Operation
Remote Monitor Panel
The Liebert Remote Monitor Panel provides an LED indication of the following conditions:
•Load On UPS
•Load On Bypass
•Battery Discharge
•Low Battery Warning
•Overload
•Ambient Overtemp
•System Summary Alarm
•New Alarm
This information is also available for customer use through a set of contacts on a separate terminal board.
Alarm messages that activate the System Summary Alarm are listed in Table 6 and Table 7.
The Remote Monitor Panel housing is a NEMA Type 1 enclosure, available for either
Separate / Simultaneous Outputs
The
Table 11 | Series 610 terminal commands | ||
|
| ||
Key(s) | Function | ||
A, return |
| Displays Present Status Report screen. NOTE: For all three report screens, a numeral 1 | |
| through 6 in place of N will access an individual UPS module. If no numeral is entered, | ||
AN (N=1 to 6), return | |||
you will get a report from the SCC. | |||
|
| ||
^B | Displays Event History Report screen, starting with the most recent frame and then | ||
^BN (N=1 to 6) return | scrolling back through earlier frames. | ||
C, return |
| Displays History Status Report screen starting with the most recent frame and then | |
^CN (N=1 to 6), return | scrolling back through the earlier frames. | ||
|
| Freezes data output. This stops the data scrolling on the monitor to allow closer study or | |
F (no return) | a printout. This is a toggle switch command. Press the F key again to resume data | ||
|
| scrolling. | |
|
| Resets (unfreezes and clears) the History Status Report memory buffer. This erases the | |
G, return |
| alarm messages and meter indications that were stored immediately before and after a | |
| significant system fault. NOTE: Do not reset the History Status Report memory buffer | ||
|
| ||
|
| until operation and maintenance personnel have reviewed it as a troubleshooting tool. | |
|
| The data output stops (quits). The UPS communication system remains on | |
Q (no return) | ready to receive the next communication command. NOTE: To return to the beginning of | ||
the Event History or History Status Report, press Q, then request your desired report | |||
|
| ||
|
| again. | |
d mm/dd/yy, return | This entry sets the date (month/day/year) in the UPS system clock. You must include the | ||
slash (/) as you key in the date. Note that the d command must be lower case. | |||
|
| ||
t hh:mm:ss, return | This entry sets the time (hour:minute:second) in the UPS system clock. You must include | ||
the colon (:) as you key in the time. Note that the t command must be lower case. | |||
|
| ||
H, return |
| Prompts the UPS system to hang up its modem (only applicable to the modem | |
| communications port). | ||
|
| ||
I, return |
| Display Battery Cycle Monitor information for | |
J, return |
| Display Battery Cycle Monitor information for | |
K, return |
| Display Battery Cycle Monitor information for | |
L, return |
| Display Battery Cycle Monitor information for over 240 second discharge events. | |
M, return |
| Display Status Summary screen of battery discharge events. | |
N, return |
| Show detail information on all battery discharge events in order of occurrence | |
| (last in, first out). | ||
|
| ||
backspace |
| Moves cursor left to cancel previous entry or command. |
72