Specifications
5.3Adjustments
All adjustments are set at the factory or during
•Input Current Limit: Normal, 115%; on generator (with optional circuit), 100%
•Battery Charge Current Limit: Normal, 10%; on generator, 1%
•Battery Equalize Charge: Set at
•DC Overvoltage: 600 volts
•Overload Alarm: 104% normal load.
•Output Frequency Tolerance: ±0.5 Hz
•Output Voltage: Nominal - operator adjustable ±5%
•Line Drop Compensation: 0 to +5% - set at
5.4Battery Operation
The separate battery manufacturer’s manual, available on the manufacturer’s Web site, provides the necessary information for the installation, operation and maintenance of the battery. Use the battery manual in conjunction with this manual.
The float charge voltage for a battery is equal to the number of cells in series making up the battery multiplied by the charge voltage for each cell.
Since the charging voltage level is critical to proper battery operation, refer to your battery manual, available on the manufacturer’s Web site, for information regarding your system.