Operation
Table 9 | Alarm messages - meaning and corrective action | ||||
Alarm |
|
| Cabinet | Special |
|
Message |
| Location | Functions | Meaning and Corrective Action | |
AC INPUT |
|
|
|
|
|
|
|
|
|
| The rectifier input line voltage is outside of specified limits or the input |
|
|
|
|
| circuit breaker is opened while the battery circuit breaker remains closed. |
Input Fail |
|
| MMU | — | The battery supplies power to the critical load through the UPS inverter. |
|
|
|
|
| Provide an alternate source of AC power or prepare to initiate critical load |
|
|
|
|
| procedures when battery reserve time is low. |
DC BUS |
|
|
|
|
|
|
|
|
|
| Either the positive (+) or negative |
DC Ground Fault |
| MMU | D, L, S | shutdown occurs. | |
| Contact Liebert Global Services at once. Do not attempt to locate or repair | ||||
|
|
|
|
| |
|
|
|
|
| the fault. |
|
|
|
|
| At least one DC capacitor fuse has opened. The UPS module is taken off- |
DC Capacitor |
| MMU | D, F, S | line and the input and battery circuit breakers trip open. | |
Fuse Blown |
|
| Contact Liebert Global Services at once. Do not attempt to reset the | ||
|
|
|
| ||
|
|
|
|
| circuit breakers. |
|
|
|
|
| The module battery circuit breaker (MBD) is open. This circuit breaker can |
|
|
|
|
| be opened either manually or automatically in a UPS shutdown |
|
|
|
|
| procedure. If the UPS is operating with this breaker open, the critical |
Battery CB Open |
| MMU | D, R, S | load is not protected from loss of the utility source power. | |
|
|
|
|
| After AC power is restored and the DC bus is at 100% operating voltage, |
|
|
|
|
| manually close the battery circuit breaker so the rectifier can charge the |
|
|
|
|
| battery. |
|
|
|
|
| The battery is discharging. This occurs whenever the battery supplies |
|
|
|
|
| power to the load for more than 5 seconds because of input power failure, |
|
|
|
|
| a rectifier problem or an overload condition. If the input power or a source |
Battery |
|
| MMU | D, R, S | of auxiliary power is restored to the UPS module, the UPS automatically |
Discharging |
|
| returns to normal operation. | ||
|
|
|
| ||
|
|
|
|
| Watch the battery voltage carefully. Reduce the load (begin controlled |
|
|
|
|
| shutdown) to extend the battery |
|
|
|
|
| the input power is restored. The message clears after 30 seconds. |
|
|
|
|
| The battery voltage is approaching the minimum discharge voltage |
Low Battery |
|
| MMU | D, R, S | (approximately 5 minutes remaining). |
Warning |
|
| Complete the controlled shutdown of the critical load. Reset the alarms if | ||
|
|
|
| ||
|
|
|
|
| the input power is restored before shutdown. |
|
|
|
|
| The battery voltage has decreased to the minimum discharge value. The |
Low Battery |
|
|
|
| UPS module is taken |
|
| MMU | D, F, L, S | battery and input circuit breakers trip open. | |
Shutdown |
|
| |||
|
|
|
| Perform a UPS system | |
|
|
|
|
| |
|
|
|
|
| available. |
|
|
|
|
| The maximum preset value of the DC Bus voltage has been exceeded. |
DC Overvoltage |
|
|
| The UPS module is taken | |
| MMU | D, F, L, S | breakers trip open. | ||
Shutdown |
|
| |||
|
|
|
| Contact Liebert Global Services at once. A fault may have occurred within | |
|
|
|
|
| |
|
|
|
|
| the UPS. Do not attempt to reset the circuit breaker. |
BYPASS |
|
|
|
|
|
|
|
|
|
| The critical load is being supplied power from the bypass line and is |
Load On Bypass |
| SCC | D | therefore exposed to utility power disturbances. | |
| Clear all of the alarms before attempting to retransfer the load from the | ||||
|
|
|
|
| |
|
|
|
|
| bypass line to the UPS. |
Table 9 Abbreviations |
|
| |||
D = |
| L = latches |
|
| |
E = logs only; |
| R = remote |
|
| |
F = freezes; |
| S = summary |
|
|
D* =
D# =
65