Liebert 610 manual UPS System

Page 58

Operation

Table 4 Alarm messages and corrective actions, continued

Alarm

Message

Special

Functions

Meaning and Corrective Action

BYPASS, continued

 

 

The UPS output is not synchronized to the bypass power source, the static bypass switch is

Static Switch

 

disconnected, or it has failed internally. Emergency and overload transfer to the bypass

D, S

source is not available. If the module has a manual Static Switch Disconnect, set it to ON

Unable

(closed). If the module does not have a manual disconnect switch, open and re-close the

 

 

 

static switch fuseholder. If the alarm conditions are automatically corrected, reset the alarm

 

 

to clear it. Contact Liebert Global Services if the alarm stays on.

Bypass Not

 

The bypass power source voltage is not within specifications. Correct the bypass AC power

Available

 

source.

Bypass Phase

 

The power conductors on the bypass line are not wired to the UPS in the required

 

sequence. This alarm should appear only during initial start-up or after a repair to the source

Sequence

D, L, S

power system. Disconnect power from the bypass line and correct the wiring. Liebert Global

Wrong

 

 

Services must be present during initial start-up of your UPS System.

 

 

UPS SYSTEM

 

 

Input Current

D, E

At least one input phase differs from the average current by 10% or more for four (4) hours.

Contact Liebert Global Services. If the condition persists, transfer the load to the bypass

Unbalanced

 

line.

 

 

Control Power

 

The logic control power supply from the UPS output is not operating properly. The UPS

D, L, S

module continues operating but will shut down if the input power fails. Contact Liebert

Fail

 

Global Services immediately.

 

 

 

 

 

Output Over/

 

Output frequency differs from the nominal (60 Hz) by more than 0.5 Hz. No transfer or

Underfre-

D, L, S

shutdown occurs. Contact Liebert Global Services at once.

quency

 

 

 

 

The UPS module output voltage is under the minimum permitted (-12%) deviation from

Output

D, F, L, S

nominal. The load automatically transfers to the bypass line. If the alarm condition is no

Undervoltage

longer present, reset the alarm and retransfer the load from bypass to UPS. Contact Liebert

 

 

 

Global Services if alarm persists.

 

 

 

 

 

The UPS module output voltage is above the maximum permitted (+10%) deviation from

Output

D, F, L, S

nominal. The load automatically transfers to the bypass line. The UPS module is shut down

Overvoltage

and isolated. Contact Liebert Global Services at once. Do not attempt to reset circuit

 

 

 

breakers.

 

 

The UPS output current exceeds the rated system load current. This condition causes an

Overload

D, R, S

alarm only, the UPS does not shut down. Determine cause of the overload. Reduce the load

 

 

until the overload condition is corrected. Reset the UPS alarm.

 

 

The load on the UPS has exceeded the current versus time window of system overload

Overload

D, F, L, S

capacity. The UPS system transfers the load to bypass. Reduce the load. If the system does

Transfer

not initiate an automatic load retransfer, manually retransfer the critical load from the bypass

 

 

 

line to the UPS. Reset the alarm.

 

 

Excessive reverse power flow from the critical bus into the UPS inverter has occurred,

Reverse

D, F, L, S

probably because of low inverter output voltage or a phase mismatch. The UPS module is

Power

shut down and isolated. Contact Liebert Global Services immediately. Do not attempt to

 

 

 

reset circuit breakers.

 

 

 

Rectifier Fuse

D, F, S

At least one of these fuses has opened. The UPS automatically transfers the critical load to

Blown

the bypass line. Circuit breakers trip open to shut down and isolate the UPS module.

 

 

 

Contact Liebert Global Services immediately. Do not attempt to reset the circuit breakers.

Inverter Fault

D, F, S

 

 

 

 

 

 

At least one of the following alarm conditions is present: Inverter Fault, Rectifier Fuse Blown,

Hardware

 

Reverse Power, Overload Shutdown, logic power supply failure or inverter output symmetry

D*

failure. The load automatically transfers to the bypass line. The UPS module is shut down

Shutdown

 

and isolated. Contact Liebert Global Services at once. Do not attempt to reset the circuit

 

 

 

 

breakers.

 

 

 

D = auto-dial

L = latches

 

E = logs only

R = remote

 

F = freezes

S = summary

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

52

Image 58
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Designed for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Battery Load Testing Customer Alarm InterfaceTemperature-Compensated Charging Automatic RestartGeneral Component Descriptions Battery PlantUPS Module Controls Hardware Detailed Component DescriptionsSoftware Operation Input Power FactorRectifier/Charger Input Circuit BreakerBattery Charge Current Limiting Battery Charging CircuitBattery Disconnect Battery Equalize Charge CircuitInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceBypass Circuit Breaker Static Switch Backfeed ProtectionStatic Bypass Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Remote Monitor Alarm messagesAdditional alarm messages Standard Remote Monitor Indications ChannelBattery Discharging Alarm Limit Settings ScreenOverload Alarm Low BatteryBattery Rating Battery Shutdown 60 MinutesBattery Rating 100% Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsWorldwide Reporting Communication InterfacesAuto-Dial Site Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Requesting InformationSeparate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Keys FunctionCircuit breaker abbreviations Load on BypassAbbreviation Circuit Breaker OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results below1000% Automatic OperationsOverloads Without Transfer 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Enabling Automatic Restart Automatic Restart OptionalSequence of Operation Maintenance Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingRecord Log Routine MaintenanceAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery voltage record Battery retorque valuesRack-Mounted Batteries Detection of Trouble Torque specifications unless otherwise labeledTorque Requirements Corrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Recommended Test EquipmentRating Power factor pf KVAKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Locations Technical Support/ServiceCompany Behind the Products United States