Liebert 1000kVA manual Electrical Specifications

Page 117

Specifications

5.5Electrical Specifications

RECTIFIER INPUT

 

Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC

Input Voltage

Standard voltages for 500 - 1000kVA units: 480 and 600VAC

 

Other voltages available on request. 3-phase, 3-wire plus ground.

Voltage Range

+10%, -15% (no battery discharge at -20%)

Frequency Range

57 Hz to 63 Hz

 

Less than 3 times normal full load input current for UPS models without optional

Subcycle Magnetization Inrush

input isolation transformer. Less than 8 times normal full load input current for

 

models with optional input isolation transformer and optional input filter

Input Current Walk-In

From 20% to 100% in 15-20 seconds

Current Limit

Maximum of 125% normal full load input current

 

Less than 30% reflected THD typical at normal full load input current. Less than 7%

 

reflected THD typical at normal full load input current with optional input filter

Current Distortion

500kVA to 750kVA models with optional 12-pulse rectifier: Less than 9% reflected

 

THD typical at normal full load input current. Less than 4% reflected THD typical at

 

normal full load input current with optional input filter

Power Factor

0.85 minimum lagging at full load

0.92 minimum lagging at full load with optional input filter

 

BYPASS INPUT

 

 

Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. 3-phase, 4-wire

Input Voltage

plus ground or 3-phase, 3-wire plus ground. Other optional voltages available.

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

 

 

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Range

±5% for manually initiated bypass transfer

±10% for automatically initiated uninterrupted transfer

 

Frequency Range

59.5 Hz to 60.5 Hz

Voltage Transient

±4% for manually initiated bypass transfer

CRITICAL LOAD OUTPUT

 

 

Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. Other optional

 

voltages available.

Output Voltage

SCC output: 3-phase, 3-wire plus ground or 3-phase, 4-wire plus ground

Module output to SCC: 3-phase, 4-wire plus ground (neutral required)

 

 

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

 

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Regulation

±0.5% for balanced load

±2% for unbalanced load

 

Voltage Adjustment Range

±5% manually

Line Drop Compensation Range

Up to +5% automatic load dependent

Frequency

595 Hz to 605 Hz

Slew Rate

0.01 to 1 Hz per second, adjustable

Phase Balancing

120° ±1° for balanced loads

120° ±3° for 50% unbalanced loads

 

Voltage Imbalance

 

20% Unbalanced Load

±1% from the arithmetic average of the 3 phases

50% Unbalanced Load

±2% from the arithmetic average of the 3 phases

Voltage Transient

 

20% Load Step

±4% RMS

50% Load Step

±4% RMS for 100-750kVA units; ±5% RMS for 1000kVA units

100% Load Step

±5% RMS for 100-750kVA units; ±8% RMS for 1000kVA units

Loss or Return of AC Input Power

±1% RMS

Manual Transfer of 100% Load

±4% RMS

Voltage Transient Recovery Time

To within 1% of steady state output voltage within 50 milliseconds

Voltage Harmonic Content

Maximum 5% RMS total, for any combination of linear and nonlinear loads

Maximum 3% RMS single, for linear loads

 

Module Overload Capacity

104% of full load rating continuously

at Full Output Voltage

125% of full load rating for 10 minutes

(System overload capacity depends on

150% of full load rating for 30 seconds

the configuration of on-line modules.)

(with ±2% voltage regulation)

 

Up to 300% of normal full load current subcycle; up to 500% of normal full load

Fault Clearing

current for up to 40 milliseconds with bypass available; up to 1000% of normal full

