Operation
Table 5 shows the alarm conditions that stop the History Status buffer from gathering data.
Table 5 Alarm conditions that freeze history data gathering
Alarm in SCC | Alarm in Module | |
|
|
|
Auto Transfer to Bypass | DC Cap Fuse Blown | |
|
|
|
Output Overvoltage | DC Overvoltage Shutdown | |
|
|
|
Output undervoltage | Inverter Fault | |
|
|
|
Overload Transfer | Low Battery Shutdown | |
|
|
|
|
| Overload Shutdown |
|
|
|
|
| Overtemperature Timeout |
|
|
|
|
| Rectifier Fuse Blown |
|
|
|
|
| Reverse Power |
|
|
|
NOTE
The Emergency Off alarm will also freeze the SCC History Status buffer with the Auto Transfer to Bypass alarm (if the load is on the UPS system when the alarm condition occurs).
The History Status buffer does not resume collecting new frames until the fault is cleared and the Alarm Reset pad is pressed for more than 5 seconds (or until the screen clears).
41