Operation
Maximum Auto-Retransfer Attempts
When a UPS output overload condition exceeds a
(0 to 5) that the UPS attempts to retransfer the load back to the UPS within a one hour time period.
If more than the selected number of overloads occurs during one hour, the critical load remains on the bypass line and must be manually retransferred to the UPS system. Note that you should determine the cause of any overload condition.
NOTE
Note that automatic retransfers are initiated only if the critical load was transferred to the bypass line because of a system overload. If an automatic transfer to bypass occurred for any other reason, an automatic retransfer will not be initiated. Refer to 3.5.3 - Automatic Retransfers to UPS.
To change the Maximum
1.From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto- Retransfer Attempts.
2.Press the Select pad. The screen below will appear.
3.Press the Up pad to increase the value or the Down pad to decrease it.
Figure 21 Maximum auto-retransfer attempts screen
©
MAX
LOWER INPUT
0
UP : INCREASE
DOWN : DECREASE
SELECT : EXIT
VALUE
3
UPPER LIMIT
5
33