Liebert 610 manual Transfer and Retransfer Conditions

Page 21

Theory of Operation

Transfer and Retransfer Conditions

1.Automatic Transfers to Bypass: Critical bus conditions that will initiate an automatic transfer of the critical load from the UPS inverter output to the bypass source are:

a.Output Overload: overcurrent condition in excess of the current versus time overload capacity curve. See Figure 58.

b.Overvoltage/Undervoltage (OV/UV): critical bus voltage is outside the allowable tolerance.

c.Inverter Inoperative: inverter diagnostic circuitry senses an imminent inverter output OV/UV condition:

1.Battery discharged to the shutdown voltage.

2.Inverter or rectifier fault condition (power, logic or overtemperature) present or imminent.

3.Failure of system logic or logic power.

4.Emergency Module Off (EMO) circuit activated.

2.Manual Transfers: Manual transfers may be initiated at any time provided no transfer inhibition conditions are present.

3.Transfer Inhibited: A manual transfer to the bypass source will be inhibited if any of the following conditions exist:

a.UPS system to bypass voltage difference (V) exceeds a predetermined percentage (normally ±5%).

b.Static switch disconnects open.

c.OK to Transfer signal from the control logic is not present.

NOTE

A load transfer to the bypass line will be completed whenever an automatic transfer to bypass is initiated. If the Static Switch Unable alarm message is present for any reason (including a greater than ±20° phase lock synchronization error), the automatic transfer will be interrupted for 40 to 120 milliseconds. Because of the reliability of the UPS components, an interrupted load transfer is a very unlikely occurrence.

4.Automatic Retransfers to UPS: Critical bus conditions that must be present to initiate an automatic retransfer (Auto-Rexfer) of the critical load from the bypass source to the UPS system are:

a.The number of Auto-Rexfer Attempts selected must be greater than zero (0). If zero (0) is selected, no automatic retransfer will occur.

b.Critical load was initially transferred to the bypass source due to a system overload only.

c.Overload condition has since been corrected (the load has dropped below 100% of the rated load).

d.Both the Input and Battery (MBD) circuit breakers have remain closed since the overload transfer.

e.OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes of the overload transfer. (A manually initiated retransfer from bypass is required for overloads lasting 5 minutes or more.)

f.Cyclic-type system overloads, which occur up to five (select range is 0 to 5) times in

60minutes, are automatically returned to the UPS system for each event including the Nth overload. A manually initiated retransfer from bypass is required for the N+1 overload.

5.Manual Retransfers: Manual retransfers may be initiated at any time provided no retransfer inhibition conditions are present.

6.Retransfer Inhibited: A retransfer (automatic or manual) from the bypass source to the UPS system shall be inhibited if any of the following conditions exist:

a.Manual (and Automatic) Retransfer Inhibitions:

1.UPS system-to-bypass voltage difference (V) exceeds a predetermined percentage (normally ±5%).

2.Bypass circuit breaker is inoperative.

3.OK to Transfer signal from the control logic is not present.

4.Inverter or rectifier fault.

b.Automatic Retransfer Inhibitions (in addition to those above):

1.The load transfer to bypass was not caused by an output overload.

2.Excessive cyclical overloads within a one-hour period.

3.Retransfer conditions are not satisfied within 5 minutes of the initial transfer.

15

Image 21
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions System Description Reliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Temperature-Compensated Charging Customer Alarm InterfaceBattery Load Testing Automatic RestartBattery Plant General Component DescriptionsUPS Module Detailed Component Descriptions Controls HardwareSoftware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Static Switch Backfeed ProtectionBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Display Screen and Operator Controls Features100kVA 500kVA 1000kVA Description Function Operator controls, typical systemDescription Function Series 610 UPS operator control panelMenu tree Menu Tree NavigationMaster menu screen Master Menu ScreenOperation Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-in display screen Walk-In Display ScreenStatus reports screen Status Reports ScreensEvent History Present StatusHistory status report screen History StatusSystem Status Battery Cycle MonitorBattery cycle monitoring summary screen System configuration screens System Configuration ScreensMaximum auto-retransfer attempts screen Maximum Auto-Retransfer AttemptsDate screen DateTime screen TimeAuto dial screen Auto DialSystem Options Language SelectionContinuous Duty Static Switch Optional Additional alarm messages Alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelOverload Alarm Alarm Limit Settings ScreenBattery Discharging Low BatteryBattery Rating 100% Battery Shutdown 60 MinutesBattery Rating Temperature Limit Setting OptionalLoad transfer procedure screen Load Transfer Procedures ScreenRefer to 3.4.1 Start-Up Procedure for more details Start-Up Procedures ScreenBattery Time Screen Shutdown Procedures ScreenBattery time screen 15-minute discharge Elapsed Time Minutes Upper Limit Actual Lower LimitStatus Reports Screens Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenAlarm and status message screen Alarm and Status Messages Status MessagesAbbreviations used in alarm messages Alarm MessagesAC Input Alarm messages and corrective actionsUPS System Cooling UPS SystemAlarm Message Special Functions Alarm messages-summaryCommunication Interfaces Worldwide ReportingAuto-Dial Local Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Requesting InformationRemote Monitor Panel Series 610 terminal commandsSeparate / Simultaneous Outputs Keys FunctionLoad on Bypass Circuit breaker abbreviationsAbbreviation Circuit Breaker Load on bypass UPS available OK to TransferLoad on UPS bypass available Momentary Overloads Momentary overload through pulse-parallel static switchInput power fail-load on battery Input Power Failure-Load on BatteryLoad on UPS-battery not available Off BatteryEmergency Module Off Refer to 3.4.4 Shutdown ProceduresEmergency power off Remote Emergency Power OffModule Shutdown Refer to 3.3.9 Maintenance BypassLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Start-Up Procedure Manual ProceduresStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load transfer procedures screen Load Transfer ProceduresMaintenance Bypass Load Transfers Shutdown Procedures Shutdown Procedures Module Shutdown ProcedureLocal Emergency Modules Off Lemo Remote Emergency Power Off RepoBattery exercise control screen above and results below Battery Exercise ProceduresOverloads Without Transfer Automatic Operations1000% 150%Automatic Retransfers to UPS Automatic Transfers to Bypass Overload ConditionAutomatic Transfers to Bypass UPS System Faults Automatic Restart Optional Enabling Automatic RestartSequence of Operation Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentPower factor pf KVA RatingKVA Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Page Company Behind the Products Technical Support/ServiceLocations United States