Operation
3.2.6Alarm Limit Settings Screen
Go to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad and the Limit Settings screen is displayed.
The Alarm Limit Settings screen has Security Access to enable an authorized Liebert
! CAUTION
All alarm limit settings are application matched and
Figure 29 Alarm limit settings screen
|
|
|
|
|
|
| UP : CURSOR UP |
SECURITY ACCESS |
|
|
|
|
| ||
|
|
|
|
|
| ||
© |
|
| DOWN : CURSOR DOWN | ||||
|
|
| |||||
|
| SELECT : CHOOSE | |||||
|
|
| ALARM SETTINGS |
|
|
| |
| EXIT |
|
|
|
|
| |
Overload Alarm | 104 | % |
| ||||
DC Over Voltage | 600 | VDC |
| ||||
Battery Discharging | 480 | VDC |
| ||||
Low Battery | 437 | VDC |
| ||||
Battery Shutdown (15 minutes) | 384 | VDC |
| ||||
| Upper Point (60 minutes) | 427 | VDC |
| |||
Battery Rating (100%) | 500 | KW | 15 min | ||||
Battery Rating | 250 | KW | 45 min | ||||
Temperature Limit Setting | 28 C |
|
|
|
Overload Alarm
This alarm setting initiates an alarm message on the display screen warning the operator that the UPS system output current has exceeded the specified limit. This condition only activates an alarm. The UPS does not shut down, but a separate control circuit will transfer the critical load to bypass if the current and time of the overload condition exceeds system capability.
DC Overvoltage
This setting limits the maximum permitted level of the DC bus voltage. When this setting is exceeded, an alarm indication appears on the module display screen, the UPS transfers the load to the bypass line, and the input and battery circuit breakers trip open.
NOTE
The following battery alarm settings are
Battery Discharging
When the battery voltage on the DC bus falls below this limit for 5 seconds, a Battery Discharging alarm message is displayed on the module screen. This means that the battery is discharging due to an input voltage sag or interruption or a module output overload.
Low Battery
While the battery is discharging, this alarm warns the operator that the Battery Shutdown level is approaching. This is generally set for a reserve time of approximately 5 minutes (typically 10 volts above the
Battery Shutdown (15 Minutes)
When the battery voltage decreases to this limit for five seconds during the first 15 minutes of the dis- charge, the battery circuit breaker opens to prevent overdischarge. Note that the rated battery reserve time at your site may be other than 15 minutes.
40