5.2Environmental Conditions

Table 12 Specifications applicable to environment

Enclosure

The UPS is housed in a NEMA-1 enclosure. The enclosure is designed for indoor use only

and is not to be subjected to falling objects or precipitation.

 

 

 

 

 

 

 

Recommended Operating

25°C ambient

 

 

Temperature

 

 

 

 

 

Maximum Operating

40°C ambient (design temperature) without derating; (see Notes 1-3).

Temperature

 

 

 

Minimum Operating

0°C

 

 

Temperature

 

 

 

 

 

Storage Temperature

-20°C to 70°C

 

 

 

 

Typical Battery

Average annual temperature shall not exceed 27°C. Peak temperature shall not exceed

Temperature Requirements

43°C during any 24-hour period. See battery manufacturer’s recommendations.

Relative Humidity

0 to 95% without condensation

 

 

 

 

Operating Elevation

Sea level to 1219 meters (4000 ft.) without derating

 

 

 

 

Storage Elevation

Sea level to 15,000 meters (50,000 ft.)

 

 

 

 

Audible Noise, measured

62-69 dBA typical for 100-450kVA units

 

72 dBA typical for 500-750kVA units

 

5 feet from unit

 

75 dBA typical for 1000kVA units

 

 

 

 

 

 

 

 

98% at 45°C

 

 

 

 

 

 

Derating for Higher

96% at 50°C

 

 

 

 

 

93% at 55°C

 

 

Ambient Temperatures

 

 

(see Note 3)

Consult your Liebert sales representative regarding applications in high ambient

 

temperatures or call 1-800-LIEBERT. Special temperature sensors must be installed at the

 

factory.

 

 

 

 

% Derating @ 104°F (40°C)

% Derating @ 95°F (35°C)

 

Elevation-ft. (m)

Ambient (see Note 3)

Ambient (see Note 3)

 

5000 (1524)

98%

100%

 

 

 

 

 

5249 (1600)

98%

100%

 

 

 

 

Derating for Higher

5906 (1800)

97%

99%

 

 

 

6562 (2000)

96%

98%

Elevations

(see Note 4)

7218 (2200)

95%

97%

 

 

 

 

 

7874 (2400)

94%

96%

 

 

 

 

 

8530 (2600)

93%

95%

 

 

 

 

 

9186 (2800)

92%

94%

 

 

 

 

 

9843 (3000)

90%

92%

 

 

 

 

NOTES

 

 

 

1.This category of electronic equipment is agency rated for use in an atmosphere free of conductive particles. Some industrial facilities may require a room air filtration system to keep the UPS free of excess moisture and contaminants.

2.The UPS system is designed to operate continuously at 40°C. However, design equipment life expectancy will be extended with lower temperatures (25°C is recommended).

3.Ambient temperature is the maximum ambient temperature during any 24-hour period. For operation at higher temperatures, consult your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.

4.Exercise care during installation to ensure unimpeded airflow through the UPS system. For operation at higher elevations, consult your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.

94

Image 100
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Designed for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Customer Alarm Interface Temperature-Compensated ChargingBattery Load Testing Automatic RestartGeneral Component Descriptions Battery PlantUPS Module Controls Hardware Detailed Component DescriptionsSoftware Input Power Factor Rectifier/ChargerOperation Input Circuit BreakerBattery Charging Circuit Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Backfeed Protection Static BypassBypass Circuit Breaker Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Alarm messages Additional alarm messagesRemote Monitor Standard Remote Monitor Indications ChannelAlarm Limit Settings Screen Overload AlarmBattery Discharging Low BatteryBattery Shutdown 60 Minutes Battery Rating 100%Battery Rating Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsWorldwide Reporting Communication InterfacesAuto-Dial Local Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Requesting InformationSeries 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Keys FunctionCircuit breaker abbreviations Load on BypassAbbreviation Circuit Breaker OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results belowAutomatic Operations Overloads Without Transfer1000% 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Enabling Automatic Restart Automatic Restart OptionalSequence of Operation Maintenance Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingRecord Log Routine MaintenanceAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery voltage record Battery retorque valuesRack-Mounted Batteries Detection of Trouble Torque specifications unless otherwise labeledTorque Requirements Reporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Recommended Test EquipmentRating Power factor pf KVAKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Technical Support/Service Company Behind the ProductsLocations United States