Operation
Table 9 | Alarm messages - meaning and corrective action (continued) | |||||
Alarm |
|
| Cabinet | Special |
| |
Message |
| Location | Functions | Meaning and Corrective Action | ||
UPS SYSTEM (Cont’d.) |
|
| ||||
|
|
|
|
| The load on the UPS has exceeded the current versus time window of | |
Overload |
|
| SCC | D, F, L, S | system overload capacity. The UPS system transfers the load to bypass. | |
|
| Reduce the load. If the system does not initiate an automatic load | ||||
Transfer |
|
| ||||
|
|
|
| retransfer, manually retransfer the critical load from the bypass line to the | ||
|
|
|
|
| ||
|
|
|
|
| UPS. Reset the alarm. | |
|
|
| SCC | S | An alarm message (see lists in SCC and module remote monitor | |
Module Summary |
|
| indications and Other alarms that activate summary alarms in 3.2.6 - | |||
|
| |||||
|
| System Configuration Screens) or the watchdog timer has activated the | ||||
Alarm |
|
| MMU | R | ||
|
| Module Summary Alarm. | ||||
|
|
|
|
| ||
|
|
|
|
| Clear alarm conditions, if possible. | |
Module N Off |
| SCC | D | The output circuit breaker of Module N is open. The number N will identify | ||
|
|
| the module (1 through 6). | |||
|
|
| ||||
Line |
|
| MMU | R | ||
|
| Review active alarms at Module N and clear alarm conditions, if possible. | ||||
|
|
|
|
| ||
|
|
|
|
| Inverter output is not synchronized with the UPS system critical bus. This | |
Inverter |
|
|
|
| also means the output circuit breaker is open and should not be closed | |
|
| MMU | — | until the output is in sync. This condition may correct itself. If not, shut | ||
Nonsynchronized | ||||||
|
| down the UPS module and then perform a | ||||
|
|
|
|
| ||
|
|
|
|
| Contact Liebert Global Services if condition persists. | |
|
|
|
|
| The UPS output current has exceeded 175% of the rated full load or the | |
Overload |
|
|
|
| overload capacity has been exceeded. The UPS module is taken | |
|
| MMU | D, F, L, S | and shut down. | ||
Shutdown |
|
| ||||
|
|
|
| Contact Liebert Global Services at once. Do not attempt to reset circuit | ||
|
|
|
|
| ||
|
|
|
|
| breakers. | |
|
|
|
|
| Excessive reverse power flow from the critical bus into the UPS inverter | |
|
|
|
|
| has occurred, probably because of low inverter output voltage or a phase | |
Reverse Power |
| MMU | D, F, L, S | mismatch. The UPS module is taken | ||
|
|
|
|
| Contact Liebert Global Services immediately. Do not attempt to reset | |
|
|
|
|
| circuit breakers. | |
|
|
|
|
| At least one of the fuses has opened or a rectifier fault was detected. UPS | |
Rectifier Fuse |
| MMU | D, F, S | module is taken | ||
Blown |
|
| Contact Liebert Global Services immediately. Do not attempt to reset | |||
|
|
|
| |||
|
|
|
|
| circuit breakers. | |
|
|
|
|
| At least one of the fuses has opened or an inverter fault was detected. | |
Inverter Fault |
| MMU | D, F, S | The UPS module is taken | ||
| Contact Liebert Global Services immediately. Do not attempt to reset the | |||||
|
|
|
|
| ||
|
|
|
|
| circuit breakers. | |
Communication |
| SCC | S | The COM FAIL status message is as important as an alarm message. | ||
Failure |
|
| Refer to 3.2.14 - Alarm and Status Messages. | |||
|
|
|
| |||
|
|
|
|
| The optional Battery Cycle Monitor can retain information about the last | |
Battery Cycle |
|
|
| 132 battery discharge events. When the storage buffer approaches its | ||
| MMU | D, S | capacity, this warning message is broadcast via terminal and modem | |||
Buffer Warning |
| |||||
|
|
| communication channels and a complete listing of all records is sent to | |||
|
|
|
|
| ||
|
|
|
|
| the terminal port. The message clears after 30 seconds. | |
|
|
|
|
| Battery | |
|
|
|
|
| start, the following conditions must be valid: | |
|
|
|
|
| 1. No Battery Overtemp Alarm must exist. | |
|
|
|
|
| 2. Battery input and output circuit breakers must be closed. | |
Battery Exercise |
| MMU | — | 3. All three input volt phases must be within nominal range (+10%, | ||
| 4. DC volts must be greater than (DC Ref) | |||||
|
|
|
|
| ||
|
|
|
|
| nominal float voltage for 240 cells (the DC voltage reference setting) the | |
|
|
|
|
| DC voltage on the battery must be greater than 520VDC. | |
|
|
|
|
| 5. Battery charge must be greater than 90%. | |
|
|
|
|
| 6. Load must be greater than 15%. | |
Table 9 Abbreviations |
|
|
| |||
D = |
| L = latches |
|
| ||
E = logs only; |
| R = remote |
|
| ||
F = freezes; |
| S = summary |
|
|
D* =
D# =
67