Operation
Remote Monitor
The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for customer use through a set of contacts on a separate terminal board.
Table 1 | Alarm messages |
|
|
| |
Standard Remote Monitor Indications | Channel | |
|
| |
Load On UPS | CH1 | |
|
| |
Load On Bypass | CH2 | |
|
| |
Battery Discharging | CH3 | |
|
| |
Low Battery Warning | CH4 | |
|
|
|
Overload |
| CH5 |
|
| |
Ambient Overtemp | CH6 | |
|
| |
System Summary Alarm | CH7 | |
|
|
|
New Alarm |
| CH8 |
|
|
|
The following alarms, as well as those listed above, will activate the System Summary Alarm.
When the New Alarm, System Summary Alarm or Module Summary Alarm is activated, you can get more information at the Operator Display Panel or through a remote terminal. Refer to 3.2.14 - Com- munication Interfaces.
Table 2 Additional alarm messages
Battery CB Open
Blower Failed
Control Power Fail
DC Capacitor Fuse Blown
DC Ground Fault
DC Overvoltage Shutdown
Emergency Off
Equipment Overtemperature
Static Switch Unable
Inverter Fault
Low Battery Shutdown
Output Overvoltage
Output Undervoltage
Overload Shutdown
Overload Transfer
Rectifier Fuse Blown
Reverse Power