Battery Rating (Modules Only): This setting is a battery discharge rating in kilowatts under par- tial load for an extended period, typically 60 minutes. The UPS uses the two battery shutdown voltage settings and the two battery discharge ratings in computing rated and calculated time remaining dur- ing a discharge event.
Battery Float Voltage
Both the information entered here and the actual float setting in the hardware are determined based on the battery’s requirements. This information is generally available before factory testing and is set up at the factory. If the information is not available, it is set to the default of 540VDC.
Temperature Limit Setting (Optional)
This setting is visible when the optional
NOTE
The Low Battery alarm setting is designed to be useful at full load battery discharge rates. It is typically set for 10 volts above the