Introduction
2.Battery Racks or Cabinets
The battery racks are specifically designed for stationary service batteries. They are painted with
3.Module Battery Disconnect
The UPS system utilizes a separate Module Battery Disconnect for remotely located batteries. A sensing circuit in the UPS module, set at the battery low voltage limit, trips the Module Battery Disconnect to safeguard the battery from excessive discharge. The Module Battery Disconnect has an undervoltage release mechanism designed to ensure that during any shutdown or failure mode all battery potential is removed from the UPS system.
4.Input Current Distortion Filter
This filter reduces rectifier input current reflected harmonic distortion to less than 7% reflected THD and less than 4% reflected THD for modules with the optional
5.12-Pulse Rectifier
All
6.Isolation Transformers
An optional rectifier input isolation transformer is available in a matching transformer cabinet; this feature is standard in 1000kVA models. A bypass isolation transformer is also available.
7.Three Breaker Maintenance Bypass
This switchboard provides
8.Two Breaker Maintenance Bypass
This switchboard provides
9.Load Bus Synchronization (LBS)
The Load Bus Sync (LBS) option keeps two independent UPS systems (and therefore their critical load buses) in sync, even when the modules are operating on batteries or asynchronous AC sources. This means that critical loads connected to both load buses through a Static Bus Transfer Switch can be switched seamlessly between the two.
10.SiteScan Central Monitoring System
Liebert manufactures a central monitoring system that automatically displays key UPS measure- ments and alarms, as well as data from a variety of sensors. This monitoring system activates alarms so corrective action can be taken. Events and data can be printed in hard copy. Data can be logged for analysis.
11.Remote Monitor Panel
The UPS system may also be provided with an optional Remote Monitor Panel. This Panel pro- vides eight LED indicators and may be placed at a convenient location near the critical load. A functional description of the Remote Monitor Panel is provided in 3.0 - Operation of this manual.
12.Customer Alarm Interface
This optional interface board allows the input and display of 8 alarms from
13.Temperature-Compensated Charging
When battery temperature climbs above a preset limit (typically 77 degrees F), this optional cir- cuit proportionally reduces float charging voltage to prevent overcharging the battery.
14.Battery Load Testing
When activated, this option forces the battery string to assume the load for a short period of time. The UPS then compares the test results to data collected during the UPS commissioning to see if the battery system appears to meet specifications.
9