Liebert 610 manual Input Power Failure-Load on Battery, Input power fail-load on battery

Page 68

Operation

3.3.4Input Power Failure—Load on Battery

If the utility AC power source fails or is outside the acceptable range, the battery plant becomes the power source for the UPS module inverters. The UPS system continues to supply power to the critical load and also to the UPS controls.

You can use the Battery Time screen at the UPS modules to monitor the present battery voltage com- pared to the shutdown value. The length of time the battery can sustain the load depends on the size of the load and the size and condition of the battery plant. The battery plant is typically large enough to supply a 100% rated load for 10-15 minutes.

Alarm messages that indicate battery status are Battery Discharge, Low Battery and Battery Shut- down. The voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings screen. These limits were selected for your installation by Liebert Global Services during initial start- up.

The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the current in Amperes. Maximum battery discharge current ranges from 326 amps (for 150kVA) to 1619 amps (for 750kVA). Refer to the separate Installation Manual or drawings for specific data on your system.

Figure 45 Input power fail—load on battery

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD

BFB

MBB

 

Critical

 

Load

 

AC Output

BIB

MIB

UPS MODULE

Static

Switch

Disconnects

Static

Bypass

Switch

Bypass CB

CONTROL POWER

RIB

Controls

Rectifier/

Inverter

INPUT

CB

MAIN INPUT

SWITCHGEAR

Charger

MBD

OUTPUT

CB

Battery

62

Image 68
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Other Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls Options Customer Alarm Interface Temperature-Compensated ChargingBattery Load Testing Automatic RestartUPS Module Battery PlantGeneral Component Descriptions Software Detailed Component DescriptionsControls Hardware Input Power Factor Rectifier/ChargerOperation Input Circuit BreakerBattery Charging Circuit Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Backfeed Protection Static BypassBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Alarm messages Additional alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelAlarm Limit Settings Screen Overload AlarmBattery Discharging Low BatteryBattery Shutdown 60 Minutes Battery Rating 100%Battery Rating Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsAuto-Dial Communication InterfacesWorldwide Reporting Local Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Requesting InformationSeries 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Keys FunctionAbbreviation Circuit Breaker Load on BypassCircuit breaker abbreviations OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results belowAutomatic Operations Overloads Without Transfer1000% 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Sequence of Operation Automatic Restart OptionalEnabling Automatic Restart Maintenance Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Reporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Recommended Test EquipmentKVA Power factor pf KVARating Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Technical Support/Service Company Behind the ProductsLocations United States