Liebert 1000kVA manual Numbers are used as keys to data in , below, Description Location Function

Page 29

Operation

Figure 10 Series 610 UPS and SCC operator control panels

Numbers are used as keys to data in Table 3, below.

Table 3

Series 610 UPS and SCC operator control panels

 

 

 

Item

Description (Location)

Function

1

Display Screen

This screen displays all vital UPS information in one convenient location. All of the

(SCC and modules)

UPS monitoring functions and conditions are indicated here.

 

 

Up

 

This touch-sensitive pad (button) is used to move the cursor up through various

2

 

selections present on the display screen. Note that all pads on this control panel

(SCC and modules)

 

have touch-sensitive switches behind them.

 

 

 

 

 

 

 

3

Down

 

Similar to the Up pad, this pad is used to move the cursor down through the

(SCC and modules)

various selections present on the display screen.

 

 

Select

After choosing the desired item (with highlighted cursor) from the display screen

4

with the Up and Down pads, pushing this pad tells the microprocessor to go to the

(SCC and modules)

 

highlighted selection.

 

 

 

 

Alarm Reset

This pad is used to clear all of the alarm conditions that are no longer present.

5

However, all active alarms remain in memory and on the applicable screens until

(SCC and modules)

 

they are corrected.

 

 

 

 

 

 

 

 

Voltage Adjust

This push-to-turn knob permits adjustment of the UPS output voltage to meet load

6

requirements or to match the bypass voltage before transferring the load to or from

(SCC only)

 

bypass.

 

 

 

 

UPS

 

This pad activates the circuits that connect the UPS to the critical load (a

7

 

retransfer). When this pad is pushed (along with Control Enable), the UPS output

(SCC only)

 

circuit breaker closes and the bypass circuit breaker opens.

 

 

 

 

Bypass

This pad activates the circuits that connect the bypass line to the critical load (a

8

transfer). When this button is pushed (along with Control Enable), the bypass

(SCC only)

 

circuit breaker closes and the UPS output circuit breaker opens.

 

 

 

 

 

 

9

Control Enable

This pad must be pressed simultaneously with the UPS, Bypass, Battery Trip or

(SCC and modules)

Output Trip pads to activate them.

 

 

 

 

This pad is used to silence the alarm horn after it is activated. When this switch is

10

Horn Off

pressed, the alarm horn is silenced but the active and latched alarm messages

(SCC only)

remain on the screen. The alarm messages still displayed stop flashing to indicate

 

 

 

 

they have been acknowledged.

11

Alarm Horn and

This electronic horn sounds to alert nearby personnel whenever a new alarm

Red LED (SCC only)

occurs. A red LED (light emitting diode) is located in the middle of the alarm horn.

 

 

Emergency Module

During an emergency, pressing this guarded switch will transfer the load to bypass

12

and then shut down the UPS modules. The load will remain on bypass power.

Off (SCC only)

 

(Refer to 3.4.5 - Shutdown Procedures.)

 

 

 

 

Battery Trip

This pad can be used (along with Control Enable) to trip the module battery

13

disconnect (MBD) circuit breaker open (disconnecting the battery from the UPS

(modules only)

 

module).

 

 

 

 

 

 

14

Output Trip

This pad can be used (along with Control Enable) to trip the module output circuit

(modules only)

breaker open (disconnecting the module from the UPS system).

 

23

Image 29
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions Multi-Module UPS, 100-500kVA System DescriptionMulti-Module UPS, 500-750kVA Designed for Success ReliabilityTypes of System Control Cabinets SCCs Input Power Failure Safety PrecautionsModes of Operation Other Factors to ConsiderOperator Controls 1989-2003 Options BatteryModule Battery Disconnect Battery Racks or CabinetsThree Breaker Maintenance Bypass Two Breaker Maintenance BypassSystem Control Cabinet General Component DescriptionsUPS Module Battery PlantSoftware Detailed Component DescriptionsControls Hardware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceShorted SCR Monitoring Static BypassFuse Protection Load Transfers Static Switch IsolationPulsed Parallel Operation Transfer and Retransfer Conditions Retransfer Inhibited Redundant ModeDisplay Screen and Operator Controls FeaturesDescription Function 500kVA1000kVA Operation Description Location Function Refer to 3.4.5 Shutdown ProceduresNumbers are used as keys to data in , below Switches behind SCC control panel door Menu tree Menu Tree NavigationModule Master Menu Master Menu ScreenSCC Master Menu Operation Output Metering Displays SCC Monitor/Mimic Display ScreenInput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic display screen Module Monitor/Mimic Display ScreenItem 5 Alarm Messages Alarm MessagesModule Display SCC DisplayMonitor/Mimic display example Utility fail KVA / 217 kW 325A 325A 325A MOD On Line OFF Line SUM ALM B-C C-A 0V 0V Not OK to Transfer Static Switch Connected Walk-in display screen during start-up Walk-In Display ScreenPresent Status Status Reports ScreensModule Status Report Event HistorySCC Status Report History status report screens History StatusAlarm in SCC Alarm in Module Alarm conditions that freeze history data gatheringSystem Status Battery Cycle Monitor-Module OnlyBattery cycle monitoring summary screen SCC system configuration screen System Configuration ScreensDate screen DateTime screen TimeAuto Dial Auto dial setting screenMaximum Auto-Retransfer Attempts Modem Baud RateLanguage Selection System Current RatingSystem Options Retransfer AttemptsContinuous Duty Static Switch Optional Battery test screen-MMU onlySCC and module remote monitor indications Remote MonitorModule alarm limit settings screen Alarm Limit Settings ScreenTemperature Limit Setting Optional Battery Float VoltageRefer to 3.4.3 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.4.1 SCC Start-Up Procedure for more details Start-Up Procedures ScreenModule start- up procedures screens Shutdown Procedures ScreenSCC shutdown procedures screen Battery time screen 15 minute discharge Battery Time Screen Module OnlyElapsed Time Minutes Upper Limit Actual Lower LimitOperation Meter calibration screen Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenSystem Status Messages Alarm and Status Messages Module Status MessagesAbbreviation Definition Abbreviations used in alarm messagesLoad Block Messages Alarm messages meaning and corrective action Static Switch Manual ResetBypass Phase Control PowerInverter Fault Reverse PowerTransfer Module N OffOvertemperature Battery OvertempTimeout New AlarmSpecial Functions Alarm messages summaryAlarm Message Worldwide Reporting Communication InterfacesAuto-Dial Requesting InformationSite Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Separate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Circuit breaker abbreviations Abbreviation Circuit Breaker OK to Transfer Load on BypassLoad on bypass, UPS available Momentary Overloads Momentary overload, pulsed static bypass switchInput power fail-load on battery Input Power Failure-Load on BatteryOne module off-line, load on UPS One Module Off-LineLoad on UPS-battery not available Off BatteryEmergency Modules Off Refer to 3.4.5 Shutdown ProceduresEmergency power off Remote Emergency Power OffSystem Shutdown Refer to 3.3.10 Maintenance BypassLoad on maintenance bypass, two breakers Refer to 3.5 Automatic Operations for more details Manual ProceduresSCC Start-Up Procedure Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Manual Transfer Instructions UPS Lead Load Transfer ProceduresIf the load is on the UPS System Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoAutomatic Operations Automatic Transfers to Bypass Overloads Without Transfer1000% 150%Automatic Emergency Modules Off Automatic Retransfers to UPSAutomatic Module Off-Line Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentKVA Power factor pf KVARating Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Specifications 112 Page Company Behind the Products Technical Support/ServiceLocations United States