Liebert 610 manual Present Status, Event History

Page 34

Operation

Present Status

The Present Status screen shows the current status of the UPS module. This screen displays any alarm messages that are present and the values of the metered parameters for each cabinet.

Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the upper right corner. The Present Status screen display is updated every two seconds.

Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge. The value is on the Battery Volts line in the TIME column (far right side of the screen). For the first two minutes of discharge, the Rated Time Remaining is displayed. After that, the Calculated Time Remaining is displayed and updated every six seconds.

All the information on this screen, including Battery Time Remaining, is available to a local terminal or modem through the communications ports provided in the Series 610 UPS. Refer to Table 6 in this manual for keyboard commands to use with the communication ports.

Figure 14 Present status report screens

PRESENT STATUS

MODULE-0

01/12/96

14:06:26 FRAME 35

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

 

 

 

A

B

C

DC

LOAD HERTZ TIME

OUTPUT VOLTS

480

480

480

 

 

OUTPUT AMPS

325

325

325

 

60.0

OUTPUT FREQUENCY

 

 

480

BATTERY VOLTS

 

 

 

0:09

BATTERY AMPS

 

 

 

-645

 

INPUT VOLTS

0

0

0

 

 

INPUT AMPS

0

0

0

 

 

LOAD KVA

 

 

 

 

270

END OF REPORT

SELECT : EXIT

Event History

The Event History screen lists the active alarms present in the UPS. This screen also displays the prior 128 alarm frames, in a first in, first out (FIFO) sequence, that have taken place along with the date and the time that each alarm frame occurred. Use the Up and Down pads to look through the different alarm frames.

Figure 15 Event history report screen

EVENT HISTORY

MODULE-0

01/17/96 11:23:41 FRAME 175

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

Low Batt Warning

UP : NEXT FRAME

DOWN : PREVIOUS FRAME

SELECT : EXIT

28

Image 34
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Designed for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls Options Battery Load Testing Customer Alarm InterfaceTemperature-Compensated Charging Automatic RestartGeneral Component Descriptions Battery PlantUPS Module Controls Hardware Detailed Component DescriptionsSoftware Operation Input Power FactorRectifier/Charger Input Circuit BreakerBattery Charge Current Limiting Battery Charging CircuitBattery Disconnect Battery Equalize Charge CircuitInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceBypass Circuit Breaker Static Switch Backfeed ProtectionStatic Bypass Pulsed Parallel OperationTransfer and Retransfer Conditions Three Breaker Maintenance Bypass Switchboard Features Display Screen and Operator ControlsOperator controls, typical system 100kVA 500kVA 1000kVA Description FunctionSeries 610 UPS operator control panel Description FunctionMenu Tree Navigation Menu treeMaster Menu Screen Master menu screenOperation Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 6 Status Messages Monitor/Mimic display example Utility fail Walk-In Display Screen Walk-in display screenStatus Reports Screens Status reports screenPresent Status Event HistoryHistory Status History status report screenBattery Cycle Monitor System StatusBattery cycle monitoring summary screen System Configuration Screens System configuration screensMaximum Auto-Retransfer Attempts Maximum auto-retransfer attempts screenDate Date screenTime Time screenAuto Dial Auto dial screenLanguage Selection System OptionsContinuous Duty Static Switch Optional Remote Monitor Alarm messagesAdditional alarm messages Standard Remote Monitor Indications ChannelBattery Discharging Alarm Limit Settings ScreenOverload Alarm Low BatteryBattery Rating Battery Shutdown 60 MinutesBattery Rating 100% Temperature Limit Setting OptionalLoad Transfer Procedures Screen Load transfer procedure screenStart-Up Procedures Screen Refer to 3.4.1 Start-Up Procedure for more detailsShutdown Procedures Screen Battery Time ScreenBattery time screen 15-minute discharge Upper Limit Actual Lower Limit Elapsed Time MinutesMeter Calibration Screen Status Reports ScreensBattery Equalize Screen Battery equalize screenAlarm and Status Messages Status Messages Alarm and status message screenAlarm Messages Abbreviations used in alarm messagesAlarm messages and corrective actions AC InputUPS System UPS System CoolingAlarm messages-summary Alarm Message Special FunctionsWorldwide Reporting Communication InterfacesAuto-Dial Site Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Requesting InformationSeparate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Keys FunctionCircuit breaker abbreviations Load on BypassAbbreviation Circuit Breaker OK to Transfer Load on bypass UPS availableLoad on UPS bypass available Momentary overload through pulse-parallel static switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOff Battery Load on UPS-battery not availableRefer to 3.4.4 Shutdown Procedures Emergency Module OffRemote Emergency Power Off Emergency power offRefer to 3.3.9 Maintenance Bypass Module ShutdownLoad on maintenance bypass two breakers Load on maintenance bypass three breakers Manual Procedures Start-Up ProcedureStart-Up Procedure Set the Static Switch Disconnect or to OFF open Start-up procedures Start-Up Procedure Load Transfer Procedures Load transfer procedures screenMaintenance Bypass Load Transfers Shutdown Procedures Module Shutdown Procedure Shutdown ProceduresRemote Emergency Power Off Repo Local Emergency Modules Off LemoBattery Exercise Procedures Battery exercise control screen above and results below1000% Automatic OperationsOverloads Without Transfer 150%Automatic Transfers to Bypass Overload Condition Automatic Retransfers to UPSAutomatic Transfers to Bypass UPS System Faults Enabling Automatic Restart Automatic Restart OptionalSequence of Operation Maintenance Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingRecord Log Routine MaintenanceAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery voltage record Battery retorque valuesRack-Mounted Batteries Detection of Trouble Torque specifications unless otherwise labeledTorque Requirements Corrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Recommended Test EquipmentRating Power factor pf KVAKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Page Locations Technical Support/ServiceCompany Behind the Products United States