Liebert manual Series 610 UPS operator control panel, Description Function

Page 25

Operation

Figure 4 Series 610 UPS operator control panel

Item

Description

Function

1

Display Screen

This screen displays all vital UPS information in one convenient location. All of the UPS

monitoring functions and conditions are indicated here.

 

 

 

 

This touch-sensitive pad (button) is used to move the cursor up through various

2

Up

selections present on the display screen. Note that all pads on this control panel have

 

 

touch-sensitive switches behind them.

3

Down

Similar to the Up pad, this pad is used to move the cursor down through the various

selections present on the display screen.

 

 

 

 

After using the Up and Down pads to move the highlighted cursor to the desired menu

4

Select

item on the display screen, push this pad to tell the microprocessor to go to the

 

 

highlighted selection.

 

 

This pad is used to clear all of the alarm conditions that are no longer present. However,

5

Alarm Reset

all active alarms remain in memory and on the applicable screens until they are

 

 

corrected.

 

 

This push-to-turn knob permits adjustment of the UPS output voltage to meet load

6

Voltage Adjust

requirements or to match the bypass voltage before transferring the load to or from

 

 

bypass.

 

 

This pad activates the circuits that connect the UPS inverter to the critical load (a

7

UPS

retransfer). When this pad is pushed (along with Control Enable), the UPS output circuit

 

 

breaker closes and the bypass circuit breaker opens.

 

 

This pad activates the circuits that connect the bypass line to the critical load (a

8

Bypass

transfer). When this button is pushed (along with Control Enable), the bypass circuit

 

 

breaker closes and the UPS output circuit breaker opens.

9

Battery Trip

This pad can be used (along with Control Enable) to trip the module battery disconnect

(MBD) circuit breaker open (disconnecting the battery from the UPS module).

 

 

10

Control Enable

This pad must be pressed simultaneously with the UPS, Bypass or Battery Trip pads to

activate them.

 

 

 

 

This pad is used to silence the alarm horn after it is activated. When this switch is

11

Horn Off

pressed, the alarm horn is silenced but the active and latched alarm messages remain

on the screen. The alarm messages still displayed stop flashing to indicate they have

 

 

 

 

been acknowledged.

 

 

 

12

Alarm Horn and Red LED

This electronic horn sounds to alert nearby personnel whenever a new alarm occurs. A

red LED (light emitting diode) is located in the middle of the alarm horn.

 

 

 

 

During an emergency, pressing this guarded switch will transfer the load to bypass and

13

Emergency Module Off

then shut down and disconnect the UPS inverter, rectifier and battery. The load will

remain on bypass power. (Refer also to 3.4.4 - Shutdown Procedures for additional

 

 

 

 

performance options.)

19

Image 25
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions System Description Designed for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Temperature-Compensated Charging Customer Alarm InterfaceBattery Load Testing Automatic RestartGeneral Component Descriptions Battery PlantUPS Module Controls Hardware Detailed Component DescriptionsSoftware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Static Switch Backfeed ProtectionBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Display Screen and Operator Controls Features100kVA 500kVA 1000kVA Description Function Operator controls, typical systemDescription Function Series 610 UPS operator control panelMenu tree Menu Tree NavigationMaster menu screen Master Menu ScreenOperation Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-in display screen Walk-In Display ScreenStatus reports screen Status Reports ScreensEvent History Present StatusHistory status report screen History StatusSystem Status Battery Cycle MonitorBattery cycle monitoring summary screen System configuration screens System Configuration ScreensMaximum auto-retransfer attempts screen Maximum Auto-Retransfer AttemptsDate screen DateTime screen TimeAuto dial screen Auto DialSystem Options Language SelectionContinuous Duty Static Switch Optional Additional alarm messages Alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelOverload Alarm Alarm Limit Settings ScreenBattery Discharging Low BatteryBattery Rating 100% Battery Shutdown 60 MinutesBattery Rating Temperature Limit Setting OptionalLoad transfer procedure screen Load Transfer Procedures ScreenRefer to 3.4.1 Start-Up Procedure for more details Start-Up Procedures ScreenBattery Time Screen Shutdown Procedures ScreenBattery time screen 15-minute discharge Elapsed Time Minutes Upper Limit Actual Lower LimitStatus Reports Screens Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenAlarm and status message screen Alarm and Status Messages Status MessagesAbbreviations used in alarm messages Alarm MessagesAC Input Alarm messages and corrective actionsUPS System Cooling UPS SystemAlarm Message Special Functions Alarm messages-summaryWorldwide Reporting Communication InterfacesAuto-Dial Local Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Requesting InformationRemote Monitor Panel Series 610 terminal commandsSeparate / Simultaneous Outputs Keys FunctionCircuit breaker abbreviations Load on BypassAbbreviation Circuit Breaker Load on bypass UPS available OK to TransferLoad on UPS bypass available Momentary Overloads Momentary overload through pulse-parallel static switchInput power fail-load on battery Input Power Failure-Load on BatteryLoad on UPS-battery not available Off BatteryEmergency Module Off Refer to 3.4.4 Shutdown ProceduresEmergency power off Remote Emergency Power OffModule Shutdown Refer to 3.3.9 Maintenance BypassLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Start-Up Procedure Manual ProceduresStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load transfer procedures screen Load Transfer ProceduresMaintenance Bypass Load Transfers Shutdown Procedures Shutdown Procedures Module Shutdown ProcedureLocal Emergency Modules Off Lemo Remote Emergency Power Off RepoBattery exercise control screen above and results below Battery Exercise ProceduresOverloads Without Transfer Automatic Operations1000% 150%Automatic Retransfers to UPS Automatic Transfers to Bypass Overload ConditionAutomatic Transfers to Bypass UPS System Faults Enabling Automatic Restart Automatic Restart OptionalSequence of Operation Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingRecord Log Routine MaintenanceAir Filters Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalBattery voltage record Battery retorque valuesRack-Mounted Batteries Detection of Trouble Torque specifications unless otherwise labeledTorque Requirements Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentRating Power factor pf KVAKVA Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Page Company Behind the Products Technical Support/ServiceLocations United States