOWN PROCEDURES

1.If load is not already being supplied by the bypass line, select the

"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer the load to bypass.

2.Open the battery breaker by simultaneously pressing the BATTERY TRIP and CONTROL ENABLE pushbuttons.

3.Manually open the input breaker by moving the handle to the OFF position.

4.Verify breaker status on the "MONITOR / MIMIC" screen.

5.Press the ALARM RESET button to clear alarms which are no longer active.

Figure 34 Shutdown procedures screen, continued

UP : FIRST PAGE

SELECT : MASTER MENU

© 1989-2003

 

SHUTDOWN PROCEDURES (Cont'd)

6.If necessary for maintenance purposes, open the static switch disconnects and/or control power switch (fuse disconnect on some models) to the OFF position.

7.Wait a minimum of two (2) minutes before attempting any other action.

3.2.10Battery Time Screen

At the Master Menu, move the highlighted cursor to BATTERY TIME. Press the Select pad and the Battery Time screen is displayed.

When AC power is not available to the UPS module, the UPS inverter uses DC power from the battery to supply the critical load. This screen helps the operator assess his power resources to determine if and when the critical load shutdown procedures need to be started.

The Battery Time screen is a line graph that tracks the present battery voltage versus the elapsed time that the battery has been discharging (Figure 35). As the battery voltage decreases, the line representing it moves closer to intersecting the line that represents the battery shutdown voltage.

When the battery starts to discharge, the screen displays a 15-minute graph. If the battery has been providing power for more than 15 minutes, the screen displays a 30-minute graph. If battery power is still available after 30 minutes, a 60-minute graph is displayed (Figure 36).

44

Image 50 Contents
Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Other Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls Options Battery Load Testing Customer Alarm InterfaceTemperature-Compensated Charging Automatic RestartUPS Module Battery PlantGeneral Component Descriptions Software Detailed Component DescriptionsControls Hardware Operation Input Power FactorRectifier/Charger Input Circuit BreakerBattery Charge Current Limiting Battery Charging CircuitBattery Disconnect Battery Equalize Charge CircuitInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceBypass Circuit Breaker Static Switch Backfeed ProtectionStatic Bypass Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Remote Monitor Alarm messagesAdditional alarm messages Standard Remote Monitor Indications Channel Battery Discharging Alarm Limit Settings Screen Overload Alarm Low BatteryBattery Rating Battery Shutdown 60 MinutesBattery Rating 100% Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsAuto-Dial Communication InterfacesWorldwide Reporting Site Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Requesting InformationSeparate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Keys FunctionAbbreviation Circuit Breaker Load on BypassCircuit breaker abbreviations OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results below1000% Automatic OperationsOverloads Without Transfer 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Sequence of Operation Automatic Restart OptionalEnabling Automatic Restart Maintenance Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Corrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Recommended Test EquipmentKVA Power factor pf KVARating Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Locations Technical Support/ServiceCompany Behind the Products United States