Liebert 610 manual UPS System, Cooling

Page 59

Operation

Table 4 Alarm messages and corrective actions, continued

Alarm

Message

Special

Functions

Meaning and Corrective Action

UPS SYSTEM, continued

 

 

The Emergency Module Off (or Emergency Power Off) switch has been pressed, which

Emergency

D*, L, S

caused the UPS system to shut down and transfer the load to the bypass line (or all power

Off

to the critical load has been shut down). Determine the cause of the emergency condition

 

 

 

and correct it if possible. Contact Liebert Global Services if you require assistance.

 

 

 

 

 

The Battery Cycle Monitor can retain information about the last 132 battery discharge

Battery Cycle

D, S

events. When the storage buffer approaches its capacity, this warning message is

Buffer Warning

broadcast via terminal and modem communication channels and a complete listing of all

 

 

 

records is sent to the terminal port. The message clears after 30 seconds.

 

 

 

COOLING

 

 

Ambient

 

The intake air to the UPS module exceeds the specified maximum temperature. This

Overtempera-

D, R, S

condition only causes an alarm, but should be corrected immediately to prevent damage to

ture

 

equipment due to overheating.

 

 

A fault in one or more of the blower motors has occurred. This condition only causes an

Blower Failed

D, S

alarm, but if not promptly corrected it could cause an equipment overtemperature condition

that would shut down the UPS module. Check the blowers for proper operation. Contact

 

 

 

 

Liebert Global Services if you require assistance.

 

 

Sensors on power semiconductor heat sinks detect temperatures above the steady state

Equipment

 

limits for these components. The control logic sets off the alarm but does not shut down the

Overtempera-

D, S

UPS module if the condition lasts less than 10 minutes. Check the air intake, air exhaust and

ture

 

filters. Reduce the load or transfer it to bypass. Contact Liebert Global Services if the alarm

 

 

persists.

Overtempera-

 

An Equipment Overtemperature condition has persisted for more than 10 minutes. The load

D, F

is transferred to the bypass line and the UPS module is shut down. Check the air intake, air

ture Time-out

 

exhaust and filters before attempting to start-up the UPS.

 

 

 

 

 

 

 

Battery self-test can be enabled from System Options screen. For test to start, the following

 

 

conditions must be valid:

 

 

1. No Battery Overtemp Alarm must exist.

 

 

2. Battery input and output circuit breakers must be closed.

Battery

3. All three input volt phases must be within nominal range (+10%, -20%).

Exercise

4. DC volts must be greater than (DC Ref) -20V. For a 540 bus, the nominal float voltage for

 

 

 

240 cells (the DC voltage reference setting) the DC voltage on the battery must be greater

 

 

than 520VDC.

 

 

5. Battery charge must be greater than 90%.

 

 

6. Load must be greater than 15%.

REMOTE MONITOR PANELS

Load On UPS

R

The UPS is operating properly. No corrective action is necessary.

 

 

 

New Alarm

R

Another new alarm message has been registered on the UPS system. Clear the new alarm

condition, if possible.

 

 

Summary

R

One or more of the UPS module alarm messages has been activated. Use the Present

Status screen to determine which alarms are active. Clear the new alarm condition, if

Alarm

 

possible to do so.

 

 

 

 

 

D = auto-dial

L = latches

 

E = logs only

R = remote

 

F = freezes

S = summary

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

53

Image 59
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions System Description Other Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls Options Automatic Restart Customer Alarm InterfaceTemperature-Compensated Charging Battery Load TestingUPS Module Battery PlantGeneral Component Descriptions Software Detailed Component DescriptionsControls Hardware Input Circuit Breaker Input Power FactorRectifier/Charger OperationBattery Equalize Charge Circuit Battery Charging CircuitBattery Disconnect Battery Charge Current LimitingOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterPulsed Parallel Operation Static Switch Backfeed ProtectionStatic Bypass Bypass Circuit BreakerTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Display Screen and Operator Controls Features100kVA 500kVA 1000kVA Description Function Operator controls, typical systemDescription Function Series 610 UPS operator control panelMenu tree Menu Tree NavigationMaster menu screen Master Menu ScreenOperation Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Monitor/Mimic display example Utility fail Walk-in display screen Walk-In Display ScreenStatus reports screen Status Reports ScreensEvent History Present StatusHistory status report screen History StatusSystem Status Battery Cycle MonitorBattery cycle monitoring summary screen System configuration screens System Configuration ScreensMaximum auto-retransfer attempts screen Maximum Auto-Retransfer AttemptsDate screen DateTime screen TimeAuto dial screen Auto DialSystem Options Language SelectionContinuous Duty Static Switch Optional Standard Remote Monitor Indications Channel Alarm messagesAdditional alarm messages Remote MonitorLow Battery Alarm Limit Settings ScreenOverload Alarm Battery DischargingTemperature Limit Setting Optional Battery Shutdown 60 MinutesBattery Rating 100% Battery RatingLoad transfer procedure screen Load Transfer Procedures ScreenRefer to 3.4.1 Start-Up Procedure for more details Start-Up Procedures ScreenBattery Time Screen Shutdown Procedures ScreenBattery time screen 15-minute discharge Elapsed Time Minutes Upper Limit Actual Lower LimitStatus Reports Screens Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenAlarm and status message screen Alarm and Status Messages Status MessagesAbbreviations used in alarm messages Alarm MessagesAC Input Alarm messages and corrective actionsUPS System Cooling UPS SystemAlarm Message Special Functions Alarm messages-summaryAuto-Dial Communication InterfacesWorldwide Reporting Requesting Information Local Reporting to a TerminalLocal Reporting to a Monitor Site Reporting SiteScan or SnmpKeys Function Series 610 terminal commandsRemote Monitor Panel Separate / Simultaneous OutputsAbbreviation Circuit Breaker Load on BypassCircuit breaker abbreviations Load on bypass UPS available OK to TransferLoad on UPS bypass available Momentary Overloads Momentary overload through pulse-parallel static switchInput power fail-load on battery Input Power Failure-Load on BatteryLoad on UPS-battery not available Off BatteryEmergency Module Off Refer to 3.4.4 Shutdown ProceduresEmergency power off Remote Emergency Power OffModule Shutdown Refer to 3.3.9 Maintenance BypassLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Start-Up Procedure Manual ProceduresStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load transfer procedures screen Load Transfer ProceduresMaintenance Bypass Load Transfers Shutdown Procedures Shutdown Procedures Module Shutdown ProcedureLocal Emergency Modules Off Lemo Remote Emergency Power Off RepoBattery exercise control screen above and results below Battery Exercise Procedures150% Automatic OperationsOverloads Without Transfer 1000%Automatic Retransfers to UPS Automatic Transfers to Bypass Overload ConditionAutomatic Transfers to Bypass UPS System Faults Sequence of Operation Automatic Restart OptionalEnabling Automatic Restart Maintenance Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Recommended Test Equipment Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Corrective ActionsKVA Power factor pf KVARating Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Page United States Technical Support/ServiceCompany Behind the Products Locations