Operation
3.4Manual Procedures
The Liebert Series 610 UPS is designed to function while unattended by an operator. Many important functions are handled automatically by the system control logic, as explained in 3.5 - Automatic Operations. Other procedures must be performed manually.
Manual procedures available to the operator include
The LCD includes a screen to help you with each manual procedure by listing each step you must per- form.
This section lists
1.
2.Load Transfers: including transfers from UPS system to bypass and retransfers from bypass to the UPS system.
3.Shutdowns: including module shutdowns for maintenance procedures and emergency shutdowns.
3.4.1Start-Up Procedure
When the UPS module has been shut down for any reason, use this procedure to
NOTE
The following procedure assumes that the UPS installation inspection and initial
! CAUTION
The following procedure provides power to the critical load distribution system. Verify that the critical load distribution is ready to accept power. Make sure that personnel and equipment are ready for the critical load distribution system to be energized.
If your installation includes a Maintenance Bypass, you may already be supplying power to the criti- cal load equipment through the Maintenance Bypass. If there is no power to the critical load, apply power through the UPS bypass line per the following procedure.
During a
69