Operation
Table 4 Alarm messages and corrective actions, continued
Alarm
Message
Special
Functions
Meaning and Corrective Action
BYPASS, continued
|
| The UPS output is not synchronized to the bypass power source, the static bypass switch is | |
Static Switch |
| disconnected, or it has failed internally. Emergency and overload transfer to the bypass | |
D, S | source is not available. If the module has a manual Static Switch Disconnect, set it to ON | ||
Unable | (closed). If the module does not have a manual disconnect switch, open and | ||
| |||
|
| static switch fuseholder. If the alarm conditions are automatically corrected, reset the alarm | |
|
| to clear it. Contact Liebert Global Services if the alarm stays on. | |
Bypass Not |
| The bypass power source voltage is not within specifications. Correct the bypass AC power | |
Available |
| source. | |
Bypass Phase |
| The power conductors on the bypass line are not wired to the UPS in the required | |
| sequence. This alarm should appear only during initial | ||
Sequence | D, L, S | ||
power system. Disconnect power from the bypass line and correct the wiring. Liebert Global | |||
Wrong |
| ||
| Services must be present during initial | ||
|
| ||
UPS SYSTEM |
|
| |
Input Current | D, E | At least one input phase differs from the average current by 10% or more for four (4) hours. | |
Contact Liebert Global Services. If the condition persists, transfer the load to the bypass | |||
Unbalanced | |||
| line. | ||
|
| ||
Control Power |
| The logic control power supply from the UPS output is not operating properly. The UPS | |
D, L, S | module continues operating but will shut down if the input power fails. Contact Liebert | ||
Fail | |||
| Global Services immediately. | ||
|
| ||
|
|
| |
Output Over/ |
| Output frequency differs from the nominal (60 Hz) by more than 0.5 Hz. No transfer or | |
Underfre- | D, L, S | shutdown occurs. Contact Liebert Global Services at once. | |
quency |
|
| |
|
| The UPS module output voltage is under the minimum permitted | |
Output | D, F, L, S | nominal. The load automatically transfers to the bypass line. If the alarm condition is no | |
Undervoltage | longer present, reset the alarm and retransfer the load from bypass to UPS. Contact Liebert | ||
| |||
|
| Global Services if alarm persists. | |
|
|
| |
|
| The UPS module output voltage is above the maximum permitted (+10%) deviation from | |
Output | D, F, L, S | nominal. The load automatically transfers to the bypass line. The UPS module is shut down | |
Overvoltage | and isolated. Contact Liebert Global Services at once. Do not attempt to reset circuit | ||
| |||
|
| breakers. | |
|
| The UPS output current exceeds the rated system load current. This condition causes an | |
Overload | D, R, S | alarm only, the UPS does not shut down. Determine cause of the overload. Reduce the load | |
|
| until the overload condition is corrected. Reset the UPS alarm. | |
|
| The load on the UPS has exceeded the current versus time window of system overload | |
Overload | D, F, L, S | capacity. The UPS system transfers the load to bypass. Reduce the load. If the system does | |
Transfer | not initiate an automatic load retransfer, manually retransfer the critical load from the bypass | ||
| |||
|
| line to the UPS. Reset the alarm. | |
|
| Excessive reverse power flow from the critical bus into the UPS inverter has occurred, | |
Reverse | D, F, L, S | probably because of low inverter output voltage or a phase mismatch. The UPS module is | |
Power | shut down and isolated. Contact Liebert Global Services immediately. Do not attempt to | ||
| |||
|
| reset circuit breakers. | |
|
|
| |
Rectifier Fuse | D, F, S | At least one of these fuses has opened. The UPS automatically transfers the critical load to | |
Blown | the bypass line. Circuit breakers trip open to shut down and isolate the UPS module. | ||
| |||
|
| Contact Liebert Global Services immediately. Do not attempt to reset the circuit breakers. | |
Inverter Fault | D, F, S | ||
| |||
|
|
| |
|
| At least one of the following alarm conditions is present: Inverter Fault, Rectifier Fuse Blown, | |
Hardware |
| Reverse Power, Overload Shutdown, logic power supply failure or inverter output symmetry | |
D* | failure. The load automatically transfers to the bypass line. The UPS module is shut down | ||
Shutdown | |||
| and isolated. Contact Liebert Global Services at once. Do not attempt to reset the circuit | ||
|
| ||
|
| breakers. | |
|
|
| |
D = | L = latches |
| |
E = logs only | R = remote |
| |
F = freezes | S = summary |
|
D* =
52