Operation
Modem Baud Rate
This sets the transmission rate at which the system relays data to a terminal through the modem.
Figure 33 Modem baud rate
|
| UP: CURSOR UP |
|
| DOWN: CURSOR |
| AUTO DIAL SETTING SCREEN | SELECT: CHOOSE |
|
| |
|
|
|
EXIT |
|
|
Enable Auto Dial | YES | |
Enable Communication Check | NO | |
Modem Baud Rate | 2400 | |
Auto Dial Number | 1 800 | |
Second Number | 0 000 | |
Modem Initialization String | xxxxxxxxxxxxx | |
Set Communication Check Time | 00:00 |
To change the modem baud rate, do the following at the SCC:
1.From the System Configuration screen, press the Up or Down pad to move the highlighted cursor to Auto Dial.
2.Move to and select the Modem Baud Rate.
3.Press the Up or Down pad to display the desired baud rate.
4.Press the Select pad to set the baud rate and to return to the System Configuration screen.
Maximum Auto-Retransfer Attempts
When a UPS output overload condition exceeds a
If more than the selected number of overloads occurs during one hour, the critical load remains on the bypass line and must be manually retransferred to the UPS system. Note that you should determine the cause of any overload condition.
Note that automatic retransfers are initiated only if the critical load was transferred to the bypass line because of a system overload. If an automatic transfer to bypass occurred for any other reason, an automatic retransfer will not be initiated. Refer to 3.5.3 - Automatic Retransfers to UPS.
Figure 34 Maximum auto-retransfer attempts screen
© 1989-2003
MAX
LOWER INPUT
0
UP : INCREASE
DOWN : DECREASE
SELECT : EXIT
VALUE
3
UPPER LIMIT
5
48