Liebert 1000kVA manual Overloads Without Transfer, Automatic Transfers to Bypass, 1000%, 150%

Page 102

Operation

3.5.1Overloads (Without Transfer)

The UPS system is capable of sustaining full output voltage (±2% of the nominal voltage) for overload conditions that remain within (under) the current versus time curve of system overload capacity and the capacity of modules on-line (Figure 69). Note that the time scale is not linear. Load On UPS is illustrated in Figure 54.

For high current demands of short duration (momentary overloads) the critical load is supplied simul- taneously by both the UPS system and the bypass line. Whenever the critical load requires more than 155% of the capacity of the modules on-line, the bypass line will supply up to 1000% rated system cur- rent through the solid state static switch for 40 milliseconds. Refer to 3.3.3 - Momentary Over- loads.

Whenever an overload condition occurs, you should determine the cause of the overload.

If an overload condition exceeds the UPS system overload capacity or the capacity of the modules on- line, the UPS system initiates an automatic load transfer to the bypass line.

Figure 69 Current-versus-time curves of module overload capacity

% Load

INVERTER OVERLOAD

 

% Load

 

 

1000%

 

 

 

 

 

 

150%

150%

 

 

125%

100%

 

 

104%

 

 

 

 

 

 

100%

 

40ms

30s

10m

PULSED-PARALLEL (FAULT-CLEARING)

40ms

3.5.2Automatic Transfers to Bypass

The UPS system will initiate an automatic load transfer to the bypass line if an overload condition exceeds the current-versus-time curve of system overload capacity or capacity of the modules on-line or if specified UPS system faults occur. Note that when the UPS system is operating in the non- redundant mode, an automatic transfer to bypass will be initiated when any UPS module is taken off line, either automatically or manually. Load On Bypass is illustrated in Figure 53.

The Overload Transfer and Output Undervoltage alarm messages will initiate an automatic transfer to bypass and the Load On Bypass message will be displayed. The status report screens will include the Automatic Transfer to Bypass message. Other UPS system faults will initiate an automatic trans- fer to bypass followed immediately by the shutdown and isolation of the UPS modules. Refer to 3.5.5 - Automatic Emergency Modules Off.

In an automatic transfer to bypass the UPS Output and System Bypass circuit breakers do not over- lap as they do in a manual transfer. The static bypass switch is fired (closed), the UPS Output circuit breaker is opened and the System Bypass circuit breaker is closed.

Bypass power is supplied to the critical load through the static bypass switch during the short time while both circuit breakers are open.

NOTE

A load transfer to the bypass line will be completed whenever an automatic transfer to bypass is initiated. If the OK to Transfer condition is present, the load transfer will be uninterrupted. If the Static Switch Unable alarm message is present for any reason, the automatic transfer will be interrupted for 40 to 120 milliseconds. Because of the reliability of the UPS components, an interrupted load transfer is a very unlikely occurrence.

96

Image 102
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Multi-Module UPS, 100-500kVAMulti-Module UPS, 500-750kVA Reliability Types of System Control Cabinets SCCsDesigned for Success Modes of Operation Safety PrecautionsInput Power Failure Other Factors to ConsiderOperator Controls 1989-2003 Battery OptionsThree Breaker Maintenance Bypass Battery Racks or CabinetsModule Battery Disconnect Two Breaker Maintenance BypassGeneral Component Descriptions System Control CabinetBattery Plant UPS ModuleDetailed Component Descriptions Controls HardwareSoftware Operation Input Power FactorRectifier/Charger Input Circuit BreakerBattery Charge Current Limiting Battery Charging CircuitBattery Disconnect Battery Equalize Charge CircuitInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceStatic Bypass Fuse ProtectionShorted SCR Monitoring Static Switch Isolation Pulsed Parallel OperationLoad Transfers Transfer and Retransfer Conditions Redundant Mode Retransfer InhibitedFeatures Display Screen and Operator Controls500kVA 1000kVADescription Function Operation Refer to 3.4.5 Shutdown Procedures Numbers are used as keys to data in , belowDescription Location Function Switches behind SCC control panel door Menu Tree Navigation Menu treeMaster Menu Screen SCC Master MenuModule Master Menu Operation SCC Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Item 5 Module Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Module Monitor/Mimic display screenAlarm Messages Item 5 Alarm MessagesSCC Display Module DisplayMonitor/Mimic display example Utility fail KVA / 217 kW 325A 325A 325A MOD On Line OFF Line SUM ALM B-C C-A 0V 0V Not OK to Transfer Static Switch Connected Walk-In Display Screen Walk-in display screen during start-upStatus Reports Screens Present StatusEvent History SCC Status ReportModule Status Report History Status History status report screensAlarm conditions that freeze history data gathering Alarm in SCC Alarm in ModuleBattery Cycle Monitor-Module Only System StatusBattery cycle monitoring summary screen System Configuration Screens SCC system configuration screenDate Date screenTime Time screenAuto dial setting screen Auto DialModem Baud Rate Maximum Auto-Retransfer AttemptsSystem Options System Current RatingLanguage Selection Retransfer AttemptsBattery test screen-MMU only Continuous Duty Static Switch OptionalRemote Monitor SCC and module remote monitor indicationsAlarm Limit Settings Screen Module alarm limit settings screenBattery Float Voltage Temperature Limit Setting OptionalLoad Transfer Procedures Screen Refer to 3.4.3 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.4.1 SCC Start-Up Procedure for more detailsShutdown Procedures Screen Module start- up procedures screensSCC shutdown procedures screen Battery Time Screen Module Only Battery time screen 15 minute dischargeUpper Limit Actual Lower Limit Elapsed Time MinutesOperation Meter Calibration Screen Meter calibration screenBattery Equalize Screen Battery equalize screenAlarm and Status Messages Module Status Messages System Status MessagesAbbreviations used in alarm messages Load Block MessagesAbbreviation Definition Alarm messages meaning and corrective action Bypass Phase Manual ResetStatic Switch Control PowerTransfer Reverse PowerInverter Fault Module N OffTimeout Battery OvertempOvertemperature New AlarmAlarm messages summary Alarm MessageSpecial Functions Auto-Dial Communication InterfacesWorldwide Reporting Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Series 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Circuit breaker abbreviations Abbreviation Circuit Breaker Load on Bypass OK to TransferLoad on bypass, UPS available Momentary overload, pulsed static bypass switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOne Module Off-Line One module off-line, load on UPSOff Battery Load on UPS-battery not availableRefer to 3.4.5 Shutdown Procedures Emergency Modules OffRemote Emergency Power Off Emergency power offRefer to 3.3.10 Maintenance Bypass System ShutdownLoad on maintenance bypass, two breakers Manual Procedures SCC Start-Up ProcedureRefer to 3.5 Automatic Operations for more details Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Load Transfer Procedures Manual Transfer Instructions UPS LeadMaintenance Bypass Load Transfers If the load is on Maintenance BypassIf the load is on the UPS System Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Remote Emergency Power Off Repo Automatic OperationsLocal Emergency Modules Off Lemo 1000% Overloads Without TransferAutomatic Transfers to Bypass 150%Automatic Retransfers to UPS Automatic Module Off-LineAutomatic Emergency Modules Off Maintenance Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Corrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Recommended Test EquipmentPower factor pf KVA RatingKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Specifications 112 Page Locations Technical Support/ServiceCompany Behind the Products United States