Liebert 1000kVA Battery Overtemp, Hardware, Emergency Off, Ambient, Overtemperature, Equipment

Page 74

 

 

 

 

Operation

Table 9

Alarm messages - meaning and corrective action (continued)

Alarm

 

Cabinet

Special

 

Message

Location

Functions

Meaning and Corrective Action

 

 

 

 

Battery Temp option must be installed and enabled. Battery Temp

Battery Overtemp

MMU

D, S

exceeds the programmed limit set in Alarm Settings screen for more than

 

 

 

 

one minutes.

 

 

 

 

At least one of the following alarm conditions is present: Inverter Fault,

 

 

 

 

Rectifier Fuse Blown, Reverse Power, Overload Shutdown, logic power

Hardware

 

MMU

D#

supply failure or inverter output symmetry failure. The UPS module is

Shutdown

 

taken off-line and is shut down.

 

 

 

 

 

 

 

Contact Liebert Global Services at once. Do not attempt to reset the

 

 

 

 

circuit breakers.

 

 

SCC

 

The Emergency Module Off (or Emergency Power Off) switch has been

 

 

 

 

pressed, which caused the UPS system to shut down and transfer the

 

 

 

 

Emergency Off

 

D*, L, S

load to the bypass line (or all power to the critical load has been

MMU

shutdown).

 

 

 

 

 

 

 

Determine the cause of the emergency condition and correct it if possible.

 

 

 

 

Contact Liebert Global Services if you require assistance.

COOLING

 

 

 

 

 

 

 

 

The intake air to the UPS module exceeds the specified maximum

Ambient

 

MMU

D, R, S

temperature.

Overtemperature

This condition only causes an alarm, but should be corrected immediately

 

 

 

 

 

 

to prevent damage to equipment due to overheating.

 

 

 

 

A fault in one or more of the blower motors has occurred. This condition

 

 

 

 

only causes an alarm, but if not promptly corrected it could cause an

Blower Failed

MMU

D, S

equipment overtemperature condition that would shut down the UPS

module.

 

 

 

 

 

 

 

 

Check the blowers for proper operation. Contact Liebert Global Services if

 

 

 

 

you require assistance.

 

 

 

 

Sensors on power semiconductor heatsinks detect temperatures above

 

 

 

 

the steady state limits for these components. The control logic sets off the

Equipment

 

MMU

D, S

alarm but does not shut down the UPS module if the condition lasts less

Overtemperature

than 10 minutes.

 

 

 

 

 

 

Check the air intake, air exhaust and filters. Reduce the load or transfer it

 

 

 

 

to bypass. Contact Liebert Global Services if the alarm persists.

 

 

 

 

An Equipment Overtemperature condition has persisted for more than 10

Overtemperature

MMU

D, F

minutes. The UPS module is taken off-line and is shut down.

Timeout

 

Check the air intake, air exhaust and filters before attempting to start-up

 

 

 

 

 

 

 

the UPS.

REMOTE MONITOR PANELS

(Refer also to SCC and module remote monitor indications and Other alarms that activate summary alarms in 3.2.6 - System Configuration Screens)

Load On UPS

 

SCC

R

The UPS is operating properly. No corrective action is necessary.

New Alarm

 

SCC

R

Another new alarm message has been registered on the UPS system.

 

 

 

Clear the new alarm condition, if possible.

 

MMU

R

 

 

 

 

 

 

One or more of the UPS system alarm messages has been activated or a

System Summary

SCC

R

control logic failure has been detected by a watchdog timer.

Alarm

 

Use the Present Status screen to determine which alarms are active.

 

 

 

 

 

 

 

Clear the new alarm condition if possible to do so.

Module Summary

MMU

R

One or more of the UPS module alarm messages has been activated.

Use the Present Status screen to determine which alarms are active.

Alarm

 

 

 

 

Clear the new alarm condition, if possible to do so.

