Page 101

Operation

Local Emergency Modules Off (LEMO)

The UPS controls at the SCC include an Emergency Module Off pad (Figure 10, item 12). When this guarded pad is pressed, the load is automatically transferred to the bypass line and the module output, battery and input circuit breakers trip open to isolate and shut down all the UPS modules. Control Power for indicators and alarms remains On.

Remote Emergency Power Off (REPO)

The Remote Emergency Power Off control (REPO) is a switch located remotely from the UPS system. It will normally be in the same room as the critical load equipment.

The Remote Emergency Power Off switch removes all power to the critical load.

When you trip the Remote Emergency Power Off switch, all UPS circuit breakers are opened, includ- ing the System Bypass circuit breaker (SBB). All power through the UPS is removed from the load. You will still have power to the UPS controls, and you may have power to the static switch.

3.5Automatic Operations

The Liebert Series 610 UPS system is designed to function while unattended by an operator. The sys- tem control logic monitors the performance of the UPS, the availability of power sources and the cur- rent required by the critical load.

The system control logic at the SCC:

Determines what overload conditions can be sustained without a transfer to bypass.

Initiates an automatic transfer to bypass to sustain an overload.

Can initiate an automatic retransfer to the UPS after a system overload has been cleared.

Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS fault occurs.

The control logic at each UPS module:

Determines what overload conditions can be sustained by the module while it is on-line.

Automatically takes the UPS module off line and initiates an emergency module shutdown when selected UPS faults occur.

95

Image 101
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions Multi-Module UPS, 100-500kVA System DescriptionMulti-Module UPS, 500-750kVA Designed for Success ReliabilityTypes of System Control Cabinets SCCs Input Power Failure Safety PrecautionsModes of Operation Other Factors to ConsiderOperator Controls 1989-2003 Options BatteryModule Battery Disconnect Battery Racks or CabinetsThree Breaker Maintenance Bypass Two Breaker Maintenance BypassSystem Control Cabinet General Component DescriptionsUPS Module Battery PlantSoftware Detailed Component DescriptionsControls Hardware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceShorted SCR Monitoring Static BypassFuse Protection Load Transfers Static Switch IsolationPulsed Parallel Operation Transfer and Retransfer Conditions Retransfer Inhibited Redundant ModeDisplay Screen and Operator Controls FeaturesDescription Function 500kVA1000kVA Operation Description Location Function Refer to 3.4.5 Shutdown ProceduresNumbers are used as keys to data in , below Switches behind SCC control panel door Menu tree Menu Tree NavigationModule Master Menu Master Menu ScreenSCC Master Menu Operation Output Metering Displays SCC Monitor/Mimic Display ScreenInput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic display screen Module Monitor/Mimic Display ScreenItem 5 Alarm Messages Alarm MessagesModule Display SCC DisplayMonitor/Mimic display example Utility fail KVA / 217 kW 325A 325A 325A MOD On Line OFF Line SUM ALM B-C C-A 0V 0V Not OK to Transfer Static Switch Connected Walk-in display screen during start-up Walk-In Display ScreenPresent Status Status Reports ScreensModule Status Report Event HistorySCC Status Report History status report screens History StatusAlarm in SCC Alarm in Module Alarm conditions that freeze history data gatheringSystem Status Battery Cycle Monitor-Module OnlyBattery cycle monitoring summary screen SCC system configuration screen System Configuration ScreensDate screen DateTime screen TimeAuto Dial Auto dial setting screenMaximum Auto-Retransfer Attempts Modem Baud RateLanguage Selection System Current RatingSystem Options Retransfer AttemptsContinuous Duty Static Switch Optional Battery test screen-MMU onlySCC and module remote monitor indications Remote MonitorModule alarm limit settings screen Alarm Limit Settings ScreenTemperature Limit Setting Optional Battery Float VoltageRefer to 3.4.3 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.4.1 SCC Start-Up Procedure for more details Start-Up Procedures ScreenModule start- up procedures screens Shutdown Procedures ScreenSCC shutdown procedures screen Battery time screen 15 minute discharge Battery Time Screen Module OnlyElapsed Time Minutes Upper Limit Actual Lower LimitOperation Meter calibration screen Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenSystem Status Messages Alarm and Status Messages Module Status MessagesAbbreviation Definition Abbreviations used in alarm messagesLoad Block Messages Alarm messages meaning and corrective action Static Switch Manual ResetBypass Phase Control PowerInverter Fault Reverse PowerTransfer Module N OffOvertemperature Battery OvertempTimeout New AlarmSpecial Functions Alarm messages summaryAlarm Message Worldwide Reporting Communication InterfacesAuto-Dial Requesting InformationSite Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Separate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Circuit breaker abbreviations Abbreviation Circuit Breaker OK to Transfer Load on BypassLoad on bypass, UPS available Momentary Overloads Momentary overload, pulsed static bypass switchInput power fail-load on battery Input Power Failure-Load on BatteryOne module off-line, load on UPS One Module Off-LineLoad on UPS-battery not available Off BatteryEmergency Modules Off Refer to 3.4.5 Shutdown ProceduresEmergency power off Remote Emergency Power OffSystem Shutdown Refer to 3.3.10 Maintenance BypassLoad on maintenance bypass, two breakers Refer to 3.5 Automatic Operations for more details Manual ProceduresSCC Start-Up Procedure Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Manual Transfer Instructions UPS Lead Load Transfer ProceduresIf the load is on the UPS System Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoAutomatic Operations Automatic Transfers to Bypass Overloads Without Transfer1000% 150%Automatic Emergency Modules Off Automatic Retransfers to UPSAutomatic Module Off-Line Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentKVA Power factor pf KVARating Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Specifications 112 Page Company Behind the Products Technical Support/ServiceLocations United States