Liebert 610 Battery Shutdown 60 Minutes, Battery Rating 100%, Temperature Limit Setting Optional

Page 47

Operation

Battery Shutdown (60 Minutes)

During extended outages or deep sags of more than 15 minutes, the shutdown voltage limit will ramp up gradually to this 60-minute limit to prevent lengthy discharge and possible battery damage. The battery circuit breaker opens when the battery voltage and the shutdown limit are equal for five sec- onds. See the Battery Time screen for more information. Also refer to the battery manufacturer’s manual, available on the manufacturer’s Web site.

Battery Rating (100%)

This setting is the full load discharge rating of the battery in kilowatts for the rated backup period. A typical rating might be 500 kW for 15 minutes.

Battery Rating

This setting is a battery discharge rating in kilowatts under partial load for an extended period, typi- cally 40 to 60 minutes. The UPS uses the two battery shutdown voltage settings and the two battery discharge ratings in computing rated and calculated time remaining during a discharge event.

Temperature Limit Setting (Optional)

This setting is visible when the optional battery-temperature-compensated charging board is installed. This setting determines the battery temperature that triggers the Battery Overtemp alarm. The alarm becomes active when the temperature setting is exceeded for more than one minute.

NOTE

The Low Battery alarm setting is designed to be useful at full load battery discharge rates. It is typically set for 10 volts above the 60-minute Battery Shutdown voltage, to provide some measure of warning under all circumstances. If the discharge period extends past 15 minutes (i.e., the load on the UPS is less than full capacity), the Battery Shutdown voltage setting is gradually and automatically increased to protect the batteries from deep discharge. The Low Battery alarm setting is not automatically increased and will give proportionately less warning for longer discharge periods. Instead, the operator should consult the Battery Time screen or Present Status screen to see the calculated time remaining based on actual usage during the discharge period.

41

Image 47
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions System Description Other Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls Options Automatic Restart Customer Alarm InterfaceTemperature-Compensated Charging Battery Load TestingUPS Module Battery PlantGeneral Component Descriptions Software Detailed Component DescriptionsControls Hardware Input Circuit Breaker Input Power FactorRectifier/Charger OperationBattery Equalize Charge Circuit Battery Charging CircuitBattery Disconnect Battery Charge Current LimitingOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterPulsed Parallel Operation Static Switch Backfeed ProtectionStatic Bypass Bypass Circuit BreakerTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Display Screen and Operator Controls Features100kVA 500kVA 1000kVA Description Function Operator controls, typical systemDescription Function Series 610 UPS operator control panelMenu tree Menu Tree NavigationMaster menu screen Master Menu ScreenOperation Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Monitor/Mimic display example Utility fail Walk-in display screen Walk-In Display ScreenStatus reports screen Status Reports ScreensEvent History Present StatusHistory status report screen History StatusSystem Status Battery Cycle MonitorBattery cycle monitoring summary screen System configuration screens System Configuration ScreensMaximum auto-retransfer attempts screen Maximum Auto-Retransfer AttemptsDate screen DateTime screen TimeAuto dial screen Auto DialSystem Options Language SelectionContinuous Duty Static Switch Optional Standard Remote Monitor Indications Channel Alarm messagesAdditional alarm messages Remote MonitorLow Battery Alarm Limit Settings ScreenOverload Alarm Battery DischargingTemperature Limit Setting Optional Battery Shutdown 60 MinutesBattery Rating 100% Battery RatingLoad transfer procedure screen Load Transfer Procedures ScreenRefer to 3.4.1 Start-Up Procedure for more details Start-Up Procedures ScreenBattery Time Screen Shutdown Procedures ScreenBattery time screen 15-minute discharge Elapsed Time Minutes Upper Limit Actual Lower LimitStatus Reports Screens Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenAlarm and status message screen Alarm and Status Messages Status MessagesAbbreviations used in alarm messages Alarm MessagesAC Input Alarm messages and corrective actionsUPS System Cooling UPS SystemAlarm Message Special Functions Alarm messages-summaryAuto-Dial Communication InterfacesWorldwide Reporting Requesting Information Local Reporting to a TerminalLocal Reporting to a Monitor Site Reporting SiteScan or SnmpKeys Function Series 610 terminal commandsRemote Monitor Panel Separate / Simultaneous OutputsAbbreviation Circuit Breaker Load on BypassCircuit breaker abbreviations Load on bypass UPS available OK to TransferLoad on UPS bypass available Momentary Overloads Momentary overload through pulse-parallel static switchInput power fail-load on battery Input Power Failure-Load on BatteryLoad on UPS-battery not available Off BatteryEmergency Module Off Refer to 3.4.4 Shutdown ProceduresEmergency power off Remote Emergency Power OffModule Shutdown Refer to 3.3.9 Maintenance BypassLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Start-Up Procedure Manual ProceduresStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load transfer procedures screen Load Transfer ProceduresMaintenance Bypass Load Transfers Shutdown Procedures Shutdown Procedures Module Shutdown ProcedureLocal Emergency Modules Off Lemo Remote Emergency Power Off RepoBattery exercise control screen above and results below Battery Exercise Procedures150% Automatic OperationsOverloads Without Transfer 1000%Automatic Retransfers to UPS Automatic Transfers to Bypass Overload ConditionAutomatic Transfers to Bypass UPS System Faults Sequence of Operation Automatic Restart OptionalEnabling Automatic Restart Maintenance Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Recommended Test Equipment Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Corrective ActionsKVA Power factor pf KVARating Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Page United States Technical Support/ServiceCompany Behind the Products Locations