Liebert 610 manual OK to Transfer, Load on bypass UPS available

Page 65

Operation

3.3.2OK to Transfer

The OK to Transfer status message will be displayed when the bypass line and UPS output power are both available, their voltage, frequency and phase synchronization are matched within specifications, and the Static Switch Disconnects are closed (ON). An alarm message may be displayed to indicate Load On Bypass (Figure 42). If no alarm is displayed, the operating status is Load On UPS (Figure 43).

When the OK to Transfer message is displayed, you can perform a manual transfer of the load from the UPS system to bypass or a manual retransfer of the load from bypass to the UPS system.

Use the Load Transfer Procedures screen when performing a manual transfer. Refer to 3.4.2 - Load Transfer Procedures.

Figure 42 Load on bypass (UPS available)

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD

BFB

MBB

 

Critical

 

Load

 

AC Output

BIB

MIB

UPS MODULE

Static

Switch

Disconnects

Static

Bypass

Switch

Bypass CB

CONTROL POWER

RIB

INPUT

CB

MAIN INPUT

SWITCHGEAR

Controls

 

Rectifier/

Inverter

Charger

 

MBD

OUTPUT

CB

Battery

The UPS system control logic will initiate an automatic transfer to bypass if an overload condition exceeds the system current versus time window or if a UPS fault is detected. An automatic retransfer to the UPS system may be initiated when recovering from system overloads lasting less than five min- utes. Refer to 3.5 - Automatic Operations.

59

Image 65
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions System Description Other Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls Options Temperature-Compensated Charging Customer Alarm InterfaceBattery Load Testing Automatic RestartUPS Module Battery PlantGeneral Component Descriptions Software Detailed Component DescriptionsControls Hardware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Static Switch Backfeed ProtectionBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Display Screen and Operator Controls Features100kVA 500kVA 1000kVA Description Function Operator controls, typical systemDescription Function Series 610 UPS operator control panelMenu tree Menu Tree NavigationMaster menu screen Master Menu ScreenOperation Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Monitor/Mimic display example Utility fail Walk-in display screen Walk-In Display ScreenStatus reports screen Status Reports ScreensEvent History Present StatusHistory status report screen History StatusSystem Status Battery Cycle MonitorBattery cycle monitoring summary screen System configuration screens System Configuration ScreensMaximum auto-retransfer attempts screen Maximum Auto-Retransfer AttemptsDate screen DateTime screen TimeAuto dial screen Auto DialSystem Options Language SelectionContinuous Duty Static Switch Optional Additional alarm messages Alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelOverload Alarm Alarm Limit Settings ScreenBattery Discharging Low BatteryBattery Rating 100% Battery Shutdown 60 MinutesBattery Rating Temperature Limit Setting OptionalLoad transfer procedure screen Load Transfer Procedures ScreenRefer to 3.4.1 Start-Up Procedure for more details Start-Up Procedures ScreenBattery Time Screen Shutdown Procedures ScreenBattery time screen 15-minute discharge Elapsed Time Minutes Upper Limit Actual Lower LimitStatus Reports Screens Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenAlarm and status message screen Alarm and Status Messages Status MessagesAbbreviations used in alarm messages Alarm MessagesAC Input Alarm messages and corrective actionsUPS System Cooling UPS SystemAlarm Message Special Functions Alarm messages-summaryAuto-Dial Communication InterfacesWorldwide Reporting Local Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Requesting InformationRemote Monitor Panel Series 610 terminal commandsSeparate / Simultaneous Outputs Keys FunctionAbbreviation Circuit Breaker Load on BypassCircuit breaker abbreviations Load on bypass UPS available OK to TransferLoad on UPS bypass available Momentary Overloads Momentary overload through pulse-parallel static switchInput power fail-load on battery Input Power Failure-Load on BatteryLoad on UPS-battery not available Off BatteryEmergency Module Off Refer to 3.4.4 Shutdown ProceduresEmergency power off Remote Emergency Power OffModule Shutdown Refer to 3.3.9 Maintenance BypassLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Start-Up Procedure Manual ProceduresStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load transfer procedures screen Load Transfer ProceduresMaintenance Bypass Load Transfers Shutdown Procedures Shutdown Procedures Module Shutdown ProcedureLocal Emergency Modules Off Lemo Remote Emergency Power Off RepoBattery exercise control screen above and results below Battery Exercise ProceduresOverloads Without Transfer Automatic Operations1000% 150%Automatic Retransfers to UPS Automatic Transfers to Bypass Overload ConditionAutomatic Transfers to Bypass UPS System Faults Sequence of Operation Automatic Restart OptionalEnabling Automatic Restart Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentKVA Power factor pf KVARating Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Page Company Behind the Products Technical Support/ServiceLocations United States