Operation
Table 9 | Alarm messages - meaning and corrective action (continued) | |||||
Alarm |
|
| Cabinet | Special |
| |
Message |
| Location | Functions | Meaning and Corrective Action | ||
BYPASS (Cont’d.) |
|
|
| |||
Auto Transfer to |
|
|
| The critical load has been automatically transferred to the bypass line. | ||
| SCC | D, E, F | Use the History Status screen to determine the cause for the transfer. | |||
Bypass |
|
| Clear all of the alarms before attempting to retransfer the load from | |||
|
|
|
| |||
|
|
|
|
| bypass to UPS. | |
Auto Retransfer |
|
|
| An automatic retransfer will be initiated when the OK to Transfer condition | ||
| SCC | — | has been present for 10 seconds, if the overload has dropped below | |||
Primed |
|
| ||||
|
|
|
| 100% of the rated SCC current and if enough UPS modules are | ||
|
|
|
|
| ||
|
|
|
|
| A manual retransfer is required. Either a system overload condition has | |
Manual Reset/ |
|
|
| lasted more than 5 minutes or no more | ||
| SCC | — | available. Note that this alarm is only used if | |||
Retransfer |
|
| ||||
|
|
|
| enabled. | ||
|
|
|
|
| ||
|
|
|
|
| Perform a manual retransfer if all necessary conditions are present. | |
|
|
|
|
| The UPS output is not synchronized to the bypass power source. The | |
|
|
|
|
| static bypass switch is disconnected or it has failed internally. | |
Static Switch |
| SCC | D, S | Emergency and overload transfer to the bypass source is not available. | ||
| Manually set the Static Switch Disconnects to ON (closed) if the static | |||||
Unable |
|
| ||||
|
|
|
| switch is disconnected. If the alarm conditions are automatically | ||
|
|
|
|
| ||
|
|
|
|
| corrected, reset the alarm to clear it. Contact Liebert Global Services if the | |
|
|
|
|
| alarm stays on. | |
Bypass Not |
|
| SCC | — | The bypass power source voltage is not within specifications. | |
Available |
|
| Correct the bypass AC power source. | |||
|
|
|
| |||
|
|
|
|
| The power conductors on the bypass line are not wired to the UPS in the | |
|
|
|
|
| required sequence. This alarm should appear only during initial | |
Bypass Phase |
| SCC | D, L, S | after a repair to the source power system. | ||
Sequence Wrong | Disconnect power from the bypass line and correct the wiring. A Liebert | |||||
|
| |||||
|
|
|
|
| Global Services representative must be present during initial | |
|
|
|
|
| your UPS System.] | |
UPS SYSTEM |
|
|
|
| ||
Input Current |
|
|
| At least one input phase differs from the average current by 10% or more | ||
| MMU | D, E | for four (4) hours. Contact Liebert Global Services. If the condition | |||
Unbalance |
|
| ||||
|
|
|
| persists, transfer the load to the bypass line. | ||
|
|
|
|
| ||
|
|
| SCC | D, L, S | The logic control power supply from the UPS output is not operating | |
Control Power |
|
|
| properly. The UPS module continues operating but will shut down if the | ||
|
|
| ||||
Fail |
|
| MMU | D, L, S | input power fails. The SCC continues operating but will shut down if the | |
|
|
|
|
| bypass power fails. Contact Liebert Global Services immediately. | |
Output Over/ |
|
|
| Output frequency differs from the nominal (60 Hz) by more than 0.5 Hz. | ||
| SCC | D, L, S | No transfer or shutdown occurs. | |||
Under Frequency | ||||||
|
| Contact Liebert Global Services at once. | ||||
|
|
|
|
| ||
|
|
|
|
| The UPS system output voltage is under the minimum | |
Output |
|
| SCC | D, F, L, S | from nominal. The load automatically transfers to the bypass line. | |
|
| If the alarm condition is no longer present, reset the alarm and retransfer | ||||
Undervoltage |
| |||||
|
|
| the load from bypass to UPS. Contact Liebert Global Services if alarm | |||
|
|
|
|
| ||
|
|
|
|
| persists. | |
|
|
|
|
| The UPS system output voltage is above the maximum (+10%) deviation | |
Output |
|
|
|
| from nominal. The load automatically transfers to the bypass line. All UPS | |
|
| SCC | D, F, L, S | modules are taken | ||
Overvoltage |
|
| ||||
|
|
|
| Contact Liebert Global Services at once. Do not attempt to reset circuit | ||
|
|
|
|
| ||
|
|
|
|
| breakers. | |
|
|
| SCC | D, R, S | The UPS output current exceeds the rated system load current. This | |
Overload |
|
|
|
| condition causes an alarm only, the UPS does not shut down. | |
|
|
|
| |||
|
| MMU | D, S | Determine cause of the overload. Reduce the load until the overload | ||
|
|
| ||||
|
|
|
|
| condition is corrected. Reset the UPS alarm. | |
Table 9 Abbreviations |
|
|
| |||
D = |
| L = latches |
|
| ||
E = logs only; |
| R = remote |
|
| ||
F = freezes; |
| S = summary |
|
|
D* =
D# =
66