 

load current for up to 16 milliseconds with bypass available

111

Image 117
Contents Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions Multi-Module UPS, 100-500kVA System DescriptionMulti-Module UPS, 500-750kVA Reliability Types of System Control Cabinets SCCsDesigned for Success Input Power Failure Safety PrecautionsModes of Operation Other Factors to ConsiderOperator Controls 1989-2003 Options BatteryModule Battery Disconnect Battery Racks or CabinetsThree Breaker Maintenance Bypass Two Breaker Maintenance BypassSystem Control Cabinet General Component DescriptionsUPS Module Battery PlantDetailed Component Descriptions Controls HardwareSoftware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Fuse ProtectionShorted SCR Monitoring Static Switch Isolation Pulsed Parallel OperationLoad Transfers Transfer and Retransfer Conditions Retransfer Inhibited Redundant ModeDisplay Screen and Operator Controls Features500kVA 1000kVADescription Function Operation Refer to 3.4.5 Shutdown Procedures Numbers are used as keys to data in , belowDescription Location Function Switches behind SCC control panel door Menu tree Menu Tree NavigationMaster Menu Screen SCC Master MenuModule Master Menu Operation SCC Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic display screen Module Monitor/Mimic Display ScreenItem 5 Alarm Messages Alarm MessagesModule Display SCC DisplayMonitor/Mimic display example Utility fail KVA / 217 kW 325A 325A 325A MOD On Line OFF Line SUM ALM B-C C-A 0V 0V Not OK to Transfer Static Switch Connected Walk-in display screen during start-up Walk-In Display ScreenPresent Status Status Reports ScreensEvent History SCC Status ReportModule Status Report History status report screens History StatusAlarm in SCC Alarm in Module Alarm conditions that freeze history data gatheringSystem Status Battery Cycle Monitor-Module OnlyBattery cycle monitoring summary screen SCC system configuration screen System Configuration ScreensDate screen DateTime screen TimeAuto Dial Auto dial setting screenMaximum Auto-Retransfer Attempts Modem Baud RateLanguage Selection System Current RatingSystem Options Retransfer AttemptsContinuous Duty Static Switch Optional Battery test screen-MMU onlySCC and module remote monitor indications Remote MonitorModule alarm limit settings screen Alarm Limit Settings ScreenTemperature Limit Setting Optional Battery Float VoltageRefer to 3.4.3 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.4.1 SCC Start-Up Procedure for more details Start-Up Procedures ScreenModule start- up procedures screens Shutdown Procedures ScreenSCC shutdown procedures screen Battery time screen 15 minute discharge Battery Time Screen Module OnlyElapsed Time Minutes Upper Limit Actual Lower LimitOperation Meter calibration screen Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenSystem Status Messages Alarm and Status Messages Module Status MessagesAbbreviations used in alarm messages Load Block MessagesAbbreviation Definition Alarm messages meaning and corrective action Static Switch Manual ResetBypass Phase Control PowerInverter Fault Reverse PowerTransfer Module N OffOvertemperature Battery OvertempTimeout New AlarmAlarm messages summary Alarm MessageSpecial Functions Worldwide Reporting Communication InterfacesAuto-Dial Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Series 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Circuit breaker abbreviations Abbreviation Circuit Breaker OK to Transfer Load on BypassLoad on bypass, UPS available Momentary Overloads Momentary overload, pulsed static bypass switchInput power fail-load on battery Input Power Failure-Load on BatteryOne module off-line, load on UPS One Module Off-LineLoad on UPS-battery not available Off BatteryEmergency Modules Off Refer to 3.4.5 Shutdown ProceduresEmergency power off Remote Emergency Power OffSystem Shutdown Refer to 3.3.10 Maintenance BypassLoad on maintenance bypass, two breakers Manual Procedures SCC Start-Up ProcedureRefer to 3.5 Automatic Operations for more details Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Manual Transfer Instructions UPS Lead Load Transfer ProceduresMaintenance Bypass Load Transfers If the load is on Maintenance BypassIf the load is on the UPS System Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Remote Emergency Power Off Repo Automatic OperationsLocal Emergency Modules Off Lemo Automatic Transfers to Bypass Overloads Without Transfer1000% 150%Automatic Retransfers to UPS Automatic Module Off-LineAutomatic Emergency Modules Off Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentPower factor pf KVA RatingKVA Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Specifications 112 Page Company Behind the Products Technical Support/ServiceLocations United States