Liebert 610 Static Bypass, Bypass Circuit Breaker, Pulsed Parallel Operation, Load Transfers

Page 20

Theory of Operation

2.2.5Static Bypass

A static bypass is an integral part of the UPS. The static bypass consists of a static bypass switch, consisting of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase and bypass power switching devices (motor-operated circuit breakers). An automatic transfer control circuit senses the status of the operator controls, UPS logic signals and alarm messages and critical bus operating con- ditions. If the inverter output can no longer supply the critical load, the static bypass switch (in con- junction with motorized circuit breakers) automatically transfers the critical load to the bypass source without interruption.

Bypass Circuit Breaker

The motor-operated bypass circuit breaker, wired in parallel with the static switch, automatically closes within 200 milliseconds after the load is transferred to the bypass power source, removing the static switch from the power flow.

Pulsed Parallel Operation

When an overload condition such as transformer inrush current or a branch load circuit fault exceeds 155% of the full-load current rating, the static bypass switch pulses on for 40 milliseconds. This allows up to 1000% rated full load current (as limited by distribution feeders) from the bypass source to clear the overload without closing the bypass circuit breaker (a Liebert design exclusive). The bypass source is in parallel with the UPS system, permitting the bypass source to carry the initial overload current. If the overload clears before 40 milliseconds, a load transfer to bypass is not made. If the overload condition exceeds the inverter capacity, the automatic transfer is made (maintaining the load voltage within the specified limits).

This pulsed static switch operation reduces nuisance operation of motor-operated circuit breakers for such short-term conditions and serves, under some circumstances, as a backup in the event that an external bypass feeder breaker trips open during this pulse-paralleling period.

Load Transfers

Transfers to (transfer) or from (retransfer) the bypass may be performed automatically or manually in a make-before-break (MBB) sequence. This is accomplished through the overlapping operation of the UPS output and the bypass power switching devices.

Manual load transfers and retransfers are initiated by the operator from the UPS control panel.

In a manual operation or an automatic retransfer, the two motorized circuit breakers UPS output and system bypass (SBB) are both closed simultaneously for a short period of time (overlap).

Automatic transfers are initiated by the UPS system control logic when an overload is beyond the specified capabilities of the UPS inverter or when a fault occurs within the UPS module. An auto- matic retransfer is initiated if this function is enabled and if system conditions for a retransfer are present.

In an automatic transfer, the circuit breakers do not overlap, but, during the short time gap, bypass power is supplied to the critical load through the solid state static switch.

Fuse Protection

The static bypass switch path uses two back-to-back SCRs per phase. Each phase is individually pro- tected by a fuse sized to clear only in the event of a catastrophic fault. This is a more reliable method than depending on external protection devices. The fuses are in the circuit to protect the critical bus distribution equipment against catastrophic faults. The static switch SCRs are oversized to easily handle any current surges that may blow the fuses.

Static Switch Backfeed Protection

The static bypass system is equipped with redundant disconnect circuits that prevent backfeed of lethal voltage to a de-energized bypass input in the event of a shorted static switch SCR. If the bypass input power is interrupted, the static switch disconnect devices will open, preventing backfeed of inverter voltage to the bypass input terminals.

14

Image 20
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Other Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls Options Customer Alarm Interface Temperature-Compensated ChargingBattery Load Testing Automatic RestartUPS Module Battery PlantGeneral Component Descriptions Software Detailed Component DescriptionsControls Hardware Input Power Factor Rectifier/ChargerOperation Input Circuit BreakerBattery Charging Circuit Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Backfeed Protection Static BypassBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Alarm messages Additional alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelAlarm Limit Settings Screen Overload AlarmBattery Discharging Low BatteryBattery Shutdown 60 Minutes Battery Rating 100%Battery Rating Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsAuto-Dial Communication InterfacesWorldwide Reporting Local Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Requesting InformationSeries 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Keys FunctionAbbreviation Circuit Breaker Load on BypassCircuit breaker abbreviations OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results belowAutomatic Operations Overloads Without Transfer1000% 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Sequence of Operation Automatic Restart OptionalEnabling Automatic Restart Maintenance Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Reporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Recommended Test EquipmentKVA Power factor pf KVARating Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Technical Support/Service Company Behind the ProductsLocations United States