 

 

 

 

Table 9 Abbreviations

 

 

 

D = auto-dial;

L = latches

 

 

E = logs only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

68

Image 74
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Multi-Module UPS, 100-500kVAMulti-Module UPS, 500-750kVA Designed for Success ReliabilityTypes of System Control Cabinets SCCs Modes of Operation Safety PrecautionsInput Power Failure Other Factors to ConsiderOperator Controls 1989-2003 Battery OptionsThree Breaker Maintenance Bypass Battery Racks or CabinetsModule Battery Disconnect Two Breaker Maintenance BypassGeneral Component Descriptions System Control CabinetBattery Plant UPS ModuleSoftware Detailed Component DescriptionsControls Hardware Operation Input Power FactorRectifier/Charger Input Circuit BreakerBattery Charge Current Limiting Battery Charging CircuitBattery Disconnect Battery Equalize Charge CircuitInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceShorted SCR Monitoring Static BypassFuse Protection Load Transfers Static Switch IsolationPulsed Parallel Operation Transfer and Retransfer Conditions Redundant Mode Retransfer InhibitedFeatures Display Screen and Operator ControlsDescription Function 500kVA1000kVA Operation Description Location Function Refer to 3.4.5 Shutdown ProceduresNumbers are used as keys to data in , below Switches behind SCC control panel door Menu Tree Navigation Menu treeModule Master Menu Master Menu ScreenSCC Master Menu Operation Output Metering Displays SCC Monitor/Mimic Display ScreenInput Metering Displays Item 5 Module Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Module Monitor/Mimic display screenAlarm Messages Item 5 Alarm MessagesSCC Display Module DisplayMonitor/Mimic display example Utility fail KVA / 217 kW 325A 325A 325A MOD On Line OFF Line SUM ALM B-C C-A 0V 0V Not OK to Transfer Static Switch Connected Walk-In Display Screen Walk-in display screen during start-upStatus Reports Screens Present StatusModule Status Report Event HistorySCC Status Report History Status History status report screensAlarm conditions that freeze history data gathering Alarm in SCC Alarm in ModuleBattery Cycle Monitor-Module Only System StatusBattery cycle monitoring summary screen System Configuration Screens SCC system configuration screenDate Date screenTime Time screenAuto dial setting screen Auto DialModem Baud Rate Maximum Auto-Retransfer AttemptsSystem Options System Current RatingLanguage Selection Retransfer AttemptsBattery test screen-MMU only Continuous Duty Static Switch OptionalRemote Monitor SCC and module remote monitor indicationsAlarm Limit Settings Screen Module alarm limit settings screenBattery Float Voltage Temperature Limit Setting OptionalLoad Transfer Procedures Screen Refer to 3.4.3 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.4.1 SCC Start-Up Procedure for more detailsShutdown Procedures Screen Module start- up procedures screensSCC shutdown procedures screen Battery Time Screen Module Only Battery time screen 15 minute dischargeUpper Limit Actual Lower Limit Elapsed Time MinutesOperation Meter Calibration Screen Meter calibration screenBattery Equalize Screen Battery equalize screenAlarm and Status Messages Module Status Messages System Status MessagesAbbreviation Definition Abbreviations used in alarm messagesLoad Block Messages Alarm messages meaning and corrective action Bypass Phase Manual ResetStatic Switch Control PowerTransfer Reverse PowerInverter Fault Module N OffTimeout Battery OvertempOvertemperature New AlarmSpecial Functions Alarm messages summaryAlarm Message Auto-Dial Communication InterfacesWorldwide Reporting Requesting InformationSite Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Separate / Simultaneous Outputs Series 610 terminal commandsRemote Monitor Panel Circuit breaker abbreviations Abbreviation Circuit Breaker Load on Bypass OK to TransferLoad on bypass, UPS available Momentary overload, pulsed static bypass switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOne Module Off-Line One module off-line, load on UPSOff Battery Load on UPS-battery not availableRefer to 3.4.5 Shutdown Procedures Emergency Modules OffRemote Emergency Power Off Emergency power offRefer to 3.3.10 Maintenance Bypass System ShutdownLoad on maintenance bypass, two breakers Refer to 3.5 Automatic Operations for more details Manual ProceduresSCC Start-Up Procedure Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Load Transfer Procedures Manual Transfer Instructions UPS LeadIf the load is on the UPS System Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoAutomatic Operations 1000% Overloads Without TransferAutomatic Transfers to Bypass 150%Automatic Emergency Modules Off Automatic Retransfers to UPSAutomatic Module Off-Line Maintenance Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Corrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Recommended Test EquipmentKVA Power factor pf KVARating Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Specifications 112 Page Locations Technical Support/ServiceCompany Behind the Products United States