Liebert 610 manual Load Transfer Procedures Screen, Load transfer procedure screen

Page 48

Operation

3.2.7Load Transfer Procedures Screen

Go to the Master Menu and move the highlighted cursor to LOAD TRANSFER PROCEDURES. Press the Select pad and the Load Transfer Procedures screen is displayed.

Figure 30 Load transfer procedure screen

 

 

 

 

 

 

 

1

2

 

 

 

 

 

 

 

 

 

SELECT : MASTER MENU

 

 

SYNCHRONIZATION

 

 

 

 

 

 

 

VOLTAGE COMPARISON

 

 

 

 

 

 

A-B

B-C

C-A

 

 

FREQUENCY

-30

 

0

+30

UPS

-

480

480

480

 

 

 

 

 

4

60.0 Hz

 

 

 

 

 

 

 

 

BYPASS

-

481

480

479

60.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

MANUAL

 

 

 

 

 

 

 

 

 

 

ON UPS

 

 

 

TRANSFER INSTRUCTIONS

UPS LEAD

=

2 Deg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK TO TRANSFER

1.

Adjust the UPS voltage until it equals the

 

 

 

 

 

 

TRANSFER PROHIBIT

 

 

bypass voltage with the VOLTAGE ADJUST pot.

 

 

 

 

2.

If the OK TO TRANSFER message is highlighted,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

simultaneously press the BYPASS and CONTROL ENABLE

 

 

 

 

 

 

 

buttons.

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Verify that the transfer was successful by checking the

 

 

 

 

 

 

 

breaker status on the "MONITOR/MIMIC" screen.

 

 

 

 

 

 

 

 

4.

Press the ALARM RESET button to clear alarms which

 

 

 

 

 

 

 

are no longer active

 

 

 

 

 

 

 

 

The Load Transfer Procedures screen contains instructions to transfer the critical load between the UPS system and the bypass line. Comparisons of the UPS and bypass voltage, frequency and phase synchronization are displayed along with transfer status messages. The metered parameter values on the Load Transfer Procedures screen are updated at half-second intervals.

Refer to 3.3 - Modes of Operation and 3.4.2 - Load Transfer Procedures for more details.

Item 1 - Voltage Comparisons: This chart shows the UPS and bypass voltage and frequency com- parisons between each of the three phases. If the UPS and bypass voltages are not within specified tolerances, a manual transfer is not permitted and TRANSFER PROHIBIT is highlighted.

The Voltage Adjust knob (push-to-turn), located on the Operator Control Panel (Figure 4), is used to match the UPS output voltage to the bypass voltage. When the UPS and bypass voltages match within the specific tolerance, a manual transfer is possible and OK TO TRANSFER is highlighted.

! CAUTION

The UPS output voltage responds very slowly to inputs from the Voltage Adjust knob. Make small adjustments and wait several seconds each time for voltage to stabilize before continuing.

Item 2 - Synchronization: This display shows the phase synchronization between the UPS output and bypass power. If the phase displacement is outside of the tolerance, a manual transfer is not per- mitted and TRANSFER PROHIBIT is highlighted.

During normal operation, the synchronization display should read UPS LEAD from zero to 4 degrees.

Item 3 - Status Messages: Three messages are constantly displayed here. Only the active message is highlighted. If TRANSFER PROHIBIT is highlighted, manual transfers/retransfers cannot be per- formed and automatic retransfers will not be initiated.

Item 4 - Manual Transfer Instructions: These instructions assist the operator in transferring the critical load between the UPS system and the bypass line.

If the load is on the bypass line, step 2 on the screen will instruct you to press the UPS and Control Enable buttons to retransfer the load from the bypass line to the UPS system.

42

Image 48
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Reliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Customer Alarm Interface Temperature-Compensated ChargingBattery Load Testing Automatic RestartBattery Plant General Component DescriptionsUPS Module Detailed Component Descriptions Controls HardwareSoftware Input Power Factor Rectifier/ChargerOperation Input Circuit BreakerBattery Charging Circuit Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Backfeed Protection Static BypassBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Alarm messages Additional alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelAlarm Limit Settings Screen Overload AlarmBattery Discharging Low BatteryBattery Shutdown 60 Minutes Battery Rating 100%Battery Rating Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsCommunication Interfaces Worldwide ReportingAuto-Dial Local Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Requesting InformationSeries 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Keys FunctionLoad on Bypass Circuit breaker abbreviationsAbbreviation Circuit Breaker OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results belowAutomatic Operations Overloads Without Transfer1000% 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Automatic Restart Optional Enabling Automatic RestartSequence of Operation Maintenance Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Reporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Recommended Test EquipmentPower factor pf KVA RatingKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Technical Support/Service Company Behind the ProductsLocations United States